Modicon TSX Micro
automation platform 1
TSX 37 10 PLCs
Compact and modular TSX 37 10 PLCs differ in their supply voltage and the type of
discrete I/O module fitted in the first slot.
Each TSX 37 10 configuration comprises a rack which integrates a power supply
(c 24 V or a 100/240 V), a processor including a 14 Kword RAM memory (program,
data and constants), a Flash EPROM backup memory, a real-time clock, a discrete
I/O module (28 or 64 I/O) and an available slot. A TSX RKZ 02 mini extension rack
enables the number of slots to be increased by 2 (4 positions).
Each available slot can accept:
b 1 standard format discrete I/O module of any type.
b 2 half format discrete I/O, safety, analog I/O or counter modules.
Also, TSX 37 10 PLCs can connect to the Ethernet network TCP/IP or to a Modem
via the TSX ETZ 410/510 external stand-alone module.
TSX 37 10 PLCs and the TSX RKZ 02 mini extension rack comprise:
1 2-slot base rack.
2 Centralized display block.
3 Terminal port (TER) (Uni-Telway, Modbus RTU master/slave protocol or
characters string).
4 Cover for accessing the power supply terminals.
5 28 or 64 discrete I/O module, placed in the first slot (positions 1 and 2).
6 Cover for accessing optional battery.
7 Mini extension rack with 2 available slots -(positions 5 to 8).
8 LED showing presence of c 24 V.
9 Power supply terminals protected by removable cover, to connect an auxiliary
c 24 V power supply if PLCs are supplied with a 100/240 V.
10Earth terminal.
11Connectors to the base PLC.
12Reset button.
(1)With TSX RKZ 02 mini extension rack.
(2) This includes a standard format module to be inserted in the 1
st
slot of the PLC.
(3) The remote discrete I/O extension modules and AS-Interface bus modules are installed in
position 4 which means that their use is mutually exclusive.
Presentation
Description
11
10 9
87
2 3 1
4
12 6 5
Selection
TSX 37 10 base PLC selection
Power supply I/O module integrated in 1
st
slot Connection Reference
Number of inputs Number of outputs HE 10
Connector
Screw terminal
block
c 24 V a 110/120 V Solid state c
24 V
Relay
c 24 V
16 12 TSX 37 10 128DT1
16 12 TSX 37 10 128DTK1
16 12 TSX 37 10 128DR1
32 32 TSX 37 10 164DTK1
a 110/240V
16 12 TSX 37 10 028AR1
16 12 TSX 37 10 028DR1
Selection of modules to be inserted (3 slots available, that is a maximum of 6 positions)
Type of module to be inserted Maximum number of modules (1) Format Connection
1 2 4 6 Stand. Half Connect. Term.blk
Discrete Inputs/Outputs 8 inputs
12 inputs
32 inputs (2)
4 outputs
8 outputs
32 outputs (2)
16 inputs/outputs
28 inputs/outputs (2)
64 inputs/outputs (2)
Preventa safety module
AS-Interface bus or I/O extension (3)
Analog I/O 4 or 8 inputs
2 or 4 outputs
Counter/positioning
channels
1 or 2 incremental encoder
channels
1 absolute encoder channel
Communication Ethernet TCP/IP or external
Modem
External module
Possible selection or insertion
F
unctions:
p
ages 1/8 and 1/9
Characteristics:
pages 1/13 and 1/14
References:
pages 1/15 and 1/16