Installation manual
4/29
4
4.2
Diagnostics,
characteristics
Modicon TSX Micro
automation platform 0
Master modules for AS-Interface bus
Diagnostics performed using the centralized display unit of the TSX Micro platform
or using the display unit of TSX SAY 100/1000 modules can be completed using a
PC terminal on which PL7 Micro/Junior/Pro software has been installed.
The terminal connected to the TSX Micro/Premium PLC is used to perform
diagnostics of the operating state of the AS-Interface V1 TSX SAZ 10 and
TSX SAY 100 master modules, the bus and the slave devices on the bus.
For the AS-Interface V2 TSX SAY 1000 master module, the diagnostics are identical
to those of the AS-Interface V1 module, and in addition, take into account
developments in the M2E standard.
Diagnostics are performed using a single screen divided into four sections providing
information on:
1 Status of the TSX SAZ 10 or TSX SAY 100/1000 module (RUN, ERR, I/O).
2 Status of the AS-Interface channel connected to the module.
3 Faulty interface (or slave).
4 Data relating to any selected interface (profile, parameters, forcing, etc).
In the event of an AS-Interface module or channel fault, a second screen can be
accessed, which clearly shows the type of fault, which may be at internal or external
level.
(1) If the interfaces are connected using extended addressing, the type of discrete I/Os is 4I/3O
(instead of 4I/4O).
Diagnostics
34
1
2
D
iagnostics of the TSX SAY 100 module using PL7
3
4
1
2
D
iagnostics of the TSX SAY 1000 module using PL7
Characteristics
Type of module TSX SAZ 10 TSX SAY 100 TSX SAY 1000
AS-Interface profile
M2(AS-Interface V1) M2E (AS-Interface V2)
Type of addressing
Standard Standard and extended
Product certification
AS-Interface No. 12001,
IEC 61131 2
AS-Interface No. 18801,
IEC 61131 2
Pending
Ambient air temperature Operation
0…+60 °C.
Storage
-25…+70 °C.
Degree of protection
IP 20
Vibration resistance
Conforming to IEC 68 2 6. Fc tests.
Shock resistance
Conforming to IEC 68 2 27. EA tests.
Number of connectable interfaces
(or slaves)
With standard addressing
31 slaves
With extended addressing
– 31 slaves
Type of connectable interfaces With standard addressing
Discrete I/Os (4I/4O) Discrete I/Os (4I/4O) (1)
Analog I/Os (a maximum of
4 channels)
Safety interfaces
With extended addressing
– Discrete I/Os (4I/3O)
Bus connection
By terminal block inside
module
(polarity locating device)
By 3-way SUB-D connector (included with the module)
Module power supply
Via power supply integrated into the host platform of the module
Display/diagnostics
Via:
v centralized display unit on TSX Micro PLC or via the display unit of TSX SAY 100/1000
modules
v use of the PL7 Micro/Junior/Pro software diagnostics function
v use of the ASI-TERV1 adjustment console (infrared link)