Installation manual

3/11
3
3.1
Functions,
characteristics
Modicon TSX Micro
automation platform 0
Process control of semi-continuous processes
The CCX 17 industrial operator panel displays and controls all the PID controller
parameters which can be modified without having to program the Micro or
Premium PLC application program.
The PID_MMI man-machine interface function, included in the PL7 Junior software,
provides an application program on the CCX 17 industrial operator panel for
controlling and adjusting PID loops.
It enables the CCX 17 operator panel to manage:
b Selection of a PID loop.
b Display and control of that PID loop.
b Adjustment of the PID loop parameters.
This man-machine interface function is easily installed for any man-machine
interface application on the CCX 17 operator panel. The three preconfigured screens
enable the required operations to be performed on any PID controller.
The CCX 17 operator panel can manage up to 9 PID controllers. Installation of the
man-machine interface function is simple and is performed as follows:
b The PID_MMI function is activated on each scan of the TSX Micro or Premium
PLC (unconditional call-up).
b A single call-up of the PID_MMI function manages all the PID loops in the
TSX Micro or Premium PLC -application.
Control and man-machine interface functions
Ex
Rf
MOD
1: LIBELLE1
4: LIBELLE4
7: LIBELLE7
2: LIBELLE2
5: LIBELLE5
8: LIBELLE8
3: LIBELLE3
6: LIBELLE6
9: LIBELLE9
LOOp SELECT
P
ID loop selection screen
MOD
UP
DN
PV
SP
OUT
LIBELLE2
:
:
:
SUP
INF
:
:
P
ID loop control screen
AUTO
Sa
MOD
UP
DN
P
ID loop adjustment screen
TI(s)
TS(s)
OUT_MAX
LIBELLE2
:
:
:
KP
TD(s)
PV_DEV
OUT_MIN
:
:
:
:
resentation:
age 3/10
References:
page 3/13
Characteristics
Function PID Type Universal, serial/parallel structure
Maximum number Limited by the number of analogue modules and by the memory data capacity
Sampling period Adjustable from 10 ms to 5 min 20 s
Operating mode Smooth changeover manual/automatic
Measurement Direct measurement in 0/10 000 format
Control Continuous output in 0/10 000 format
Proportional gain Adjustable from - 100...+ 100
Integral action Time adjustable from 0…2000 s. Integral saturation. Pure integration operation
Derivative action Time adjustable from 0…1000 s on measurement or deviation
Execution time (ms)
TSX
37 05/08/10
TSX 37 21/22 TSX 57 10 TSX 57 20
Internal RAM Cartridge Internal RAM Cartridge
No man-machine interface 1.08 0.9 0.96 1.5 0.9 1
Man-machine interface 1.32 1.1 1.17 1.7 1.1 1.2
Process control
functions with pulses
outputs
PWM Type
Pulse width modulation
Modulation period
Adjustable from 0…327.67 s
Execution time (ms)
0.6 0.5 0.53 0.7 0.5 0.56
SERVO Type Position control of bidirectional motorised actuator (±)
Operating mode
v with position feedback: with discrete servo control with adjustable hysteresis
v without position feedback: pulse widths are proportional to the PID output variation. Setting
parameters for valve opening times and minimum pulse duration.
Execution time (ms)
0.96 0.8 0.85 1 0.8 0.89
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com