Comfort Panels ___________________ Preface 1 ___________________ Overview SIMATIC HMI HMI devices Comfort Panels 2 ___________________ Safety instructions Mounting and connecting the 3 ___________________ HMI device 4 ___________________ Commissioning the device 5 ___________________ Commissioning a project Operating Instructions 6 ___________________ Operating a project 7 ___________________ Maintenance and care 8 ___________________ Technical specifications A ___________________ Technical Support
Legal information Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
Preface Purpose of the operating instructions These operating instructions contain information based on the requirements defined by DIN EN 62079 for mechanical engineering documentation. This information relates to the place of use, transport, storage, mounting, use and maintenance. These operating instructions are intended for: ● Users ● Commissioning engineers ● Maintenance personnel Read especially the information in the chapter "Safety instructions" (Page 25).
Preface CAUTION Manual belongs to HMI device The supplied manual belongs to the HMI device and is also required to repeat commissioning. Keep all supplied and supplementary documentation for the entire service life of the HMI device. Provide all stored documents to subsequent owners of the HMI device.
Preface Naming conventions Term Applies to Plant System Machining center One or more machines Comfort HMI device KP400 Comfort KP1500 Comfort HMI device KTP400 Comfort TP1500 Comfort KP700 Comfort TP1900 Comfort TP700 Comfort TP2200 Comfort KP900 Comfort TP900 Comfort KP1200 Comfort TP1200 Comfort Key model KP400 Comfort KP1500 Comfort Key HMI device KP700 Comfort KP900 Comfort KP1200 Comfort Touch model KTP400 Comfo
Preface Comfort Panels 6 Operating Instructions, 03/2012, A5E03404994-02
Table of contents Preface ...................................................................................................................................................... 3 1 2 3 Overview.................................................................................................................................................. 13 1.1 Product description ......................................................................................................................13 1.
Table of contents 4 Commissioning the device ....................................................................................................................... 55 4.1 4.1.1 4.1.2 4.1.3 Overview ..................................................................................................................................... 55 Backup design............................................................................................................................. 55 Changing memory cards .........
Table of contents 4.4.12 4.4.12.1 4.4.12.2 4.4.12.3 4.4.12.4 4.4.12.5 4.4.12.6 4.4.13 4.4.13.1 4.4.13.2 4.4.13.3 4.4.13.4 4.4.14 4.4.15 4.4.16 5 Configuring network operation ...................................................................................................117 Overview of network operation ..................................................................................................117 Setting the device name of the HMI device ..........................................................
Table of contents 6 7 8 Operating a project ................................................................................................................................ 153 6.1 Overview ................................................................................................................................... 153 6.2 Function keys ............................................................................................................................ 156 6.3 Direct keys...............
Table of contents A B 8.4 8.4.1 8.4.2 8.4.3 8.4.3.1 8.4.3.2 8.4.3.3 8.5 8.5.1 8.5.2 8.5.3 8.5.4 8.5.5 8.5.6 8.5.7 8.5.8 8.5.9 8.5.10 Technical specifications .............................................................................................................191 KP400 Comfort to KP1200 Comfort, KTP400 Comfort to TP1200 Comfort ..............................191 KP1500 Comfort, TP1500 Comfort to TP2200 Comfort ............................................................193 Ambient conditions......
Table of contents Comfort Panels 12 Operating Instructions, 03/2012, A5E03404994-02
1 Overview 1.1 Product description SIMATIC HMI Comfort Panels are a fully redesigned product line of the Touch Panels and Key Panels. The product line includes the following models: ● Five key panels (operated by keyboard) with 4", 7", 9", 12" and 15" displays ● Six touch panels (operated by touch screen) with 7", 9", 12", 15", 19" and 22" displays.
Overview 1.1 Product description Features of the SIMATIC HMI Comfort Panels Enclosure Plastic enclosure for the 4" model Aluminum pressure enclosures for all 7" and larger models Mounting format Mounting and operation of the touch models in horizontal and vertical format The respective format must be selected during the configuration of the user interface.
Overview 1.2 Product package 1.2 Product package The following components are included in the product package of the HMI device.
Overview 1.3 Configuration of the devices 1.3 Configuration of the devices 1.3.1 KP400 Comfort and KTP400 Comfort The following sections describe the basic design of the KP400 Comfort and KTP400 Comfort HMI devices.
Overview 1.
Overview 1.3 Configuration of the devices 1.3.2 KP700 Comfort to KP1500 Comfort, TP700 Comfort to TP2200 Comfort The following sections describe the basic design of the devices with 7" or larger displays, using the KP700 Comfort and TP700 Comfort as examples. The enclosure dimensions and form for the other models may differ from the illustrations shown. Front view The figure below shows the front view of the HMI devices, using the KP700 Comfort and TP700 Comfort as examples.
Overview 1.3 Configuration of the devices Side view The figure below shows the side views of the HMI devices, using the KP700 Comfort and TP700 Comfort as examples. ① ② ③ 1.3.3 Recesses for mounting clamps Interfaces Mounting seal Ports Interfaces for the 4" models The figure below shows the KP400 and KTP400 Comfort interfaces.
Overview 1.
Overview 1.4 Accessories 1.4 Accessories Accessories are not included in the product package of the HMI device, but can ordered in the Internet at Industry Mall (http://mall.automation.siemens.com). This section contains the number of accessories available at the time of publication of the operating instructions. Converters and adapters Name Order no.
