User Guide
102 | uponorengineering.com
EP reducing
tees
Flow/port
Avg. C
v
Eq. length (ft)
½ x ½ x ¾ Branch 3.8 4.1
¾ x ½ x ½
Through 4.6 3.5
Branch 3.4 6.4
¾ x ½ x ¾
Through 5.4 2.3
Branch 5.4 16.1
¾ x ¾ x ½
Through 14.2 2.0
Branch 3.1 7.6
¾ x ¾ x 1 Branch 8.7 5.7
1 x ¾ x ¾
Through 12.8 2.4
Branch 5.3 16.7
1 x ¾ x 1
Through 12.9 2.4
Branch 10.5 15.1
1 x 1 x ½
Through 32.2 1.2
Branch 3.4 6.5
1 x 1 x ¾
Through 27.8 1.7
Branch 8.2 6.4
1¼ x 1 x ¾
Through 21.0 3.4
Branch 9.3 5.2
1¼ x 1 x 1
Through 11.7 11.0
Branch 8.4 23.0
EP tees Flow/port
Avg. C
v
Eq. length (ft)
½ x ½ x ½
Through 7.7 1.0
Branch 3.4 6.3
¾ x ¾ x ¾
Through 15.7 1.5
Branch 5.4 15.6
1 x 1 x 1
Through 30.5 1.3
Branch 11.3 12.7
1¼ x 1¼ x 1¼
Through 34.0 3.8
Branch 23.9 8.6
1½ x 1½ x 1½
Through 63.7 1.8
Branch 31.0 10.6
2 x 2 x 2
Through 150.7 0.8
Branch 52.5 15.5
2½ x 2½ x 2½
Through 197.2 2.7
Branch 81.5 22.3
3 x 3 x 3
Through 286.6 2.8
Branch 122.8 23.9
EP reducing
tees
Flow/port
Avg. C
v
Eq. length (ft)
1¼ x 1¼ x ½
Through 45.2 1.9
Branch 4.1 3.9
1¼ x 1¼ x ¾
Through 43.4 2.3
Branch 8.9 5.7
1¼ x 1¼ x 1
Through 33.0 4.2
Branch 15.8 6.3
1½ x 1 x ¾
Through 19.5 4.0
Branch 9.3 5.1
1½ x 1 x 1
Through 18.9 4.3
Branch 15.6 6.5
1½ x 1 x 1½
Through 19.1 4.2
Branch 26.5 14.9
1½ x 1¼ x ¾
Through 33.1 4.2
Branch 6.3 11.3
1½ x 1¼ x 1
Through 36.4 3.1
Branch 11.2 13.1
1½ x 1¼ x 1¼
Through 45.4 2.0
Branch 17.0 17.7
1½ x 1½ x ½
Through 60.5 2.4
Branch 3.4 6.3
1½ x 1½ x ¾
Through 56.0 2.9
Branch 9.0 5.4
1½ x 1½ x 1
Through 53.8 3.1
Branch 15.3 6.9
1½ x 1½ x 1¼
Through 54.3 3.2
Branch 33.7 4.1
2 x 1½ x ¾
Through 43.5 4.9
Branch 8.4 6.2
2 x 1½ x 1
Through 42.4 5.5
Branch 13.9 8.4
2 x 1½ x 1¼
Through 41.8 5.6
Branch 22.0 10.3
2 x 1½ x 1½
Through 42.1 5.4
Branch 28.5 13.0
2 x 1½ x 2
Through 38.6 6.6
Branch 51.8 16.1
2 x 2 x ½
Through 111.1 2.7
Branch 4.3 4.0
2 x 2 x ¾
Through 115.0 2.7
Branch 8.2 6.8
Fitting equivalent length and C
v
data