Technical data

Technical Manual Cold Storage Controllers TKP / TKC x130 - x140 Page 9
Assignment page Level Range Default value
function relay 1 3 --, on, refrig. 1, refrig.2, refrig.3, refrig.4 alarm
defrost11, defrost12, defrost13, defrost14,
defr. 11 thru 44 means:
defrost21, defrost22, defrost23, defrost24,
defrost
yz defrost31, defrost32, defrost33, defrost34,
y=circuit, z=evaporator
defrost41, defrost42, defrost43, defrost44,
Example:
fan 1, fan 2, fan 3, fan 4, unit on
defr.11 = defrost relay
control circuit 1,
alarm, frame heater, roller blind,
evaporator 1
light, heater 1
function relay 2 3 dto. refrigeration 1
function relay 3 3 dto. refrigeration 2
function relay 4 3 dto. frame heater
function relay 5 3 dto. defrost 21
function relay 6 3 dto. defrost 11
function Opto. 1 3 ---, manual defrost, night settings, man. defrost
(digital input OC 1) unit OFF actHigh, security chain,
setpoint layer, door contact 1...4
alarm input 1,alarm input 2
alarm input 3, alarm input 4,
circuit OFF 1 - - - thru
circuit OFF 1 2 3 4, analog value,
refLock actLow, refLock actHigh,
refForce actLow, refForce actHigh,
unit OFF actLow, circ.OFF.low 1 - - -
thru circ.OFF.low 1 2 3 4
function Opto. 2 3 dto. night settings
function Opto. 3 3 dto. controller OFF
function Opto. 4 3 dto. - - -
funct. sensor 1a 3 - - - (sensor is switched OFF), control sens. 1
control sensor 1 ... control sensor 4,
defr sensor x/x =
defrost sensor circuit x / no. x,
demdefr sens co1,
demdefr sens wa1,
alarm sensor 1 thru alarm sensor 4,
disp only sens
Examples
walk-in fr. chest fr. walk-in (+4°) refrig. shelf
alarm alarm alarm alarm
refrig. 1 refrig. 1 refrig. 1 refrig. 1
fan 1 frame heater fan 1 refrig. 2
defr. 1/3 defr. 1/3 defr. 1/3 roller blind
defr. 1/2 defr. 1/2 defr. 1/2 off
defr. 1/1 defr. 1/1 defr. 1/1 refrig. 3
m. defrost m. defrost m. defrost m. defrost
night sett. night sett. night sett. night sett.
contr. OFF contr. OFF contr. OFF contr. OFF
setp. layer setp. layer setp. layer setp. layer
contr.sens1 alm sens 1 contr.sens.1 contr.sens. 1