Selection guide (continued)
Modicon TSX Micro
automation platform 0
Network and buses
Applications Modbus open industrial field bus Open industrial fiedbus conforming to
Fip standard
Types of network or bus Modbus RTU Fipio (agent)
Structure Physical interface RS 485, isolated via TSX P ACC 01 tap Norme Fip
Access method Slave Master/slave Bus managed by bus arbitrator
Rate 19,2 Kbit/s max. 1 Mbit/s
Médium Double twisted shielded pair Twisted shielded pair
Fibre optic via transceivers or repeaters
Configuration Maximum number of devices 28 devices max. 32 per segment, 128 on all segments
98 slave addresses
max.
248 slave
addresses max.
Maximum length 1300 m max. for isolated RS 485 From 1000 m to 15,000 m (depending on the
medium use) with repeaters
No. of links/station 1 max.
Services Modbus slave RTU Modbus
master/slave RTU
-Uni-TE
- Periodic data exchange
- Application-to-application
- Transparent exchange of remote I/O
13 Modbus functions (read/write bits and
words, diagnostic…)
Type of TSX Micro PLC base TSX 37-05/08/10
PLC bases
TSX 37-21/22 PLC bases
Nature of modules Built-in link on terminal port Type III PCMCIA card
Type of modules
TER
terminal port
AUX
terminal port
TSX FPP 10