Install Instructions

20
www.uponorpro.com
20
Section 11
Technical Data
Technical Data
Connection Dimensions R32
Max. Operating Temperature and Pressure
6 bar at 60°C
87 psi at 140°F
5 bar at 70°C
72 psi at 158°F
4 bar at 80°C
58 psi at 176°F
3 bar at 90°C
44 psi at 194°F
Max. Test Pressure
(24 h, ≤ 86°F)
10 bar/145 psi
Max. Water Flow per Manifold 0.97
L
/
S
or 15.4 gpm
Cv Value Inlet/Outlet Valves 1.40
Adaptable Thermal Actuators
EP Heating Manifold Two-wire
Actuator (A3030522)
or
Thermal Actuator, four wire
(A3010522) with EP Heating
Manifold Actuator Adaptor
(A2671300)
Available Sizes
2 to 8 heating/cooling
loop connections
Table 11-1: Technical Data