Installation manual

1/8
1
Functions
Modicon TSX Micro
automation platform 1
TSX 37 05/08/10/21/22 PLCs
The range of in-rack discrete I/O modules offers several possibilities for meeting
requirements:
b Cost-effective connection where a c 24 V solution is required (mixed I/O modules
with HE type 10 connectors for direct connection to pre-actuators in the device using
cables with flying leads or direct connection to the TELEFAST2 pre-wired system).
b Connection to the screw terminal block on the front panel of mixed I/O modules.
A set of half format modules enable the PLC configuration to be adapted as closely
as possible to the user's requirements in terms of number, range of I/O and type of
connection.
For further details, see pages
2/6
to
2/17
.
The TSX DPZ 10D2A Preventa type safety relay module provides a monitoring
function for the emergency stop pushbuttons or limit switches, and is adapted to
conform to the safety requirements stipulated in EN 954-1.
For further details, see pages
2/18
to
2/23.
TSX 37 10/21/22 Micro PLCS offer two different possibilities for extending the I/O:
b Either with the TSX STZ 10 remote discrete I/O extension module. The discrete I/
O of 4 Nano PLCs can be used at a distance of up to 200m (one of which can be a
Nano extension PLC).
These Nano PLCs can be used as remote discrete I/O or local slave PLCs.
For further details, see pages
2/24
et 2/25
.
b The AS-Interface sensor/actuator bus. TSX Micro PLCs are connected to the
AS-Interface bus via an AS-Interface master module. In this case, the PLC becomes
the master station on the bus and manages a maximum of 248 I/O over a distance
of up to 100 m (200 m with a repeater).
For further details, see pages
4/26
to
4/29
.
b The CANopen machine bus. The communication of the Micro TSX 37 21/22 PLCs
enables the connectivity to the CANopen machine bus. It is appeared as a PCMCIA
card equipped with a cable (length 0.5m) and a tap junction (with 9-way SUB-D
connector). This TSX CPP 110 kit allows the direct linking to the bus and ensures the
role of the master on the CANopen bus. The PCMCIA card is inserted into the
reserved slot for communication card, available on the TSX 37 21 and TSX 37 22.
For further details, see pages 4/22 to 4/25
.
TSX Micro PLCs offer several ways of performing analogue processing:
b For data input or commands which do not need a high resolution level, using I/O
integrated in TSX 37 22 PLCs.
b For precise measurement and commands, using TSX AEZ/ASZ/AMZ ppp half
format analogue I/O modules.
b To locate analog I/O remotely via the TSX STZ 10 rackmaster module with
TSX 37 10/21/22 PLCs. The latter enables the use of three TSX AMN 400p analog
extensions, each equipped with 3 analogue inputs and one analog output.
For further details, see pages
3/5
and
3/6
.
TSX Micro PLCs have, as standard, process control functions which can be
accessed by the user via the PL7 Micro, PL7 Junior or PL7 Pro programming
software.
For further details, see pages
3/10 to 3/13
.
Functions
Discrete inputs/outputs
Remote discrete I/O extension module
Analogue I/O and process control
escription:
ages 1/4 to 1/7
Characteristics:
pages 1/13 and 1/14
References:
pages 1/15 and 1/16
Dimensions, mounting:
page 1/17
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com