Overview 1.5 The HMI device in the operating process 1.5 The HMI device in the operating process The HMI device is part of the operating process. The following two phases are key to the way the HMI device is integrated in the process: ● Configuration ● Process management Configuration During the configuration phase, you create the user interfaces for operation and monitoring of the technical process to a configuring PC with WinCC as of version 11.
Overview 1.6 Software options 1.6 Software options The following software add-ons are available for the HMI devices: Add-on WinCC /Sm@rtServer 1 Description 1 The WinCC /Sm@rtServer add-on enables you to access a remote HMI device from the HMI device or PC via Ethernet. It also enables you to set up communication between different HMI systems. WinCC /Audit 1 The WinCC /Audit add-on extends the HMI device to include functions for recording operations in an audit trail and electronic signature.
Overview 1.
Safety instructions 2.1 2 General safety instructions Open equipment and the Machinery Directive WARNING The device constitutes open equipment The device constitutes open equipment. This means that the device may only be installed in enclosures or cabinets which provide front access for operating the device. Access to the enclosure or cabinet in which the device is installed should only be possible by means of a key or tool and for trained and authorized personnel.
Safety instructions 2.2 Security information High frequency radiation CAUTION Unwanted operating states High-frequency radiation, for example from cellular phones, interferes with device functions and can cause device malfunction. This causes injury and damages the plant. Avoid high-frequency radiation: Remove the sources of radiation from the vicinity of the device. Switch off radiating devices. Reduce the radio output of radiating devices. Observe the information on electromagnetic compatibility.
Safety instructions 2.3 Notes about usage 2.3 Notes about usage CAUTION HMI device approved for indoor use only The HMI device may be damaged if operated outdoors. Operate the HMI device indoors only. Industrial applications The HMI device is designed for industrial applications.
Safety instructions 2.
Mounting and connecting the HMI device 3.1 3 Preparation for mounting Select the mounting location of the HMI device Points to observe when selecting the mounting location: ● Position the HMI device so that it is not subjected to direct sunlight. ● Position the HMI device such that it is ergonomically accessible for the operator. Choose a suitable mounting height. ● Ensure that the HMI device air vents are not covered as a result of installation. ● Note the permissible mounting positions. 3.1.
Mounting and connecting the HMI device 3.1 Preparation for mounting 3.1.2 Checking the operating conditions Note the following aspects before installing the HMI device: 1. Familiarize yourself with the standards, approvals, EMC parameters and technical specifications for operation of the HMI device. This information is available in the following sections: – Certificates and approvals (Page 169) – Electromagnetic compatibility (Page 172) 2.
Mounting and connecting the HMI device 3.1 Preparation for mounting Mounting position Select one of the approved mounting positions for your HMI device. The approved mounting positions are described in the following sections. Mounting in horizontal format All HMI devices are suitable for horizontal mounting positions.
Mounting and connecting the HMI device 3.1 Preparation for mounting 3.1.
Mounting and connecting the HMI device 3.1 Preparation for mounting 3.1.5 Preparing the mounting cutout NOTICE Stability of the mounting cutout The material in the area of the mounting cutout must provide sufficient strength to guarantee the enduring and safe mounting of the HMI device. The force of the clamps or operation of the device may not lead to deformation of the material in order to achieve the degrees of protection described below.
Mounting and connecting the HMI device 3.1 Preparation for mounting Dimensions of the mounting cutout w w h +1 0 h +1 0 .3 .73 .3 73 .3 73 .3 73 .3 73 73 73 Width and height should be reversed accordingly when mounting in vertical format. 3.1.
Mounting and connecting the HMI device 3.1 Preparation for mounting Procedure Proceed as follows: 1. Edit the template on a PC and then print it. 2. Apply a fixing spray film to the labeling strips. The printout can be made water and smudge-proof with a fixing spray. The color printer ink will not bleed onto the keyboard foil as well. 3. Cut out the labeling strip. 4. Ensure that the corners are cut at a 45° angle to it easier to slide them into the slot. 5.
Mounting and connecting the HMI device 3.1 Preparation for mounting The image below shows the positions of the KP1500 Comfort guides and labeling strips. ① ② ③ ④ ⑤ ⑥ Guide for labeling strips F1, F3 ... F15 Guide for labeling strips F2, F4 ... F16 Guide for labeling strips F17 ... F22 Guide for labeling strips F23 ... F26 Guide for labeling strips F27 ... F31 Guide for labeling strips F32 ... F36 Result The labeling strips protrude approximately 3 cm out of the slot.
Mounting and connecting the HMI device 3.2 Mounting the device 3.2 Mounting the device Position of the mounting clamps To ensure the necessary degree of protection on the HMI device, you need to use the mounting clamps with the positions listed below. The positions of the mounting clamps are marked by stamps on the cutouts. Fit mounting clamps in all the stamped cutouts. The following table shows the type, number and position of mounting clamps needed for the various HMI devices.
Mounting and connecting the HMI device 3.2 Mounting the device Comfort HMI device TP700 Mounting clamps Type Quantity Aluminum mounting clamps 10 Position on the HMI device 73 &RPIRUW 12 KP700 TP900 TP1200 .3 &RPIRUW 73 &RPIRUW 73 &RPIRUW KP900 16 KP1200 .3 &RPIRUW .3 &RPIRUW KP1500 Steel mounting clamps 12 TP1500 .
