Installation manual
1/13
1
Characteristics
Modicon TSX Micro
automation platform 1
TSX 37 05/08/10/21/22 PLCs
TSX Micro PLCs have been developed to conform to the national and international
standards concerning electronic devices for industrial control systems:
b Specific requirements for programmable controllers: functional characteristics,
resistance, robustness, safety, etc. IEC 61131-2, CSA 22-2, UL 508.
b Merchant navy requirements from the main European bodies: BV, DNV, GL,
GOST, LR, RRS.
b European directives (low voltage, electromagnetic compatibility), e marking.
b Electrical qualities and self-extinguishing capacity of insulating materials:
UL 746C, UL 94, etc. See page
6/4
.
(1) Minimum level in the test conditions defined by the standards.
(2) Values to be taken into account when starting up several devices at the same time or when
sizing protection devices.
Characteristics
Environmental characteristics
(characteristics common to all TSX Micro PLC components)
Temperature Operation °C 0...+ 60 (+ 5...+ 55 conforming to IEC 61131-2), 0…+ 70 with TSX FAN ventilation modules
Storage
°C - 25...+ 70 (conforming to IEC 61131-2)
Relative
humidity
Operation
10 %...95 %, without condensation
Storage
5 %..95 % conforming to IEC 61131/2 without condensation
Altitude
m 0…2000
Mechanical
withstand
Resistant to vibrations
Conforming to IEC 68-2-6, Fc test
Resistant to shocks
Conforming to IEC 68-2-27, Ea test
Resistant to
electrostatic
discharge
Withstand to electrostatic discharge
Conforming to IEC 1000-4-2, level 3 (1)
Resistance to HF
interference
Resistant to electromagnetic fields
Conforming to IEC 1000-4-3, level 3 (1)
Resistant to rapid transient bursts
Conforming to IEC 1000-4-4, level 3 (1)
Resistant to shock waves
Conforming to IEC 1000-4-5
Resistant to damped oscillatory
waves
Conforming to IEC 1000-4-12
Resistance to LF interference
Conforming to IEC 61131-2
Power supply characteristics
Type of power supply Power supply a Power supply c
Primary Voltage Nominal
V a 100...240 c 24
Limit (including
ripple)
V a 90…264 c 19.2...30V
possible up to 34 V for 1 hr per 24 hrs
Frequency
Nominal (limit) Hz 50-60 (47-63) –
Current Nominal input
A y 0.7 (a 100 V), ≤ 0.3 (a 240 V) 2
Inrush (2)
A y 60 y 60
Micro-breaks
Accepted duration y 1/2 period, repetition ≥ 1 s y 10 ms, repetition u 1 s
Secondary Power
Total useful
(typical)
W 24 (32 peak) 16 (18 peak)
Output currents c 5 V output
A 2.8 (3.2 peak) 2.8 (3.2 peak)
Output c 24 VR
(for relay outputs)
A 0.5 (0.6 peak) –
c 24 V output
sensors
A 0.4 (0.6 peak) –
Protection
integrated on the
outputs against
Overloads
Yes Yes
Short-circuits
Yes Yes
Isolation Dielectric
resistance
Primary/
secondary
V rms 2000 - 50/60 Hz No isolation, 0 V internal connected to the PLC
ground
F
unctions:
p
ages 1/8 and 1/9
References:
pages 1/15 and 1/16
Dimensions, mounting:
page 1/17
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com