Technical data

Technical Manual Cold Storage Controllers TKP / TKC x130 - x140Page 6
Setpoint page Le Range Default-
vel value
setpoint layer 1 1, 2 1
setpoint Ch 1 1 -50/+50°C -20°C
setpoint Ch 2 1 -50/+50°C -20°C
setpoint Ch 3 1 -50/+50°C -20°C
setpoint Ch 4 1 -50/+50°C -20°C
2nd setp Ch 1 1 -50/+50°C -20°C
2nd setp Ch 2 1 -50/+50°C -20°C
2nd setp Ch 3 1 -50/+50°C -20°C
2nd setp Ch 4 1 -50/+50°C -20°C
alt setp Ch 1 1 -50/+50°C -20°C
alt setp Ch 2 1 -50/+50°C -20°C
alt setp Ch 3 1 -50/+50°C -20°C
alt setp Ch 4 1 -50/+50°C -20°C
alt 2nd setp Ch 1 1 -50/+50°C -20°C
alt 2nd setp Ch 2 1 -50/+50°C -20°C
alt 2nd setp Ch 3 1 -50/+50°C -20°C
alt 2nd setp Ch 4 1 -50/+50°C -20°C
warning offset 2 0...50K 7 K
(relative to the active setpoint)
alt warn offset 2 0...50K 7 K
(relative to the active setpoint)
warn low limit 2 -50/+50°C - 22°C
(absolute value)
alt warn low lim 2 -50/+50°C (Absolutwert) - 22°C
(absolute value)
hysteresis 2 0,1...20K 2 K
PID propor band 2 0,1...30K 4 K
PID integr time 2 off, 00:00 thru 10:00 min:sec 10 sec.
PID attack time 2 off, 00:00 thru 00:10 min:sec off
PID delay 2 off, 0,1 thru 10 sec. off
opto->analog val. 2 0,0...100,0 %, 0%
voltage / current from analog
output with activated
digital (OC-) input
fan start delay 2 0:00:00 thru 0:30:00 (h:min:sec), 0:05:00
freeze-on time
fan off delay 2 00:00 thru 30:00 min:sec 00:00
warning delay 2 0:00:00 thru 2:00:00 (h:min:sec) 0:45:00
cooling limit 2 0:00 thru 23:59 (h:min), off off
door time limit 2 0:00 thru 23:59 (h:min), off off
refrDlyAftMnsOff 2 0...30 min 0 min
compr. pause 2 00:00 thru 30:00 hh:mm 00:00
OC inp alm delay 2 00:00 thru 02:00 hh:mm 00:05
door alm delay 2 00:01 thru 04:00 hh:mm 00:05
sec chain delay 2 00:00 thru 01:00 min:sec 01:00
Examples
walk-in fr. chest fr. walk-in (+4°) refrig. shelf
111 1
-20°C -26°C +4°C +1°C
- - - - - - - - - +3°C
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - 24°C - - - +3°C
- - - - - - - - - +5°C
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - 15K 5K 50K
- - - - - - - - - - - -
off off 2°C -35°C
off off 2°C -35°C
2K 4K 2 K 2 K
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
0:03:00 - - - 0:03:00 - - -
0:02:00 - - - 0:02:00 - - -
1:00:00 1:00:00 1:00:00 1:00:00
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
Your Value
- Parameters marked with
"Disp. only" are for Infor-
mation only and cannot be
adjusted.
- The numbers in column
"Level" show the user level,
where this parameters are
displayed.
2nd setp Ch 1
-> -20.0 °C <-
- The current active setpoints /
alarm offsets / alarm limits are
marked by additional arrows in
the display.
Example: