Installation manual

2/46
2
2.2
7
2
2
5
4
1
6
3
1
2
3
Tego Power is a modular system which standardises and simplifies the
implementation of motor power-starters with its prewired control and power circuits.
Hence, installation of a motor power-starter is quick, simple, safe and flexible with no
wires needed for connection. In addition, this system enables the motor
power-starter to be customised at a later date. The system reduces maintenance
time and optimises panel space, by reducing the number of terminals, the amount of
ducting and intermediate interfaces.
Two solutions are offered :
b A solution using Quickfit technology for TeSys motor power-starter components with
spring terminals : model d contactors (9 to 32 A) and the GV2-ME motor circuit-breaker.
b A solution for TeSys motor power-starter components with screw terminals : model
d (9 to 18 A) and model k (6 to 12 A) contactors and GV2 motor circuit-breakers.
Tego Power Design definition software
This software on CD-ROM enables the motor power-starter application to be
graphically defined according to the circuit-breakers and contactors used.
It determines which Tego Power products are required for the application.
Referencing labels can also be created for the starters.
The motor power-starters concerned are those formed by combining :
b GV2-M circuit-breakers,
b with 9 to 32 A model d (LC1) contactors.
Consisting of simple parts, Tego Power Quickfit technology is used to create motor
starter assemblies up to 15 kW/400 V.
The main components which make up this range are :
For the power circuit
b a power kit comprising, for each starter, a plate
1
for mounting the contactor and
the circuit-breaker, and the two power connection modules
2
,
b a power splitter box
5
for 2 or 4 starters,
b an upstream terminal block
6
for a power supply up to 63 A (16 mm
2
),
b a downstream terminal block
7
for connecting the motor power supply cables
and the earth cables (6 mm
2
).
For the control circuit
b a control splitter box
3
for 2 or 4 starters, with control-command data on HE 10
connector. The data on 4 to 8 starters can be fed back directly to the PLC via an 8I/8O
or 16I/8O Telefast cable or to a fieldbus module (AS-i, Fipio, CANopen, DeviceNet,
Interbus, Profibus) (see opposite page).
b a control circuit connection module
4
which plugs directly into the contactor and
the circuit-breaker on each starter. This module concentrates the motor starter
control-command data. It integrates the circuit-breaker status data in the prewiring of
the contactor control circuit.
The motor power-starters concerned are those formed by combining :
b GV2 circuit-breakers (mainly GV2-ME and GV2 P),
b with 6 to 12 A model k contactors (LC1, LP1, LC2, LP2, LP4, LP5) and 9 to 18 A
model d contactors (LC1).
The main components which make up this range are :
b modular sub-bases
1
for 2 or 4 direct or reversing contactors, consisting of a
prefabricated power busbar system and a control-command circuit. These sub-bases
can be combined to form a variable configuration of 2, 4, 6 or 8 direct starters.
b the sub-base interconnection kit to interconnect the control and power circuits
on two sub-bases.
b connection blocks
2
and
3
which perform the following three functions :
v ensure the mechanical fixing of the motor starter to the modular sub-base,
v connect the power terminals of the contactor and circuit-breaker,
v connect the auxiliary contact and A1-A2 coil terminals to the modular sub-base.
General presentation
System for Quickfit technology TeSys motor power-starters with spring terminals
System for TeSys motor power-starters with screw terminals
Modicon TSX Micro
automation platform 0
Installation system
Tego Power for motor power-stater components
Presentation
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com