Component Alarms/Issues Causes Solutions Notes
Thermostat or
Actuator
Room too cold
Thermostat setting is too
low (corresponding LEDs
ashing).
Press + or – key to
display and change the
temperature setpoint on the
thermometer.
Use minimum and maximum
limitations to protect system
from consequences of
unreasonable temperature
settings.
Thermostat inuenced by
a heat source (temperature
displayed drops when
thermostat is moved)
Change the location of the
thermostat.
Thermostats are mixed up. Place each thermostat in the
room supplied by the loops.
• Actuator doesn't open.
The white indicator doesn't
display in the indicator
window.
Replace the actuator. See Installation Report to
contact an installer.
ECO in room information
menu
Change ECO prole or
assign another prole to
the room.
End the ECO period by
pressing a thermostat key.
Temperature displayed
in the room information
menu is lower than the
temperature on the
thermostat.
Change minimum and
maximum limitation.
Thermostats of single rooms
are mixed up.
See Installation Report
and the base unit/
channel numbering under
thermostat battery cover.
Force thermostat to
transmit and check the
corresponding LEDs are
ashing.
Place the thermostat in
the room supplied by the
loops controlled by the
thermostat.
Thermostat
Room temperature
OK, but the oor is
cold.
Supply system defect: no
warm water in manifold.
Check boiler and circulation
pump.
All rooms are cold.
Vacation mode still on End vacation mode
ECO mode Change ECO prole or
assign another prole to
the room.
End the ECO period by
pressing all thermostat
keys.
Table 10-1: Troubleshooting Solutions (cont.)