Technical data

Level Display
Operation
4-36
P/N 7135049A
E 2007 Nordson Corporation
VBC_Siemens
Melter (contd.)
Level (Option)
If the melter is heated up and there are no undertemperature faults or
sensor alarms (short-circuit / sensor break), the command to fill is given as
soon as the level reaches or falls below the value Start at.
Filling continues until the level has reached or exceeded Stop at. All values
are shown as a percentage of the tank volume.
The status diode is lit during filling.
Activate and Deactivate Level Control
Level control is activated and deactivated by pressing .
Level display and monitoring no longer occur when level control is
deactivated. Now the tank can be emptied for maintenance or repair work
without the fault Tank empty occurring.
Fig. 4-41 V13
Start at: 10 %
Stop at: 80 %
Low level warning: 10 %