Mounting and connecting the HMI device 3.2 Mounting the device Procedure NOTICE Risk of guaranteed degree of protection not being met If the mounting seal is damaged or protrudes beyond the HMI device, the degree of protection is not ensured. Checking the placement of the mounting seal To avoid leakage around the mounting cutout, do not install the mounting seal turned inside out. If the mounting seal is damaged, order a replacement seal.
Mounting and connecting the HMI device 3.2 Mounting the device Proceed as follows: 1. Insert the HMI device into the mounting cutout from the front. 2. Insert the mounting clamp into the cutout provided on the HMI device. 3. Tighten the mounting clamp with the threaded pin. Note Adhere to the permissible torque when tightening the threaded pin of the mounting clamp: 4" model: 0.2 Nm 7" to 22" models: 0.5 Nm 4. Repeat steps 2 and 3 for all mounting clamps. 5. Check the fit of the mounting seal.
Mounting and connecting the HMI device 3.3 Connecting the device 3.3 Connecting the device 3.3.1 Notes on connection Requirement ● The HMI device must be mounted according to the specifications of these operating instructions. ● Always use shielded standard cables for the data cable. Additional information is available in the catalog and online order system at Industry Mall (http://mall.automation.siemens.com). Connection sequence Connect the HMI device in the following sequence: 1.
Mounting and connecting the HMI device 3.3 Connecting the device 3.3.2 Connecting the equipotential bonding circuit Differences in electrical potential Differences in electrical potential can develop between spatially separated plant components. Such electrical potential differences can lead to high equalizing currents over the data cables and therefore to the destruction of their interfaces.
Mounting and connecting the HMI device 3.3 Connecting the device Wiring diagram The figure below shows the equipotential bonding connection for the TP700 Comfort; it also applies to all other Comfort devices. 73 ① ② ③ ④ ⑤ ⑥ ⑦ Control cabinet Equipotential bonding rail Equipotential bonding cable PROFINET data line PROFIBUS data line Cable clip Ground connection CAUTION Damage to the interface modules possible Cable shielding is not suitable for equipotential bonding.
Mounting and connecting the HMI device 3.3 Connecting the device 3.3.3 Connecting the power supply CAUTION Safe electrical separation Use only 24 VDC power supply units with safe electrical isolation in accordance with IEC 60364-4-41 or HD 384.04.41 (VDE 0100, Part 410), e.g. to PELV standard. The supply voltage must be within the specified voltage range. Otherwise, malfunction at the HMI device cannot be ruled out.
Mounting and connecting the HMI device 3.3 Connecting the device Connecting the power supply terminal NOTICE Damage Do not tighten the screws of the power supply terminal if it is plugged into the HMI device. The pressure from the screwdriver may otherwise damage the HMI device socket. Only connect the wires when the power supply terminal is withdrawn. Connect the power supply terminal to the cables of the power supply as shown in the figure above.
Mounting and connecting the HMI device 3.3 Connecting the device 3.3.4 Connecting the configuration PC Wiring diagram The following figure shows how to connect the HMI device to a configuration PC. ① ② Connection to the configuration PC via PROFINET (LAN) Connection to the configuration PC via USB type Mini-B The ports are described in the specifications. Note Alternatively, you can also connect the HMI device to the configuration PC via PROFIBUS.
Mounting and connecting the HMI device 3.3 Connecting the device Procedure Proceed as follows: 1. Switch off the HMI device. 2. Switch on the configuration PC. 3. Connect the HMI device to the configuration PC either via the PROFINET (LAN) or via the USB type Mini-B interface. Please note the following for USB connection: – Connect the USB Mini B connector of the USB cable to the USB type Mini B interface of the HMI device.
Mounting and connecting the HMI device 3.3 Connecting the device 3.3.5 Connecting the PLC Wiring diagram The figure below shows how to connect the HMI device to a PLC. ① ② Connection to the PLC via PROFINET (LAN) Connection to the PLC via PROFIBUS NOTICE Only use approved cables If you do not use approved cables to connect a SIMATIC S7 controller, you may experience malfunctions. Only use approved cables to connect a SIMATIC S7 controller. Standard cables are available for the connection.
Mounting and connecting the HMI device 3.3 Connecting the device 3.3.6 Connecting a USB device Below are examples of devices you can connect to the USB type A interfaces of the HMI device: ● External mouse ● External keyboard ● Printer ● USB memory stick ● Industrial USB Hub 4 Industrial USB hub 4 can be obtained using order number 6AV6671-3AH00-0AX0.
Mounting and connecting the HMI device 3.3 Connecting the device 3.3.7 Connecting a printer Wiring diagram The following figure shows the connection between the printer and HMI device. Note when connecting NOTICE Data exchange cables If you use cables without a metallic netting shield between the HMI device and printer, you may experience functional problems. Only use cables with metal-braided shielding grounded at both ends for connecting the HMI device and printer.
Mounting and connecting the HMI device 3.3 Connecting the device 3.3.8 Connecting an audio device You can use the following ports for audio devices: ● "Line Out", for example, for active speakers or external audio amplifier ● "Line In" for audio sources with line-in level NOTICE Cable to "Line Out" interface may cause increased emitted interference If you connect an audio device to the "Line-Out" interface, the connection cable of the audio may cause increased emitted interference.
Mounting and connecting the HMI device 3.3 Connecting the device 3.3.9 Switching on and testing the HMI device Procedure Proceed as follows: 1. Switching on the power supply. The screen lights up after power is switched on. An animated graphic is displayed during startup. If the HMI device fails to start, you have probably crossed the wires on the power supply terminal. Check the connected wires and change their connection. The Loader opens after the operating system has started.
