Overview of Primary Product

Engineered Plastic (EP) Heating Manifold Single Section
with Isolation Valve
Submittal Information
Revision A: Dec. 1, 2008
Project Information
Job Name:
Location: Part No. Ordered:
Engineer: Date Submitted:
Contractor: Submitted By:
Manufacturer’s Representative: Approved By:
Technical Data
Manifold:
PA66-GF30 Max. Test Pressure (24 h,
86°F) tested with water:
145 psi (10 bar)
Valve Insert,
Handwheels:
POM
Max. Test Pressure (24 h,
70°F) tested with air:
100 psi (7 bar)
Metal
Inserts:
Brass C38500 Max. Water Flow per
Manifold:
0.97 l/s 15.4 gpm
Axel: Stainless
Steel
Cv Value Inlet/Outlet
Valves:
1.35
Spring:
Stainless
Steel
Connection Dimensions: R32
O-ring:
EPDM Adaptable
Actuators:
EP Heating Manifold, two-wire Actuator
(A3030522); Thermal Actuator, four-wire
(A3010522) with EP Heating Manifold Actuator
Adaptor (A2671300)
Max. Operating
Temperature and
Pressure:
6 bar at 60°C
87 psi at 140°F
5 bar at 70°C
72 psi at 158°F
4 bar at 80°C
58 psi at 176°F
3 bar at 90°C
44 psi at 194°F
Product Information and Application Use
The Engineered Plastic (EP) Heating Manifold Single Section with Isolation Valve (A2670001)
adds additional loops to an EP Heating Manifold assembly for use in hydronic radiant heating
and cooling systems. Use only propylene glycol in radiant systems with EP Heating Manifolds;
never use ethylene glycol.
9
Description Part Number Height Width
Weight
EP Heating Manifold Single Section with Isolation Valve A2670001 4.6" 2.0" 0.30 lbs.
EP Heating Manifold Isolation Valve Body, replacement part A2670004 4.6" 2.0" 0.30 lbs.
EP Heating Manifold Valve Replacement Tool A2670007 4.6" 2.0" 0.30 lbs.
EP Heating Manifold Replacement O-ring A2670008 4.6" 2.0" 0.30 lbs.
Installation
Select the proper bracket spacing for the manifold and mount the bracket to the wall. Snap the manifold to the bracket. For additional
information, refer to the instruction sheet. Note: Use only propylene glycol in radiant heating and cooling systems with EP Heating
Manifolds; never use ethylene glycol. Refer to the EP Heating Manifold Installation Guide for a complete chemicals list.
Standards/Codes/Listings
N/A
Related Applications Contact Information
Radiant Heating and Cooling Systems
Snow and Ice Melting Systems
Permafrost Protection Systems
Turf Conditioning Systems
Uponor, Inc.
5925 148
th
Street West
Apple Valley, MN 55124 USA
Phone: (800) 321-4739
Fax: (952) 891-2008
www.uponor-usa.com
Uponor Ltd.
2000 Argentia Road, Plaza 1, Suite 200
Mississauga, ON L5N 1W1 CANADA
Phone: (888) 994-7726
Fax: (800) 638-9517
www.uponor.ca

Summary of content (1 pages)