Installation manual
4/19
4
4.1
Characteristics (continued)
Modicon TSX Micro
automation platform 5
ConneXium industrial Ethernet
Characteristics of transceivers
Mechanical characteristics
Models 499 NTR 100 10 499 NTR 101 00
Operating temperature
° C (F) 0...60 (32...140)
Relative humidity
10...95 % (non-condensing)
Dimensions (W x H x D)
mm
(in)
40 x 134 x 80
(1.58 x 5.28 x 3.15)
47 x 135 x 111
(1.9 x 5.3 x 4.4)
Enclosure
IP 30 IP 20
Agency approvals and compliance
cUL 1950 ; FM 3810 Class 1, Div. 2 ; e ;
Germanischer Lloyd ; IEC 61131 2
cUL 1950 ; cUL 508 ; cUL 1604 ;
FM 3810 Class 1, Div. 2 ; e ;
Germanischer Lloyd ; IEC 61131 2
Electrical characteristics
Models 499 NTR 100 10 499 NTR 101 00
Technology
Ethernet 10 Mbit/s Ethernet 100 Mbit/s
Interfaces
1 10BASE-T port with shielded RJ45
connector
1 10BASE-FL port with BFOC connector
1 100BASE-TX port with shielded RJ45
connector
1 100BASE-FX ports with SC connector
Connection type
Twisted pair cable and fiber optic Ethernet cable
Operating voltage
VDC 18...32, safety low voltage
Terminal block
1 x 5-pin, pluggable
Power consumption at 24 VDC
mA 80 typical
100 maximum
160 typical
190 maximum
Redundancy
Power supply
Maximum range
m (ft) 10BASE-T 100 (328)
10BASE-FL 3100 (1070)
10BASE-TX 100 (328)
10BASE-FX 3100 (1070)
Link budget
dB 11.5 db for 50/125 and 62.5/125 µm fiber 8 db for 50/125 µm fiber, 11 db for
62.5/125 µm fiber
LED indicators
P1, P2 power, redundancy manager, data exchange/port
R
eferences:
p
age 4/21
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
efesotomasyon - telemecanique inverter