Technical data

Technical Manual Cold Storage Controllers TKP / TKC x130 - x140 Page 5
Actual Values Disp
Level
Range Default val. Your value
only
sensor 1 xxxxxx
x
1 Display of the temperature of this sensor
range -100/+100°C, calibr. = 0
calibration range here is +/- 10K
x
indicates the function assigned to this sensor:
Rx = control sensor x,
Wx = alarm sensor x
DO = display only sensor,
w1 = defrost demand sensor warm x
c1 = defrost demand sensor cold x
Dxy = evap sensor, circuit x / no.y
sensor 2 1 dto. calibr. = 0
sensor 3 1 dto. calibr. = 0
sensor 4 1 dto. calibr. = 0
sensor 5 1 dto. calibr. = 0
sensor 6 1 dto. calibr. = 0
run time refr. 1 X 1 refrigeration runtime today 00:00
thru
run time refr. 4 X 1 00:00
door open 1 X 1 total door open time today 00:00
thru
door open 4 X 1 00:00
rem. door open 1 X 2 remaining time before alarm
thru "door open" ("---" = door closed)
rem. door open 4 X 2 h:min:sec
remain alm delay X 2 remaining time before temperature alarm
remain defr time X 2 remaining defrost time in mm:ss
rem. defr pause 1 X 2 h:min:sec
thru
rem. defr pause 4 X 2
remain fandelay 1 X 2 h:min:sec
thru
remain fandelay 4 X 2
rem compr pause1 X 2 h:min:sec
thru
rem compr pause4 X 2
rem strt sec ch(ain) X 2 h:min:sec
rem chck defrdem X 2 min:sec 00:00:00
dem defr stored X 2 yes, no no
solenoid valve X 2 enabled, off
status X 1 off circuit X
night settings X 1 day, night
runtime relay 1 2 h:m:s (resettable only) 00:00:00
thru
runtime relay 6 2 00:00:00
analog value X 1 output is X% of the selected range
OC1 OC2 OC3 OC4 X 1 voltage at this digital inputs
relay status X 1 state of relays 1-6, 1=ON, 0=OFF
Parameter pages
Parameters marked with "Disp. only" are for Information only and cannot
be adjusted.
The numbers in column "Level" show the user level, where this parameters
are displayed.