Mounting and connecting the HMI device 3.3 Connecting the device Result The Loader appears again. Note When restarting the system, a project may already be loaded on the HMI device. The project will then start after an configurable delay or when you press the "Start" button. Use the relevant operating element to close the project. Refer to your plant documentation to find any additional information on this topic. Function test Perform a function test following commissioning.
Mounting and connecting the HMI device 3.3 Connecting the device Attaching a strain relief With the 4" and 7" models, protect the cables with a separate strain relief. Attach the strain relief to the HMI device. The following figure shows the fixing elements of the strain relief for the 4" model: ① ② Borehole for Torx screw The strain relief is secured with the Torx screw of the connection for equipotential bonding. Before you attach the strain relief, unscrew the Torx screw.
Commissioning the device 4.1 Overview 4.1.1 Backup design 4 Introduction The HMI devices use the following memory types: ● Internal memory ● Memory card ● System memory card You can also connect a USB mass storage device to the USB port. Internal memory The following data is saved in the internal memory: ● Operating system ● Project file ● License keys ● User administration ● Recipes*) *) To save recipes in the internal memory, select "\Flash\" as the path in WinCC.
Commissioning the device 4.1 Overview Memory card The following data are saved on the memory card: ● Logs ● Backups ● Recipes*) *) To save recipes on the memory card, select "\StorageCard SD\" as the path in WinCC. You can use commercially available memory cards with the "SD(IO / HC)" or "MMC" format. For data consistency reasons, Siemens recommends the use of the SIMATIC HMI Memory Card as the memory card, see Accessories (Page 21).
Commissioning the device 4.1 Overview Slots for memory and system memory card The slots for memory card and system memory card are on the back of the enclosure for the 7" models. The memory cards and system memory cards are thus accessible at the rear of the cabinet. The memory cards and system memory cards are protected by a safety lock. The memory cards and system memory cards can be hot-swapped during ongoing operation of the HMI device. The slots are on the back of the enclosure for the 4" models.
Commissioning the device 4.1 Overview 4.1.2 Changing memory cards Introduction The memory cards and system memory cards are protected by a safety lock. The memory card and system memory card can be hot-swapped during ongoing operation of the HMI device. NOTICE Potential loss of data The data on the memory card is lost if you attempt to remove it while the HMI device is accessing its data. Do not remove the memory card while data is being accessed. Observe the corresponding alarms on the screen.
Commissioning the device 4.1 Overview Requirement Memory card and/or system memory card are read-only Procedure Note Format of the system memory card Only a SIMATIC HMI Memory Card ≥ 2 GB may be used as a system memory card. All other memory cards are not recognized as system memory card by the HMI device. Proceed as follows: 1. Push the safety switch to the appropriate position. 2. To remove the memory card and/or system memory card, briefly press the card in question.
Commissioning the device 4.1 Overview 4.1.3 Front operator controls Touch HMI device You can operate the Touch HMI devices with the touch screen. All operating elements required for operation are displayed on the touch screen once the HMI device has started. NOTICE Unintentional action possible Do not carry out several operations simultaneously. You may otherwise trigger an unintentional action.
Commissioning the device 4.1 Overview Key HMI devices You operate the key HMI devices using the system keys and the function keys. The functions of the function keys are defined during configuration. The function keys have no function before the project is opened in the HMI device.
Commissioning the device 4.2 Using the service concept 4.2 Using the service concept If the service concept is enabled, the HMI device stores all data necessary for the operation on the system memory card. You can insert the system memory card into any HMI device of the same type. After copying the data and restarting the same-type HMI device is operational.
Commissioning the device 4.2 Using the service concept 4.2.2 Replacing HMI device Requirement ● The service concept is enabled on the defective HMI device. ● A replacement device of the same type is available. The slot for the system memory card is enabled on the replacement device (factory state). If required, check the setting in the Control Panel under "OP Properties", "System Card" tab, see section "Disabling the service concept (Page 64)". Procedure Proceed as follows: 1. Switch off the HMI device.
Commissioning the device 4.2 Using the service concept 4.2.3 Disabling the service concept If you do not wish to continually back up the data of an HMI device on a memory card to ensure information security, you can disable the service concept. Procedure Proceed as follows: 1. Open the Control Panel. 2. Open the "OP Properties" dialog by using the "OP" icon. 3. Open to the "System Card" tab. 4. Disable the service concept with "Disable & Reboot". 5. Restart the HMI device.
Commissioning the device 4.3 Operating the device 4.3 Operating the device 4.3.1 Loader Overview The loader is displayed automatically when the HMI device is switched on. If there is a project on the HMI device, it is started automatically after a delay time. If you operate the loader during this delay time, the project no longer starts automatically. If you stop on the HMI device Runtime or show the Windows CE Desktop, the loader will open automatically.
Commissioning the device 4.3 Operating the device The following figure shows the open Start menu. Depending on the software installed, other symbols may be displayed in the desktop's status bar. Protection against unauthorized use You can protect the control panel against unauthorized access by using a password. If the Control Panel protected with a password, "SecureMode" is automatically enabled. "SecureMode" additionally protects the taskbar and the Windows CE Desktop.
Commissioning the device 4.3 Operating the device 4.3.2 Control Panel The HMI device's Control Panel is similar to the control panel on a PC.
