System information
™
Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
45
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Cradle Position Switch
Three series of optional auxiliary switches are available for the cradle:
•
Cradle position switches (CE) to indicate the connected position.
•
Cradle position switches (CD) to indicate the disconnected position. This 
position is indicated when the required clearance for isolation of the power 
and auxiliary circuits is reached.
•
Cradle position switches (CT) to indicate the test position. In this position, the 
power circuits are disconnected and the auxiliary circuits are connected.
Table 41: Cradle Position Switch Characteristics
Circuit Breaker Type
NT NW
1
Possible Ring-Terminal Combinations
CE CD CT CE CD CT CE CD CT
Maximum Push-In Switches with 
Standard Actuators
3213
1
3
1
3
1
1b 1a 1b
1b 1a, 1b 1b
1a, 2b 1a, 2b 1a
With Additional Actuators
9 0 0 1a, 2b 2a, 1b 1b
6 3 0 2a, 1b 1a, 2b 1b
3 6 0 1a 1a 1a
6 0 3 3a 3a 1a
Breaking 
Capacity at a 
Power Factor 
(p.f) of 0.3
Standard (100 mA/24 V minimum load) 3b 3b 1b
Vac
240 8 A 8 A
Additional Actuators for Cradle 
Position Switches on Masterpact NW 
Circuit Breakers
A set of additional actuators may be 
installed on the cradle to change or add 
the functions of the cradle position 
switches. Each standard actuator can be 
replaced by any other actuator to 
change the function of the cradle 
position switch.
380 8 A 8 A
480 8 A 8 A
600/690 6 A 6 A
Vdc
24/48 2.5 A 2.5 A
125 0.8 A 0.8 A
250 0.3 A 0.3 A
Low-Level (2 mA/15 V minimum load)
Vac
24/48 5 A 5 A
240 5 A 5 A
380 5 A 5 A
Vdc
24/48 2.5 A 2.5 A
125 0.8 A 0.8 A
250 0.3 A 0.3 A
Figure 11: Cradle Position Switch Actuators
Cradle Position 
Switch (CE, CD, CT)
Actuator for up to Three 
CE Switches (standard)
Actuator for up to Three 
CD Switches (standard)
Actuator for up to Three 
CT Switches (standard)