Technical data

Technical Manual Cold Storage Controllers TKP / TKC x130 - x140 Page 7
Defrost page
Disp
Le- Range Dim. Default-
only
vel value
defrost type
(fan dur.defr.)
2 on, off off
defrost mode 2 extern(al only), extern
extern+intern +intern
difference meth.,
dem def by opti,
adaptive *
defrost time 1 1 00:00 - 23:59, off hh:min 5:00
defrost time 2 1 00:00 - 23:59, off hh:min off
defrost time 3 1 00:00 - 23:59, off hh:min off
defrost time 4 1 00:00 - 23:59, off hh:min off
defrost time 5 1 00:00 - 23:59, off hh:min off
defrost time 6 1 00:00 - 23:59, off hh:min off
defr temp limit 1 2 (control circuit 1) °C 14°C
0,0°C....50,0°C
defr temp limit 2 2 (control circuit 2) °C 14°C
0,0°C....50,0°C
defr temp limit 3 2 (control circuit 3) °C 14°C
0,0°C....50,0°C
defr temp limit 4 2 (control circuit 4) °C 14°C
0,0°C....50,0°C
last defr cycle 1 X 2 (circuit 1) min:sec mm:ss 00:00
last defr cycle 2 X 2 (circuit 2) min:sec mm:ss 00:00
last defr cycle 3 X 2 (circuit 3) min:sec mm:ss 00:00
last defr cycle 4 X 2 (circuit 4) min:sec mm:ss 00:00
n/o defr ignored X 2 0, 1, 2, 3, 4, 5, 6 0
demand defr diff 2 0,0...20,0K K 5K
dem defr period 2 00:00...10:00 mm:ss mm:ss 02:00
pulsedef. limit 2 -5,0...+50,0°C °C 50,0°C
defr alarm delay 2 00:00 thru 60:00 mm:ss 30:00
pause ahead defr 2 0...15 min min 0
pause aft. defr 2 00:00 thru 30:00 mm:ss 00:00
n/o.def.evnt > alm 2 Number of defrost
cycles without alarm,
off, 1-15 3
max defrost time 2 00:00 thru 4:00:00 mm:ss 45:00
manual defrost 1 start, finish
* defrost forerun 2 00:00 thru 00:15 hh:mm 00:03
* time (up) to defr X 2 hh:min:sec
* max time to defr 2 02:00 thru 48:00 hh:mm 24:00
Examples
walk-in fr. chest fr. walk-in (+4°) refrig. shelf
off - - - on - - -
ext/int ext/int ext/int ext/int
6:00 5:00 5:00 5:00
21:00 20:00 11:00 13:00
off off 17:00 21:00
off off 23:00 - - -
off off - - - - - -
off off - - - - - -
8°C 8°C 8°C 8°C
- - - - - - - - - 8°C
- - - - - - - - - 8°C
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
+3°C 50°C +3°C 50°C
30:00 30:00 30:00 30:00
1:00 00:00 00:00 00:00
off off off off
45:00 45:00 30:00 45:00
- - - - - - - - - - - -
* in TKP/TKC x140 only.
- Parameters marked with "Disp. only" are for Information only and cannot be adjusted.
- The numbers in column "Level" show the user level, where this parameters are displayed.
Your value