Specification

L: 13.0in (330 mm)
W: 6.76in (171.7 mm)
H: 8.27in (210 mm)
TH: 9.33in (237 mm)
Tolerances are +/- 0.04 in. (+/- 1mm)
and +/- 0.08 in. (+/- 2mm) for height
dimensions. All data subject to
change without notice.
Terminals
Marine Combo Post
5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HRF.V/Time
361.1 269.3 189.5 114.7 59.9 34.9 25.6 20.0 16.5 11.6 10.5 5.79.60V
325.2 245.4 169.6 108.7 56.3 33.3 24.9 19.5 16.2 11.4 10.2 5.510.20V
313.2 233.4 159.6 105.7 54.9 32.5 24.3 19.2 16.0 11.3 10.0 5.510.50V
301.2 221.4 149.6 102.7 52.9 31.7 23.7 18.9 15.6 11.0 10.0 5.410.80V
289.3 209.5 139.7 99.8 50.9 30.9 22.9 18.3 15.2 10.7 9.5 5.111.10V
5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HRF.V/Time
3919.2 2959.6 2013.0 1217.9 693.3 404.0 297.3 231.4 190.5 134.7 121.7 65.59.60V
3610.0 2724.2 1882.3 1207.0 651.4 386.0 289.3 225.4 149.7 131.7 118.7 63.810.20V
3552.1 2647.4 1809.5 1199.0 630.4 377.1 282.3 221.4 184.5 130.7 116.7 63.010.50V
3506.2 2577.5 1741.6 1196.0 613.5 369.1 276.3 217.5 181.5 127.7 115.7 62.710.80V
3442.4 2492.8 1661.8 1187.0 605.5 368.1 273.3 216.5 180.5 126.7 112.7 60.811.10V
Nominal Voltage
Nominal Capacity
20-hr. (5.50A)
10-hr. (10.2A)
5-hr. (18.7A)
1-hr. (66.0A)
Approximate Weight
Internal Resistance (approx.)
Shelf Life (% of normal capacity at 68º F (20º C)
3 Months 6 Months 12 Months
Temperature Dependancy of Capacity
12 volts
110 Ah
102 Ah
93.5 Ah
66.0 Ah
33.0 A or smaller
14.6 - 14.8 V
77º F (25º C)
(20 hour rate)
65.5 lbs (29.0 kgs)
5m
91% 83% 64%
102% 100% 85%
Charge Method
65%
(Constant Voltage)
Cycle Use
Float Use
Initial Current
Control Voltage
13.6 - 13.8 V
Control Voltage
(Repeating Use)
13.0 (330)
8.27 (210)
9.33 (237.0)
6.76 (171.7)
Edge of Battery
2.09 (53.1)
1.06 (27.0)
.31 (7.9)
2.28 (57.9)
.33
(8.4)
1.51 (38.4)
.74 (18.8)
1.00 (25.4)
488 S. Royal Lane Coppell, Texas 75019 P 469.892.1122 T 866.892.1122 F 469.892.1123 sales@upgi.com
www.kinetikpower.com
Y1801-2
All specications are subject to change without notice.
AGM Operational Temperature
AGM Storage Temperature
(0 C to 40 C)32 F to 104 F
5 F to 113 F
5 F to 104 F
(-15 C to 45 C)
Charge
Discharge
(-15 C to 40 C)
Absorbant Glass Mat (AGM) technology for superior performance. Valve regulated, spill proof construction
allows safe operation in any position. Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certied.
U.L. recognized under le number MH 20567.
UPG No. 40603
Maintenance-Free
KINETIK MARINE
SEALED LEAD-ACID BATTERY
Specification
Physical Dimensions: in (mm)
Constant Current Discharge Characteristics Unit: A (25 C, 77 F)
Constant Power Discharge Characteristics Unit: W (25 C, 77 F)
Due to continuous improvements to our products, product may vary slightly from depiction.
104 F (40 C) 77 F (25 C) 32 F (0 C) 5 F (-15 C)
Copyright 2018 Universal Power Group, Inc. All rights reserved.
C

Summary of content (2 pages)