Installation manual

1/9
1
Functions (continued)
Modicon TSX Micro
automation platform 1
TSX 37 05/08/10/21/22 PLCs
Counter modules TSX Micro PLCs offer several ways of counting:
b Using 500 Hz discrete inputs (2 up/down counter channels with upcounting,
downcounting or up/down counting functions, with or without detection of direction of
operation).
b 10 kHz counter channels integrated into TSX 37 22 PLC bases (2 10 kHZ fast
counter channels, with 1 channel having down-counting functions as above).
b Counting/positioning TSX CTZ modules pA, from 40...500 kHz or TSX CTZ 2B,
from 200 kHz...1 MHz. These half format modules are inserted in the available slots
in the base rack.
For further details, see pages
3/16
to 3/25.
TSX Micro PLCs offer several possibilities:
b Integrated communication which offers cost-effective dialogue functions via the
terminal port for TSX 37 05/08/10 PLCs or via the terminal and man-machine
interface ports for TSX 37 21/22 PLCs. These RS 485 type non-isolated links use
Uni-Telway master/slave, Modbus RTU slave or character string.
Also TSX 37 10/21/22 PLCs integrate Modbus master protocol.
b PCMCIA format communication card for TSX 37 21/22 PLCS. They have a
dedicated slot for the PCMCIA format communication card ("Full-duplex"
asynchronous serial link, CANopen bus, Fipio bus, Uni-Telway or Modbus, Modbus
Plus or Fipway network).
b Ethernet TCP/IP 10/100 MHz external modules. This external module connects to
the terminal port of TSX 37 10/21/22 PLCs and has Uni-TE and Modbus messaging.
It also allows connection to an external modem using PPP protocol.
For further details, see pages
4/6
to
4/21
.
TSX FAN ppP fan modules installed above TSX Micro PLCs ensure a forced air
convection, which creates a uniform ambient temperature within the enclosure and
eliminates any hot spots which might exist.
Fan modules are required when the ambient temperature is between 60 °C and
70 °C. Forced ventilation is used to eliminate hot spots (1).
Three types of fan module are available: c 24 V, a 110 V and a 220 V.
One fan module is required for a TSX 37 05/08/10/21/22 configuration, two fan
modules are required for a TSX 37 10/21/22 configuration with the TSX RKZ 02
mini rack.
(1) For an ambient temperature of between 25 °C…60 °C, the use of fan modules increases the
MBTF.
Counting/positioning
Communication
TSX FAN
pp
P
T
SX 37 05/08/10 TSX 37 10 + TSX RKZ 02
TSX 37 08/21/22 TSX 37 21/22 + TSX RKZ 02
Fan modules
escription:
ages 1/4 to 1/7
Characteristics:
pages 1/13 and 1/14
References:
pages 1/15 and 1/16
Dimensions, mounting:
page 1/17
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com