Installation manual

2/22
2
2.1
Characteristics,
references
Modicon TSX Micro
automation platform 0
Safety automation system solutions
Preventa safety module type TSX DPZ
Standards and certifications
Standards Whole machine Electrical equipment of industrial machines EN 60204-1 ou IEC 204-1, EN 292
Emergency stop device EN 418
Product
Safety of machinery: safety related parts of control
systems
EN 954-1 category 3, pr EN 954-2, EN 1088 IEC 61508
(SIL 2)
PLC
Specific requirements IEC 1131-2 or EN 61131-2, CSA 22-2, UL 508
Certifications
BG, INERIS, INRS, UL, CSA
General characteristics
Power supply Nominal voltage V c 24
Limit operating voltage V c 21.6…30
Error signalling V c < 16
Maximum consumption mA < 200
Protection via external F1 fuse
Conforming IEC 947-5-1 A 1 (gl)
Consumption on internal 5 V
mA < 20
Isolation
kV 4 (overvoltage category III, degree of pollution 2)
Characteristics of discrete inputs
Nominal voltage V c 24
Modularity
Emergency stop or limit switch discrete inputs 8
Feedback loop discrete input 1
Logic
Positive
Inrush current
A 10/100 µs
Isolation between input and earth
V rms 1500 - 50/60 Hz for 1 minute
Power
Dissipated in the module W < 4.5
Characteristics of safety relay outputs
Modularity 2 volt-free outputs
Limit operating voltage
a.c. V a 19…264
d.c. V c 17…250
Max. thermal current (I the)
A 1.25
Minimum current
mA 10
a.c. load
Inductive
AC-15 duty
Voltage V a 24 a 48 a 110 a 220
Power VA 30 60 140 165
d.c. load
Inductive
DC-13 duty
(L/R = 100 ms)
Voltage V c 24
Power VA 30
Response time
ms < 100
Type of contacts
AgNi gold flashed
External output protection via
F2 fuse
Conforming IEC 947-5-1 A 4 (gl)
Isolation between input and earth
Insulation voltage conforming DIN VDE 0110 part 2 V 300
Test voltage V rms 2000-50/60 Hz for 1 minute
Environment
Temperatures Operation °C - 10 °C…+ 60 °C
Stockage °C - 25 °C…+ 60 °C
Degree of protection
IP 20 conforming IEC 529
Connecting cable c.s.a.
Without cable end mm
2
1 x 0.8 minimum
With cable end mm
2
2 x 1 maximum
Reference
Inputs number Voltage Safety outputs Connection
Format
Reference Weight
kg
4 Emergency stops or limit
switches (dual or single
contacts)
1 Start button
c 24 V 2 “N/O” (volt-free)
1.25 A (l the)
Via screw terminal
block (suplied)
Half-format
TSX DPZ 10D2A 0.280
TSX DPZ 10D2A
onnections:
age 2/23
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
efesotomasyon - telemecanique inverter