Commissioning the device 4.3 Operating the device 4.3.3 Installed programs Overview The following programs are installed on the HMI devices by default: ● Viewers for documents in "PDF", "Excel" and "Word" format ● Media Player for Windows CE ● Internet Explorer for Windows CE The programs can be found on the desktop or in the Start menu under "Programs". Each of these programs can also be opened from the HMI project.
Commissioning the device 4.3 Operating the device Internet Explorer Internet Explorer for Windows CE and the Internet Explorer version which can run on a PC differ in terms of functionality. Internet Explorer for Windows CE has separate proxy settings that are independent of the settings in the control panel of the HMI device. You can find additional information at the Microsoft website. 4.3.4 Reference for system keys You operate key HMI devices using the system keys.
Commissioning the device 4.3 Operating the device The following table shows the system key functions that work both in the Control Panel and in the project: Key or key combination Function Switch between upper and lower case: LED on: Upper case LED off: Lower case Deletes the character left of cursor. Moves to the next operating element in the TAB order. Moves to the previous operating element in the TAB order. Deletes the character right of cursor. Toggles "overwrite" mode on or off.
Commissioning the device 4.3 Operating the device Operating Windows CE and the Explorer The following table shows the system key functions when operating Windows CE and the Explorer: Key or key combination Function Enables the taskbar and opens the Start menu. Displays the loader. Opens the task manager. Toggles between the Windows CE Desktop and the Explorer. Navigates to the directory above. Selects the first entry. Selects the last entry. Opens the shortcut menu. Displays the properties.
Commissioning the device 4.3 Operating the device Operating the Control Panel and dialogs The following table shows the system key functions when operating the Control Panel and dialogs: Key or key combination Function Activates the menu. To navigate the menu, use the cursor keys. Selects or clears a check box. The following figure shows the "Enable Transfer" and "Remote Control" check boxes: Opens a drop-down list box. Selects a list item without closing the dialog. Navigates through tabs or options.
Commissioning the device 4.3 Operating the device Operating a project The following table shows the system key functions when operating an ongoing project: Key or key combination Function Acknowledges the currently displayed error alarm or all the alarms of an alarm group as group acknowledgment. A lit LED indicates unacknowledged fault alarms. Calls up the configured infotext for an operating element. When the LED is let, it indicates that an infotext is available.
Commissioning the device 4.3 Operating the device Requirement Cursor must be in the text box. Procedure Proceed as follows: 1. Press the respective key repeatedly until the desired character is selected in the preview. The mapping of system keys to letters and numbers can be restricted within a given context. The desired character is applied in about one second or immediately after pressing a different button. 2. To toggle between upper and a lower case, press .
Commissioning the device 4.3 Operating the device 4.3.6 Using the screen keyboard Introduction Use the screen keyboard to enter alphanumeric values. If you connect an external keyboard to an HMI device with a touch screen, the screen keyboard is not displayed. You operate the screen keyboard like a normal keyboard. If you touch an operating element with a value, the screen keyboard opens automatically. Depending on the operating element, either the alphanumeric or numerical screen keyboard opens.
Commissioning the device 4.
Commissioning the device 4.
Commissioning the device 4.3 Operating the device Requirement The screen keyboard is open. Procedure Proceed as follows: 1. Enter the desired value using the keys. 2. Display the available special characters if needed using . 3. Display the numerical keypad if needed using . 4. To complete entry: – If you want apply the selected value, press "Return". – If you want discard the selected value, press "Esc". Result The screen keyboard closes.
Commissioning the device 4.4 Configuring the device 4.4 Configuring the device 4.4.1 Reference for functions Overview of functions The following table shows the settings in the Control Panel.
Commissioning the device 4.
Commissioning the device 4.4 Configuring the device Procedure Proceed as follows: 1. Open the "Siemens HMI Input Panel - Options" dialog with the "InputPanel". icon. 2. If you want to change the size of the screen keyboard, select the "Show Resize Button" check box. The next time you open the screen keyboard, the icon for changing the size of the screen keyboard will appear. 3. Use "Open Input Panel" to open the screen keyboard. 4.
Commissioning the device 4.4 Configuring the device 4.4.2.2 Setting the character repeat The details provided below will explain how to set the character repetition and the associated delay for the keyboard or screen keyboard. Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the "Keyboard Properties" dialog with the Keyboard icon. 2. If you want to enable character repetition, select the "Enable character repeat" check box. 3.
Commissioning the device 4.4 Configuring the device 4.4.2.3 Setting the double-click You can start applications in the Control Panel and in Windows CE with a double-click. A double-click corresponds to two brief touches in sequence. In the "Mouse Properties" dialog, make the following adjustments for operation with the touch screen or external mouse: ● Interval between two touch contacts on the touch screen ● Interval between mouse clicks Requirement The Control Panel is open.
Commissioning the device 4.4 Configuring the device Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the ""OP Properties" " dialog with the "OP". icon. 2. Open to the "Touch" tab. 3. Calibrate the touch screen with "Recalibrate". The following dialog opens: &DUHIXOO\ SUHVV DQG EULHIO\ KROG VW\OXV RQ WKH FHQWHU RI WKH WDUJHW 5HSHDW DV WKH WDUJHW PRYHV DURXQG WKH VFUHHQ 4. 4" to 12" models: Briefly touch the center of the calibration crosshairs.
