Technical data
Operation
4-28
P/N 7135049A
E 2007 Nordson Corporation
VBC_Siemens
Parameters (Screen 3)
NOTE: To be able to work on the parameter level, the password for level 2
(trained personnel) must first be entered.
Control parameters
The PID control parameters can be selected as desired in this screen.
NOTE: Should be adjusted only by personnel with experience in metrology
and control technology.
NOTE: The I-component can be deactivated with the value 0.
Fig. 4-25 T4
Assigning Temperature Channel to a Group
Defining Groups
All temperature channels (except for grid and reservoir) can be combined to
application groups Group A to Group H. Channels not assigned to any
group belong to No group.
Of the eight possible application groups, four can be switched via the
control panel as well as via the interface Standard I/O; the others can be
switched only via the control panel (Refer to Standard I/O Group Inputs).
Example:
1. Select temperature channel.
2. Select group letter, e.g. Group A.
A different group letter can be selected by repeatedly pressing the group
key.
If several temperature channels are to be combined to one group:
1. Select temperature channel.
2. Select desired group.