Installation manual

3/4
3
3.1
Presentation,
description
Modicon TSX Micro
automation platform 0
Integrated analogue channels and analogue I/O
modules
TSX Micro PLCs provide three ways of performing analogue processing:
b With input half format TSX AEZ ppp modules, and TSX ASZ ppp analogue
outputs modules and TSX AMZ 600 analogue I/O installed in the available slots
(base or mini extension rack).
b Or by using the analogue I/O integrated into TSX 37 22 PLC bases.
b Or by using Nano remote analogue I/O extension modules (see pages
2/25
and
2/26
).
b The maximum number of analogue modules in a TSX Micro PLC configuration is:
v 2, for a TSX 37 05/08/10 configuration,
v 4, for a TSX 37 21/22 configuration (2 TSX ASZ 200/TSX AMZ 600 modules
maximum in the base).
These analogue input or output modules are always connected via screw terminal
blocks.
TSX AEZ/ASZ/AMZ analogue I/O modules comprise:
1 Rigid metal casing.
2 Locking system for fixing the module in its slot. This system can only be accessed
when the screw terminal block is removed.
3 Module reference label.
4 Connector for fitting screw terminal block.
Connection equipment supplied with each module:
5 TSX BLZ H01 removable screw terminal block for connection of analogue sensors
and actuators.
Eight 0...10 V inputs and one 0...10 V output are integrated in TSX 37 22 PLC bases.
These integrated channels can receive the TSX ACZ 03 adjustment/adaptor
module, which enables:
b The use of 4 potentiometers for the user to adjust the 4 application constants
(setpoint, threshold, etc.).
b Conversion of 0...10 V inputs to 0...20 mA or 4...20 mA inputs.
b Conversion of 8 0...10 V inputs to 8 c 24 V discrete inputs.
1 A 15-pin SUB-D type connector for connecting the analogue
sensors/pre-actuators or mounting the TSX ACZ 03 adaptor.
2 A 15-way SUB-D type connector for connecting the analogue
sensors/preactuators or the discrete sensors.
3 Potentiometers for adjusting the first 4 input channels.
The Telefast 2 pre-wired system facilitates installation of modules by providing
access to inputs via screw terminal blocks.
Connection is via a TSX CCP S15 ppp shielded cable (length 0.5 to 2.5 m) fitted
with SUB-D type connectors at each end.
The ABE 7CPA01 wiring connection base is used to connect the following:
b 8 analogue inputs (or 8 c 24 V discrete inputs with TSX ACZ 03 adaptor module).
b 1 analogue output.
b 1 c 10 V reference output for using 4 external potentiometers for the last
4 channels (4.7 k, precision ± 20 % maximum), if required.
Presentation
1
2
3
4
5
Description
TSX AEZ/ASZ/AMZ analogue I/O modules
2
3
1
TSX 37 22
TSX ACZ 03
TSX 37 22
ABE 7CPA01
TSX CCP S15
Drive
Integrated analogue I/O
Connection principle for integrated analogue channels using the Telefast 2 pre-wired system
unctions:
ages 3/5 and 3/6
Characteristics:
pages 3/7 and 3/8
References:
page 3/9
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
efesotomasyon - telemecanique inverter