Commissioning the device 4.4 Configuring the device 5. Proceed as in step 4 for all four following positions. Once you have touched all the positions of the calibration crosshairs, the following dialog appears: New calibration settings have been measured. Tape the screen to register saved data. Wait for 30 seconds to cancel saved data and keep the current setting. Time limit: 30 sec 6. To apply the calibration, touch the screen within 30 seconds.
Commissioning the device 4.4 Configuring the device 4.4.3 Changing password protection You can protect access to the Control Panel with a password. If you configure password protection, "SecureMode" is automatically enabled for the HMI device. "SecureMode" additionally protects the taskbar and the Windows CE Desktop against unauthorized access. Requirement The Control Panel is open.
Commissioning the device 4.4 Configuring the device Result The "secure mode" label is displayed on the Windows CE Desktop: If you attempt to operate the Control Panel, taskbar or Windows CE Desktop, you are prompted for a password. "SecureMode" is then switched off. "Switching "SecureMode" on again To switch SecureMode back on, double-click the SecureMode icon on the Windows CE Desktop.
Commissioning the device 4.4 Configuring the device Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the "Date/Time Properties" dialog with the "Date/Time Properties" icon. 2. Select the appropriate time zone for the HMI device under "Time Zone". 3. Confirm your entry with "Apply". The time of day shown under "Current Time" is adjusted correspondingly to the selected time zone. 4. Set the date in the calendar. 5. Set the current time of day under "Current Time". 6.
Commissioning the device 4.4 Configuring the device See also Reference for functions (Page 79) Synchronizing the time via the time server (Page 111) 4.4.4.2 Changing regional settings In different countries, for example, the date, time and decimal points are displayed differently. You can adjust this display to meet the requirements of different regions. The country-specific settings apply to the current project. If the project language is changed, the country-specific settings are also changed.
Commissioning the device 4.4 Configuring the device 4.4.4.3 Backup registry information You can install and uninstall your own programs on the HMI devices under Windows CE. You need to back up the registry settings after installation or removal. You can back up the following data to the internal memory: ● Registry Information ● Temporary files "Temporary files" are all files which are not saved under "\flash". Temporary files are no longer available after restarting the HMI device.
Commissioning the device 4.4 Configuring the device Result Registry entries and files from the temporary memory are saved in the internal memory of the HMI device. The HMI device uses the saved registry entries the next time it starts. The saved files are written back into the temporary memory. The HMI device uses the saved registry information the next time it starts. The temporary files are copied back. See also Reference for functions (Page 79) 4.4.4.
Commissioning the device 4.4 Configuring the device Procedure Proceed as follows: 1. Open the "Display Properties" dialog with the Display icon. 2. To change the color depth, open the "Settings" tab. – Select the desired color depth under "Color Quality". – Confirm with "Apply". A change of the color depth only takes effect after rebooting the HMI device. 3. To change the brightness, open the "Brightness" tab. The figure below shows the TP1500 Comfort "Brightness" tab as an example.
Commissioning the device 4.4 Configuring the device 4. To change the screen orientation of a touch HMI device, open the "Orientation" tab. – If you installed the HMI device vertically, select "Portrait". – If you installed the HMI device horizontally, select "Landscape". – Confirm with "Apply". 5. Close the dialog with "OK". Result The screen settings have been changed. When you change the screen orientation, the setting only takes effect after you reboot the HMI device.
Commissioning the device 4.4 Configuring the device 4.4.4.5 Setting the screen saver You can set the following time intervals on the HMI device: ● Automatic reduction of the screen backlighting ● Automatic activation of the screensaver The configured function is automatically activated if the HMI device is not operated within the specified period of time. NOTICE Reduce backlighting The brightness of the backlighting decreases incrementally during its operational life.
Commissioning the device 4.4 Configuring the device 3. Select the type of screen saver: – To display an animation, select "Standard". – To switch off backlighting, select "Blank Screen". Backlighting is completely switched off. This will increase the service life of the screen. Energy consumption is reduced. 4. Confirm your entries with "OK". Result The screen saver and the reduced backlighting for the HMI device is set.
Commissioning the device 4.4 Configuring the device 4.4.4.6 Changing the printer properties The HMI device can print on local printers or network printers. You can print hardcopies and reports on a network printer. Line printing of alarms is only possible on a local printer. You can find the list of current printers and required settings for HMI devices in the Internet at Printers approved for SIMATIC Panels and Multi Panels (http://support.automation.siemens.com/WW/view/en/11376409).
Commissioning the device 4.4 Configuring the device 4.4.4.7 Enabling sound and setting sound volume You can activate an acoustic feedback for keyboard and touch screen operations. A sound is emitted with each touch or activation of a key. Requirement The Control Panel is open. Note If you deactivate the settings under "Enable sounds for", no more acoustic signals will be emitted during inadvertent operations. Procedure Proceed as follows: 1.
Commissioning the device 4.4 Configuring the device 4.4.4.8 Assigning sound to an event When acoustic feedback is activated, a sound is used to report an event. You can select the sound to reflect the event. The sound is output by the loudspeaker of the HMI device. Note Acoustic feedback with sounds is support from the 7" models. Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the "Volume & Sounds Properties" dialog with the Volume & Sounds icon. 2. Open the "Sound" tab. 3.
Commissioning the device 4.4 Configuring the device 4.4.4.9 Restarting the HMI device Required restart The HMI device must be restarted in the following cases: ● You have enabled or disabled PROFINET IO services. ● You have changed the time zone setting. ● You have changed the automatic daylight savings and standard setting ● You have changed the color depth of the screen. ● You have changed the orientation of the screen (Touch HMI devices only).
