Technical data
Index Protocols and Communication Data List
B-35
P/N 7135049A
E 2007 Nordson Corporation
VBC_Siemens
Data
index
Data designation Channel
number
Setting range,
resolution
Inert gas
15 Melter status and alarms (Also refer to melter) 0 Bit field −
[R]
Bit 7 Value: 1 Status: Inert gas injection
0 Status: No inert gas injection
170 Switching on/off inert gas injection (manual) 0 0 / 1 0
0: Switching off
1: Switching on
171 Gas on duration 0 2 − 120 s 5
172 Gas off duration 0 2 − 120 min 30
173 Reserved
174 Reserved
Level
Index 15 Bit 6 and 13 only with 5-point sensor
(fixed measuring points)
Index 190 to 193 only with analog level sensor
(variable measuring points)
15 Melter status and alarms (Also refer to melter) 0 Bit field −
Bit 6 Reserved
Bit 9 Value: 1 Status: Tank is being filled
0 Status: Tank is not being filled
Bit 10 Value: 1 Alarm: Tank overfilled (warning)
0 No alarm
Bit 11 Value: 1 Alarm: Tank level is low (warning)
0 No alarm
Bit 12 Value: 1 Alarm: Tank empty (fault)
0 No alarm
Bit 13 Reserved
190
[R]
Actual level 0 0 − 100 % −
191 Start (filling) at 0 5 − 98 % 10
192 Stop (filling) at 0 5 − 98 % 80
193 Warning Tank level low 0 5 − 90 % 10