Submittal Sheet
SetPoint 521, Programmable Thermostat with Floor Sensor
Submittal Information
Revision A: Jan. 15, 2016
Project Information
Job Name:
Location:
Part No. Ordered:
Engineer:
Date Submitted:
Contractor:
Submitted By:
Manufacturer’s Representative:
Approved By:
Technical Data
Control:
Microprocessor control
Ambient conditions:
Indoor Use Only, 32°F (0°C) to 122°F (50°C)
≤90% RH non-condensing
Power supply: 10 to 30V (ac/dc), 50/60 Hz, 1.8 VA, Class II
Relay: 30V (ac/dc), 2 A, Class II circuits
Floor Sensor
(A3040079):
NTC thermistor, 10 kΩ at 77°F (25°C ±0.2°C)
Enclosure:
316 stainless steel, 10ꞌ (3m) 24 AWG, 300-volt,
PVC-insulated zipcord
Operating range: -58°F to 221°F (-50°C to 105°C)
Product Information and Application Use
The SetPoint 521, Programmable Thermostat with Floor Sensor is
designed to provide three different modes of operation: single-stage
heating, two stages of heating with a fan, or one stage of heating and one
stage of cooling with a fan. Auxiliary sensors may be added to measure
floor, outdoor or room temperature. Uponor Floor Sensor (A3040079) is
included to measure floor temperature to protect the floor from
overheating and enhance comfort. Programmable schedules support
either a 7-day or 24-hour schedule with two or four events per day.
Description Part Number Length Width Depth Weight
Setpoint 521, Programmable Thermostat with Floor Sensor
Floor Sensor, replacement part
A3040521
A3040079
3.0"
1.5"
3.6875"
0.1875"
0.9375"
n/a
0.60 lbs.
0.10 lbs.
Installation
Install the thermostat on an interior wall of the desired zone approximately 5 feet above the floor. Do not mount the thermostat on a location
that may be affected by localized heat sources or cold drafts. It may be necessary to install a draft barrier behind the thermostat to prevent
air from blowing through the wiring hole which can affect the thermostat’s built-in sensor. Refer to the Uponor SetPoint 521 Programmable
Thermostat with Floor Sensor Installation and Operation Manual for more information.
Accessories
Cover Plate for SetPoint 521 Thermostat (A3040012)
Standards
N/A
Codes
N/A
Listings/Approvals
Thermostat: Meets Class B: ICES and FCC Part 15, CE
Floor Sensor: CSA C US
Related Applications
Contact Information
Radiant Heating and Cooling Systems
Uponor, Inc.
5925 148
th
Street West
Apple Valley, MN 55124 USA
Phone: 800.321.4739
Fax: 952.891.2008
www.uponorpro.com