Technical data

Technical Manual Cold Storage Controllers TKP / TKC x130 - x140Page 8
Mode page Disp Le- Range Dim. Default-
only vel value
compound
2
1, 2, none 1
fan operation 2 interval, permanent interval
cooling mode 2 refrigeration, refrigeration
freezing
emergency operat. 2 0...100% 0%
frame period 2 10:00...60:00 mm:ss 15:00 mm:ss
frame pulse day 2 0...100% 100%
frame pulse nigt 2 0...100% 100%
alm temp. low 2 yes, no yes
night setp ON 2 0:00 thru 23:59, off off
night setp OFF 2 0:00 thru 23:59, off off
runtime mess at 2 0...23 h 6 h
corr sensor 1 2 calibration offset, K
adjustable +/-10
(actual value also adjustable)
corr sensor 2 2 calibration offset, K
adjustable +/-10
(actual value also adjustable)
corr sensor 3 2 calibration offset, K
adjustable +/-10
(actual value also adjustable)
corr sensor 4 2 calibration offset, K
adjustable +/-10
(actual value also adjustable)
corr sensor 5 2 calibration offset, K
adjustable +/-10
(Istwert dto. einstellbar)
corr sensor 6 2 calibration offset, K
adjustable +/-10
(actual value also adjustable)
sensor (type) 3 TF 201 (PTC), Pt1000
!! 3130/1=Pt1000 only TF 501 (Pt 1000)
unit text 3 unit name as desired TKP
operator layer 3 yes, no no
program version X 1 version no. of this
program
summer / winter 3 no, EU up to 1995, EU from 1996
EU from 1996
actual time 2 h:min:sec
actual date 2 day:month:year
Sprache / language 2 deutsch, english,
francais,
Nederlands
baudrate 3 1200, 2400, 4800, 9600
9600
adress in netwk 3 0 - 78
Examples
walk-in fr. chest fr. walk-in (+4°) refrig.shelf
2 (TK) 2 (TK) - - - - - -
interval - - - interval - - -
freezing freezing refrigeration refrigeration
60% 80% 50% 50%
- - - 30:00 - - - - - -
- - - 80% - - - - - -
- - - 40% - - - - - -
no no yes yes
- - - - - - - - - 20:00
- - - - - - - - - 6:00
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
!!! !
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
EU from EU ab EU from ‘96 EU from ‘96
‘96 ‘96
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
9600 9600 9600 9600
- - - - - - - - - - - -
- Parameters marked with "Disp. only" are for Information only and cannot be adjusted.
- The numbers in column "Level" show the user level, where this parameters are displayed.
Your value