Commissioning the device 4.4 Configuring the device 3. Use "Reboot" to start the selection process for restart the HMI device. The following alarm is displayed: 4. To restart the HMI device, press "Reboot". All unsaved data are lost when you reboot. 5. To set the HMI device to the mode for bootstrapping, press "Prepare for Restart". 6. To cancel the restart of the HMI device, press "NO". Result The HMI device restarts.
Commissioning the device 4.4 Configuring the device 4.4.4.10 Displaying information about the HMI device You will need specific information about the device if you contact Technical Support. Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the "OP Properties" dialog with the OP icon. 2. Open the "Device" tab. Comfort devices of 15" or more come with the second network adapter "PN_X3".
Commissioning the device 4.4 Configuring the device 4.4.4.11 Displaying system properties The general system-specific information provides you with information about the processor, operating system and memory. The system properties are device-specific and may therefore deviate from that of your HMI device. Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the ""System Properties" " dialog with the "System". icon. 2. Open the "General" tab.
Commissioning the device 4.4 Configuring the device 4.4.4.12 Displaying memory distribution The "Memory" system-specific information provides you with information about the distribution and size of the memory in the HMI device. NOTICE "Memory" tab Do not change the memory distribution in the "Memory" tab. Requirement The Control Panel is open. Procedure 1. Open the "System Properties" dialog with the System icon. 2. Open the "Memory" tab. 3. Determine the HMI device's current memory structure 4.
Commissioning the device 4.4 Configuring the device 4.4.5 Setting storage location There are various storage locations available for storing the compressed source file of your project, for example, the external memory card or a network drive. Requirement The Control Panel is open. Procedure 1. Open the "Transfer Settings" dialog with the Transfer icon. 2. Open the "Directories" tab.
Commissioning the device 4.4 Configuring the device 4.4.6 Setting the delay time To specify the starting characteristics of the project after switching on the HMI device, you can set a delay time. The delay time is a period in which the loader is displayed on the HMI device. If you operate the loader during this time period, the project no longer starts automatically. Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the "Transfer Settings" dialog with the Transfer icon. 2.
Commissioning the device 4.4 Configuring the device 4.4.7 Setting the uninterruptible power supply A UPS ensures that the HMI device is shut down in a controlled manner after a configurable buffer time in the event of a power failure. This avoids the loss of data. Connect the UPS to the USB port of the HMI device. You can also configure a message or controlled shutdown of the HMI device if the UBS port is faulty.
Commissioning the device 4.4 Configuring the device 3. If a controlled shutdown of the HMI device is to be performed following interruption of the power supply: – Select "Battery mode". – Under "min" and "s", specify the time after which the Runtime software application is automatically closed on the HMI device.
Commissioning the device 4.4 Configuring the device 4.4.8 State of uninterruptible power supply If you have connected a UPS to a USB port of the HMI device, you can display the monitoring status of this port. Requirement ● The Control Panel is open. ● The UPS is connected to the 24-V input and to the HMI device's USB port. ● The "Uninterruptible Power Supply (UPS) with USB support" option is transferred to the HMI device with ProSave. ● UPS settings are configured Procedure Proceed as follows: 1.
Commissioning the device 4.4 Configuring the device 4.4.9 Enabling PROFINET services PROFINET services must be enabled on the HMI device in the following circumstances: ● The HMI device is connected to the PLC via PROFINET. ● Function keys or buttons are configured as PROFINET IO direct keys in the project. ● The backlighting of the HMI device is to be controlled with PROFIenergy. Note If you enable PROFINET services, you cannot use the RS 422/RS 485 port for serial operation.
Commissioning the device 4.4 Configuring the device Procedure Proceed as follows: 1. Open the "PROFINET" dialog with the PROFINET icon. Comfort devices of 15" or more come with the second network adapter "PN_X3". 2. To enable the PROFINET services, activate "PROFINET IO enabled". NOTICE Inconsistent device name If the device name does not match the device name entered in the WinCC, the direct keys will not work. Use the device name from WinCC.
Commissioning the device 4.4 Configuring the device 4.4.10 Synchronizing the time via the time server Introduction To obtain the time of the HMI device from a time server, you can specify up to four different time servers. The time is synchronized via the "Network Time Protocol" (NTP). You additionally specify the synchronization cycle for the time. The synchronization cycle applies to all configured time servers. You can separately test the availability of each time server.
Commissioning the device 4.4 Configuring the device 5. Press "Configure" to open the "Time Server Configuration" dialog for configuring the time servers: 6. Enter the DNS name of the time server under "Name". Alternatively, you can enter the IP address of time server. 7. Use "Test" to test the availability of the time server. The connection to the time server is established and the time is displayed under "DateTime:". The IP address of the time server is also entered under "Address". 8.
Commissioning the device 4.4 Configuring the device 4.4.11 Changing transfer settings 4.4.11.1 Configuring the data channel In the transfer settings of the HMI device, set the following: ● Releasing and locking a data channel ● Enabling and disabling automatic transfer ● Configuring data channels If you lock the data channels, the HMI device is protected against unintentional overwriting of the project data and HMI device image.
