Undertemperature Interlock
The undertemperature interlock prevents the melter motors from being
switched on as long as the material is too cold and thus too thick. This could
damage the pumps.
The undertemperature interlock is active during every Heatup phase (status
display) and after every standby. Also refer to section Troubleshooting,
Undertemperature Fault Triggered. If the system ready delay time is
activated, this time must also have expired before the interlock is disabled.
Motor Startup Protection
The motor startup protection prevents the motors from starting up on their
own after heatup or after a fault. The melter goes to startup protection if at
least one motor was running before heatup or before the fault occurred.
Condition for Motor running: All motors ON and Enable motor
When the system is ready again (status display), the motors can be
switched on again via the control panel or the interface Standard I/O.
Acknowledge Startup Protection
On the Control Panel
Press the key Switch on/off all motors (collective enable); startup
protection is acknowledged and all enabled motors run again.
Via Interface Standard I/O
Switch All motors ON/OFF from OFF to ON. All enabled motors run again.
Via Field Bus
Set All motors ON/OFF (collective enable). (rising edge; refer to Melter
control: If bit 1 = 0, then set to 1. If bit 1 = 1, set to 0 then back to 1). All
enabled motors are running again.