Installation manual
4/59
4
4.4
References (continued),
Dimensions
Modicon TSX Micro
automation platform 0
Fipio bus and Fipway network
Fipway network/Fipio bus connecting cables (1)
Description Type Conditions of use Rep. Length Reference Weight
kg
Trunk cables 8 mm
1 shielded twisted
pair 150
Ω
In normal environment
(2)
and inside building
1 100 m TSX FP CA100 5.680
200 m TSX FP CA200 10.920
500 m TSX FP CA500 30.000
9.5 mm, 1 shielded
twisted pair 150
Ω
In harsh environment (3)
outside building or in
garland (4)
100 m TSX FP CR100 7.680
200 m TSX FP CR200 14.920
500 m TSX FP CR500 30.000
9.5 mm, 1 shielded
twisted pair 150
Ω
and 1 x 1.5 mm
2
pair
for remote supply
I/O IP 67, in normal
environment (2)
and inside building
100 m TSX FP CP 100 7.680
500 m TSX FP CP 500 30.000
Tap link cables 8 mm, 2 shielded
twisted pairs 150
Ω
In normal environment(2)
and inside building
3 100 m TSX FP CC100 5.680
200 m TSX FP CC200 10.920
500 m TSX FP CC500 30.000
Cable for PCs card 2 shielded twisted
pairs
From TSX FPC10M card
to TSX FP ACC3/4 box
5 3 m TSX FP CE030 0.410
Fibre optic jumper Double fibre optic
62.5/125
For electrical/fibre optic
repeater
15 2 m TSX FP JF020 0.550
(1) The characteristics and performances of the Fipio bus/Fipway network are dependent on the above TSX FP accessories
being used.
(2) Normal environment:
v
without special environmental restrictions,
v
operating temperature between + 5 °C and + 60 °C,
v
fixed installations.
(3) Harsh environment:
v
resistance to hydrocarbons, industrial oils, detergents, solder chips,
v
up to 100% humidity,
v
saline environment,
v
extreme variations in temperature,
v
operating temperature between - 10 °C and + 70 °C,
v
mobile installations.
(4) Mobile installations: cables as per VDE 472, part 603/H:
v
for use on cable drag chain with minimum bend radius of 75 mm,
v
for use on gantry crane (strikethrough: portal support), subject to compliance with conditions for use such as acceleration,
speed, length etc: contact our regional branch office for further information.
v
not authorized for use on robots, or multi-axis applications.
Dimensions
TSX FP ACC4 TSX FP ACC6 TSX FP ACC8M TSX FP ACC14
80
50
20
==65
80
20
20
==
RUN DEF ø¡
175
160
2020
==50
8325
=
=
RUN DEF ø¡
220
205==
20
==50
7925
27
116
68
104