Installation manual
4/3
4
0
Local area network conforming to Fip standard CAN field bus Open industrial field bus conforming to AS-i
standard
Fipway Bus CANopen V4.02 AS-Interface
Fip standard ISO 11898 AS-Interface standard, M2 profile
Bus managed by bus arbitrator CSMA/CA, multi-master Master/slave
10 Kbit/s...1 Mbit/s according to distance 167 Kbit/s
Twisted shielded pair
Fibre optic via transceivers or repeaters
Double twisted shielded pair 2-wire AS-Interface cable
32 per segment, 64 on all segments 127 slaves 31 sensor/actuator devices
1000 m per electrical segment
5000 m max. with repeaters
From 20 m (1 Mbit/s)...2500 m (20 Kbit/s) 100 m
200 m with repeaters
-Uni-TE
- COM/shared table
- Application-to-application
-Telegram
CANopen :
- Implicit PDO exchange
- Explicit SDO exchange or CAN function block
- Explicit PDU CAN exchange
Transparency of exchanges with sensor/actuator
devices
TSX 37 10/21/22 PLC bases
Type III PCMCIA card Half-format module to be insert in slot 4
TSX FPP 20 TSX CPP 110 TSX SAZ 10
4/49 4/25 4/27
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
efesotomasyon - telemecanique inverter