Power supplies for d.c. control circuits
Phaseo regulated switch mode power supplies
Technical characteristics
Type of power supply ABL-7REQ24p ABL-7UEQ24p ABL-7UES24p ABL-7UPS24p
Product certifications
cULus, c us
Conforming to standards
Safety EN 60950
EMC
EN 50081-1, EN 50082-2
Low frequency harmonic currents
EN 61000-3-2
Input circuit
LED indication
Input voltages
Rated values V a 2 x 380…415 a 3 x 380…415 a 3 x 400…520 a 3 x 400…520
Permissible values
V a 2 x 340…460 a 3 x 340…460 a 3 x 360…550 a 3 x 360…550
Permissible frequencies
Hz 50…60
Efficiency at nominal load
> 85 % > 90 %
Current consumption
Ue = 400 V A 0.65 (120 W)/1.2
(240 W)
0.75 (240 W)/1.5
(480 W)
0.7 (240 W)/1.2 (480 W)/1.7 (960 W)
Current at switch-on
A <35
Power factor
0.6 0.55 0.7 0.7/0.9 (960 W)
2-phase operating mode
V Relaxation if input voltage < a 450
Output circuit
LED indication Green LED
Nominal output voltage (U out)
V c 24
Nominal output current A 5/10 10/20 5 10/20/40
Precision
Output voltage Adjustable from 100 to 116%
Line and load regulation
1 % max
Residual ripple - interference
mV < 200 (peak-peak)
Micro-breaks
Holding time for I max and Ve min ms 15 10 Between 8 and 13
Temporary overloads
Permissible inrush current (U out >19V) See curves, page 2/59
Protection
Short-circuit Permanent/automatic or normal restart
Overload
1.20 In < 50 ms
Overvoltage
V 28.5 typical
Undervoltage
V 19 typical
Operating and environmental characteristics
Connections Input mm
2
2 x 1.5…2.5 mm
2
+ earth
Output
mm
2
4 x 1.5…2.5 mm
2
4 x 4…6 mm
2
4 x 1.5…2.5 mm
2
4 x 1.5…2.5 mm
2
+ earth
(240 W)
4 x 4…6 mm
2
+ earth (480 W)
4 x 4…10 mm
2
+ earth (960 W)
Ambient
conditions
Storage temperature
°C - 25…+ 70
Operating temperature
°C 0° C…+ 60° C
Maximum relative humidity
30…90 %
Degree of protection
IP 20 or IP XXB
Vibrations
Conforming to IEC 61131-2
Operating position
Vertical
MTBF
> 100 000 h
Connections Series
Possible
Parallel
See page 2/58
Dielectric
strength
Input/output 3750 V/50 and 60 Hz 1 min
Input/earth
3500 V/50 and 60 Hz 1 min
Output/earth (and output/output)
500 V/50 and 60 Hz 1 min
Input fuse incorporated
No
Disturbance Conducted/radiated
EN 55011/EN 5022 - class B
Immunity Electrostatic discharge
EN 61000-4-2 (4 kV contact/8 kV air)
Electromagnetic
EN 61000-4-3 level 3 (10 V/m)
Conducted interference
EN 61000-4-4 level 3 (2 kV) , EN 61000-4-5, EN 61000-4-6 level3, EN 61000-4-8 level 4 (for
ABL-7RE/RP)
Mains interference
EN 61000-4-11 (voltage drops and cuts)