Connection principles
Modicon TSX Micro
automation platform 0
Discrete I/O modules
The screw connection terminal blocks are fitted with a removable cover ensuring:
b The screws are held in place
b Personnel safety
Each terminal on a screw terminal block can accept bare wires or wires fitted with
cable ends, with closed or open tags. The capacity of each terminal is:
b Minimum:
v 1 wire 0.28 mm
2
(AWG 23) without cable end
b Maximum:
v 2 wires 1 mm
2
(AWG 17) with cable end, or
v 1 wire 1.5 mm
2
(AWG 15) without cable end, or
v 1 open or closed tag for wires of 1 mm
2
(AWG 17)
.
Used for the simple and direct wire to wire connection of the
I/O of modules with connectors
1
to the sensors, preactuators or terminals.
The prewired cable
3
comprises:
At one end, a moulded HE 10 type connector
2
with 20 x 0.34 mm
2
cross-section
wires in a sheath.
At the other end
4
, flying leads -differentiated by colour coding conforming to DIN
47100.
TSX CDP 301: length 3 m,
TSX CDP 501: length 5 m,
TSX CDP 1001: length 10 m.
Used to connect the I/O of modules with HE 10 type
connectors
1
to Telefast 2
connection and adaption rapid wiring interfaces
2
. The cable
3
comprises 2 HE 10
type connectors
4
and a sheathed rolled ribbon cable with 0.08 mm
2
cross-section
wires.
Bearing in mind the small cross-section of the wire, this method of connection is only
recommended for low current I/O (100 mA maximum per input or per output).
TSX CDP 102: length 1 m,
TSX CDP 202: length 2 m,
TSX CDP 302: length 3 m.
Used to connect the I/O of modules with HE 10 type connectors
1
to Telefast 2
connection and adaption rapid wiring interfaces
2
. The cable
5
comprises 2 moulded
HE 10 type connectors
6
and a cable suitable for carrying higher currents (500 mA
maximum).
TSX CDP 053: length 0.5 m,
TSX CDP 103: length 1 m,
TSX CDP 203: length 2 m,
TSX CDP 303: length 3 m,
TSX CDP 503: length 5 m,
TSX CDP 1003: length 10 m.
Connection principles
Connecting modules with screw terminal blocks
1
3
4
2
Connecting modules with HE 10 type connectors
Prewired cable with 20 flying leads, gauge 22 (0.324 mm
2
)
Sheathed rolled ribbon cable, gauge 28 (0.08 mm
2
)
Connection cable, gauge 22 (0.324 mm
2
)
1
4
4
2
6
5
6
3
haracteristics:
ages 2/9 to
2/12
References:
pages 2/13 and 2/14
Connections:
pages 2/15 to 2/17
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com