Installation manual
6/4
6
Modicon TSX Micro
automation platform 0
Power consumption of TSX Micro PLC modules
The power supplies incorporated into TSX Micro PLC bases have sufficient nominal power to enable them to activate 60% of discrete inputs
and/or outputs simultaneously at state 1. At peak power, these power supplies can activate 100% of discrete inputs and/or outputs
simultaneously at state 1 without tripping.
Note:
b Base supplied in a.c., c 24 V process power supply must be used for the mini extension rack when this supports analogue I/O modules and
relay output modules.
b Base supplied in d.c., providing c 24 V voltage for the mini extension rack, even if this supports analogue I/O modules and relay output
modules.
For configurations near the limit, it is however necessary to establish the power consumption using the table below.
Reference Format Number Nominal currents consumed in mA (1)
1/2 : half Voltage c 5 V Voltage c 24 VR Voltage c 24 V (2)
S : standard Module Total Module Total Module Total
Discrete inputs
TSX DEZ 12D2K 1/2 20 76/104
TSX DEZ 32D2 S
60 170/254
TSX DEZ 12D2 1/2
20
positive logic inputs 87/123
negative logic inputs
83/107
TSX DEZ 08A4 1/2
20
TSX DEZ 08A5 1/2 20
Discrete outputs
TSX DSZ 08T2K 1/2 46/56 35/38
TSX DSZ 08T2 1/2
46/56 35/38
TSX DSZ 32T2 S
106/146 72/94
TSX DSZ 04T22 1/2
30 32/36
TSX DSZ 08T5 1/2
25 55/85
TSX DSZ 32T5 S 50 115/175 125/175
Discrete I/O
TSX DMZ 16DTK 1/2 46/56 55/76
TSX DMZ 28DTK S
56/68 104/132
TSX DMZ 28DT S
56/68 104/132
TSX DMZ 28DR S
45 85/125
positive logic inputs 106/160
negative logic inputs
95/131
TSX DMZ 28AR S
40 85/125
TSX DMZ 64DTK S 110/152 147/197
Preventa safety module
TSX DPZ 10D2A 1/2 20
Analogue I/O
TSX AEZ 801 1/2 30 60
TSX AEZ 802 1/2 30 60
TSX AEZ 414 1/2 40 85
TSX ASZ 401 1/2 30 90
TSX ASZ 200 1/2 30 150
TSX AMZ 600 1/2 30 180
Counting/positioning
TSX CTZ 1A 1/2 100 15
TSX CTZ 1B 1/2
100 15
TSX CTZ 2A 1/2
100 15
TSX CTZ 2AA 1/2
120 15
Total (to report page 6/5) Total current (mA)
(1) The first value corresponds to the module consumption with 60% of inputs and/or outputs at state 1 simultaneously. The second value is for 100% of inputs and/
or outputs at state 1.
(2)
c
24 V sensor voltage, provided by the
a
100…240 V power supply on basic configurations, is limited to supplying approx. 100 inputs. In excess of this, use
a process power supply (see page 2/61).