3M™ Fire Barrier Sealant CP 25WB+
1, 2 3M™ Fire Barrier Sealant IC 15WB+
3M™ Fire Barrier Water tight Sealant 3000 WT
UL
Max 2" SDR 9 PEX (closed only). U300, U400,
or V400 series gypsum wallboard assemblies.
Max. diameter of opening 1½" larger than OD
of penetrant. Point contact to max. 1½" annular
space. Concentric or eccentric installations. 1 & 2
hour F rating. No mineral wool required.
Figure 3-13: Search results
Figure 3-14: Fire assembly document
Figure 3-16: Assembly criteria
Figure 3-15: Assembly drawing
Product Support Line
1-800-328-1687
WL
Gypsum2000 Series
Non-Metallic Pipes
Through Penetrations
3Fire Protection Products
3m.com/firestop
Product Support Line
1-800-328-1687
W-L-2547 • 1 of 1
1. Wall assembly – The 1 and 2 hr fire rated gypsum board/stud wall assemblies shall be constructed of the materials and in the manner
specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the
following construction features:
A. Studs – Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm)
lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum board* – Thickness, type, number of layers and fasteners as required in the individual Wall and Partition Design. Diameter of
opening shall be 1-1/2 in. (38 mm) larger than the outside diam of tubing (Items 2).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. The hourly T
Rating is 0 and 1-3/4 hr for 1 and 2 hr rated assemblies, respectively.
2. Crosslink polyethylene (PEX) tubing – Nom 2 in. (51 mm) diam (or smaller) SDR 9 PEX tubing for use in closed (process or supply)
piping system. Tubing installed concentrically or eccentrically within opening. Annular space between tubing and edge of opening to be min
0 in. to max 1-1/2 in. (38 mm). Tubing to be rigidly supported on both sides of wall assembly.
3. Fill, void or cavity materials* – caulk or sealant – Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with
both surfaces of wall assembly. An additional min 1/2 in. (13 mm) bead of fill material applied at the tubing/gypsum board interface at point
contact location on both surfaces of wall assembly.
3M COMPANY
3M FIRE PROTECTION PRODUCTS – CP 25WB+, IC 15WB+ or FB-3000 WT
*Bearing the UL classification mark
Reprinted from the online certifications directory with permission from Underwriters Laboratories Inc.
Copyright © 2010 Underwriters Laboratories Inc.®
System no. W-L-2547
August 04, 2009
F Ratings – 1 and 2 Hr (See item 1)
T Ratings – 0 and 1-3/4 Hr (See item 1)
Product Support Line
1-800-328-1687
WL
Gypsum2000 Series
Non-Metallic Pipes
Through Penetrations
3Fire Protection Products
3m.com/firestop
Product Support Line
1-800-328-1687
W-L-2547 • 1 of 1
1. Wall assembly – The 1 and 2 hr fire rated gypsum board/stud wall assemblies shall be constructed of the materials and in the manner
specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the
following construction features:
A. Studs – Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm)
lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum board* – Thickness, type, number of layers and fasteners as required in the individual Wall and Partition Design. Diameter of
opening shall be 1-1/2 in. (38 mm) larger than the outside diam of tubing (Items 2).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. The hourly T
Rating is 0 and 1-3/4 hr for 1 and 2 hr rated assemblies, respectively.
2. Crosslink polyethylene (PEX) tubing – Nom 2 in. (51 mm) diam (or smaller) SDR 9 PEX tubing for use in closed (process or supply)
piping system. Tubing installed concentrically or eccentrically within opening. Annular space between tubing and edge of opening to be min
0 in. to max 1-1/2 in. (38 mm). Tubing to be rigidly supported on both sides of wall assembly.
3. Fill, void or cavity materials* – caulk or sealant – Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with
both surfaces of wall assembly. An additional min 1/2 in. (13 mm) bead of fill material applied at the tubing/gypsum board interface at point
contact location on both surfaces of wall assembly.
3M COMPANY
3M FIRE PROTECTION PRODUCTS – CP 25WB+, IC 15WB+ or FB-3000 WT
*Bearing the UL classification mark
Reprinted from the online certifications directory with permission from Underwriters Laboratories Inc.
Copyright © 2010 Underwriters Laboratories Inc.®
System no. W-L-2547
August 04, 2009
F Ratings – 1 and 2 Hr (See item 1)
T Ratings – 0 and 1-3/4 Hr (See item 1)
1. Wall Assembly — The 1 and 2 hr re rated gypsum board/stud wall assemblies shall be constructed of the materials and in the manner specied in the individuals U300, U400 or V400 Series Wall
and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51mm by 102mm) lumber spaced
16 in. (406mm) o.c. Steel studs to be min 3½ in. (89mm) wide and spaced max 24 in. (610mm) o.c.
B. Gypsum Board* — Thickness, type, number of layers and fasteners as required in the individuals Wall and Partition Design. Diameter of opening shall be 1½ in.
(38mm) larger than the outside diameter of tubing (Items 2).
The hourly F Rating of the restop system is equal to the hourly re rating of the wall assembly in which it is install. The hourly T Rating is 0 and 1¾ hr for 1 and 2 hr rated
assemblies, respectively.
2. Crosslink Polyethylene (PEX) Tubing — Nom 2 in. (51mm) diameter (or smaller) SDR9 PEX tubing for use in closed (process or supply) piping system. Tubing installed concentrically or
eccentrically within opening. Annular space between tubing and edge of opening to be min 0 in. to max 1½ in. (38mm). Tubing to be rigidly supported on both sides of wall assembly.
3. Fill, Void or Cavity Materials* — Caulk or Sealant — Min ⅝ in. (16mm) thickness of ll materials applied within the annulus, ush with both surfaces of wall assembly. An additional min ½ in. (13
mm) bead of ll material applied at the tubing/gypsum board interface at point contact location on both surfaces of wall assembly.
3M Company
3M FIRE PROTECTION PRODUCTS — CP25WB+, IC15WB+ OR FB-3000WT
*Bearing the UL Classication Mark
Reprinted from the Online Certications Directory with permission from Underwriters Laboratories Inc.
Copyright © 2010 Underwriters Laboratories Inc.
®
Step four
Ensure the selected re
assembly document matches:
• Type of construction
• F rating of assembly
• Through penetrant dened
as crosslinked polyethylene
pipe or PEX pipe
• Range of pipe size being
installed
• Penetration hole size and
shape
• Firestop solution availability
(See Figures 3-14, 3-15 and
3-16.)
Note: It may be desirable to
select a restop product that
can be used for other MEP
system penetrations, such as
drain, waste and vent (DWV)
and conduit applications. This
can help ease coordination on
the jobsite during the restop
installation.
Refer to the respective
restop manufacturer for
more information pertaining
to the appropriate application
of their products. Be mindful
of information stated in the
published listings to ensure
compliance during installation.
Note: Ensure the required
restop material dened in the
assembly (i.e., sealant) does
not come into contact with
Uponor EP ttings. Assemblies
dene the penetrating item
as “PEX pipe” and therefore
only PEX pipe shall come
into contact with the required
restopping material.