Install Instructions

6
www.uponorpro.com
Connecting Tubing to the Manifold
Connect the tubing to the manifold using either the ProPEX connection method or
QS-style fittings. Refer to the Uponor Product Catalog for fitting information.
ProPEX Connections
Square-cut the Tubing
Slide ProPEX Ring onto Tubing
Expand the Tubing
1. Use a PEX Cutter (E6081125, E6081128
or E6081501) to square-cut the tubing
perpendicular to the tubing length.
Note: Do not use a saw or similar cutting
tool as shavings may clog the manifold valves.
2. Slide the ProPEX Ring over the end of the tubing
until it reaches the stop edge.
Note: Ensure the ring is dry and free of grease to
prevent it from sliding out of place.
3. Attach the proper size ProPEX Expander Head onto
the expander tool and expand the tubing with the
proper number of expansions (see Table 1).
4. After expanding the tubing and ring, immediately
remove the expander tool and slide the tubing over
the fitting until the tubing reaches the stop on the
fitting. Hold the tubing in place for two or three
seconds to ensure a proper seal.
QS-style Fittings
1. When connecting the tubing with a QS-style fitting,
make sure the tubing is pushed all the way into the
fitting and tighten the fitting with a wrench.
Note: Do not over-tighten or twist the tubing.
2. If you need to remove a QS-style fitting from the
tubing, use a screwdriver to open the clamp ring
and remove the insert.
Table 1: Recommended Number of ProPEX Expansions
*H refers to Uponor H-series expander heads.
Tubing
Size
Milwaukee® ProPEX Tool Uponor ProPEX Tool
M12 M18 Manual 100 & 150
3
/8" 8 9 5 7
1
/2" 5 6 4 4
3
/4" 9 8 9 9H*
1 mm
Use a Screwdriver to Open
Clamp Ring and Remove Fitting
1
2
2
4