Installation manual

4/13
4
4.1
Description
Modicon TSX Micro
automation platform 0
Ethernet network and TCP/IP Modem serial link
The Ethernet TSX ETZ 410/510 modules are autonomous and thus do not fit into a
TSX Micro PLC rack, but fix onto a DIN profile or on AM1-PA perforated mounting
plate.
The front of the TSX ETZ 410/510 modules are arranged as follows:
1 Three display LEDs indicating the module status (RUN, ERR, RX/TX).
2 A screened-on label indicating the module's MAC address (default address set in
the M bit).
3 A mini DIN connector for terminal port (TER address).
4 An RJ45 connector for Uni-Telway auxiliary port RS 485 serial link
(RS 485 address).
5 An RJ45 normalized connector for connecting to the Ethernet network
(10/100BASE-T address).
6 A 9 pin male SUB-D connector for RS 232 serial link (Modem).
7 A screw terminal block for connecting to the external power supply c 24 V.
8 A support plate enabling it to be fixed to the module.
The TSX ETZ 410/510 modules support two kinds of exclusive TCP/IP connections:
b By Ethernet network via 10BASE-T/100BASE-TX (RJ45) interface, see page 4/21
for accessories and connection cables.
b By Modem via RS 232 serial link, see page 4/66 for accessories and connection
cables.
The TSX ETZ 410/510 modules are connected to the TSX Micro PLCs
TSX 37 10/21/22 via:
b The terminal port (TER) or the auxiliary port (AUX).
b The PCMCIA RS 485 TSX SCP114 serial link.
The wiring chart opposite corresponds to one of the methods of connection.
The TSX ETZ 410/510 module is attached to the TSX Micro PLC via its terminal port
(TER or AUX).
1 TSX PCU 1031: Uni-Telway connection cable between a compatible PC and the
TER port of the TSX ETZ 410/510 module.
2 TSX ETZ CDN 003: connection cable (0.35 m cable, supplied with the
TSX ETZ 410/510 module) between the module (rep. RS 485) and the TER/AUX
port of the TSX Micro PLC. The TSX CX 100 cable authorizes a connection with
longer lengths (up to 10 m).
3 490 NTW 000pp: shielded twisted pair cable connection right of the module
(rep. 10BASE-T/100BASE-TX) to Ethernet via hub (see page 4/21). Length from
2...80 m.
4 RS 232 cable between the SUB-D 9 connector contacts of the module
(rep. RS 232) and the Modem.
5 Connection for external power supply c 24 V (see Phaseo power supply
page 2/61).
Description of the TSX ETY 410/510 modules
8
7
6
5
4
3
2
1
Wiring system
Flow chart
1
2
3
4
5
Ethernet
TSX Micro
Modem
TSX ETZ 410/510
resentation:
age 4/6
Functions:
pages 4/8 to 4/12
Characteristics:
page 4/14
References:
page 4/15
Dimensions:
page 4/15
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com