Commissioning the device 4.4 Configuring the device Procedure Proceed as follows: 1. Open the "Transfer Settings" dialog with the Transfer Settings icon. 2. Open the "Channel" tab. 3. To release the data channels of the HMI device, select "Enable Transfer". 4. To enable automatic transfer, select "Remote Control". 5. Configure at least one data channel: – Select the data channel. – Configure the data channel using "Properties...". Note: The "USB device" data channel has no configurable properties. 6.
Commissioning the device 4.4 Configuring the device 4.4.11.2 Changing MPI/PROFIBUS DP settings Introduction The communication settings for MPI or PROFIBUS DP are defined in the project of the HMI device. In the following cases, the transfer settings might have to be changed: ● The first time the project is transferred ● If changes are made to the project but are only applied later NOTICE Transfer mode using MPI/PROFIBUS DP The bus parameters are read from the project currently loaded on the HMI device.
Commissioning the device 4.4 Configuring the device Procedure Proceed as follows: 1. Use "Properties" to open the "MPI" or "PROFIBUS" dialog. 2. If there are several masters connected on the bus, deactivate the "Panel is the only master on the bus" check box. 3. Enter the bus address for the HMI device under "Address". NOTICE The bus address in the "Address" text box must be unique throughout the MPI/PROFIBUS DP network. 4. Select the transfer speed under "Transmission Rate". 5.
Commissioning the device 4.4 Configuring the device 4.4.12 Configuring network operation 4.4.12.1 Overview of network operation Introduction You can connect the HMI device to a PROFINET network via the Ethernet port. NOTICE The HMI device only has client functionality in the PC network. This means that users can access files of a node with TCP/IP server functionality from the HMI device via the network. However, you cannot, for example, access files of the HMI device from a PC via the network.
Commissioning the device 4.4 Configuring the device Printing via a network printer The HMI device's operating system does not support line by line alarm logging via a network printer. All other printing functions, for example, hardcopy or logs, are available without restriction via the network. Preparation Before beginning the configuration, request the following network parameters from your network administrator.
Commissioning the device 4.4 Configuring the device Procedure Proceed as follows: 1. Open the "System Properties" dialog with the System icon. 2. Open the "Device Name" tab. 3. Enter the computer name of the HMI device under "Device name". The computer name must be unique within the network. 4. If necessary, enter a description for the HMI device under "Device description". 5. Confirm your entries with "OK". Result The computer name for the HMI device is now set. The network functionality is enabled.
Commissioning the device 4.4 Configuring the device Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the network adapter display with the "Network&Dial-Up Connections" icon. The image below shows the network adapter of a KP1500 Comfort. Comfort devices of 15" or more come with the second network adapter "PN_X3". The interface for the HMI devices KP400 Comfort and KTP400 Comfort is called "FEC". 2. Open the "PN_X1" entry. The "'PN_X1' Settings" dialog box opens. 3.
Commissioning the device 4.4 Configuring the device 5. If you have selected manual address assignment, enter the corresponding addresses under "IP Address", "Subnet Mask" and if necessary under "Default Gateway". NOTICE PROFINET I/O error if the PN_X1 and PN_X3 subnet masks are identical In principle, the two network adapters may be assigned to a shared physical subnetwork.
Commissioning the device 4.4 Configuring the device 8. If you want to set additional Ethernet parameters, open the "Ethernet Parameters" tab. The KP400 Comfort and KTP400 Comfort HMI devices only have one Ethernet port ("Port1"). 9. If needed, select the transmission mode and speed for the Ethernet port of the HMI device. 10.Change the limits for the Ethernet ports "Port 1" and "Port 2" if needed. 11.Confirm your entries with "OK". Result The LAN connection parameters for the HMI device have been changed.
Commissioning the device 4.4 Configuring the device 4.4.12.4 Changing the logon data Use the Windows CE login information to gain access to network resources. You can obtain the login data "User name", "Password" and "Domain" from your administrator. Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the "Network ID" dialog with the Network ID icon. 2. Enter the user name under "User name". 3. Enter your password under "Password". 4. Enter the domain name under "Domain". 5.
Commissioning the device 4.4 Configuring the device 4.4.12.5 Changing e-mail settings Requirement The Control Panel is open. Note Additional tabs may appear in the "WinCC Internet Settings" dialog. This depends on the options that have been enabled for network operation in the project. For more information, please refer to the WinCC or WinCC flexible Online Help. Procedure Proceed as follows: 1. Open the "WinCC Internet Settings" dialog with the icon of the same name. 2. Open the "Email" tab. 3.
Commissioning the device 4.4 Configuring the device 5. Use "Advanced" to open the "Advanced Email Settings" dialog: – Enter the user name of the e-mail account under "Login". – Enter the password for the e-mail account under "Password". 6. Confirm your entries with "OK". Result The e-mail settings have been changed. See also Reference for functions (Page 79) 4.4.12.6 Configuring Telnet for remote control If the Telnet service is enabled, you can remotely control the HMI device via Telnet.
Commissioning the device 4.4 Configuring the device Result The Telnet service is now enabled on the HMI device. You can remotely control the HMI device via Telnet without restrictions. See also Reference for functions (Page 79) 4.4.13 Changing Internet settings 4.4.13.1 Changing general Internet settings Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the "Internet Options" dialog with the Internet Options icon. 2. Open the "General" tab. 3.
Commissioning the device 4.4 Configuring the device 6. If you want to clear the cache: – Open the "Delete Browsing History" dialog with the "Delete Browsing History..." button. – Use "Delete" or "Delete all" to delete all temporary data and the history. – If cookies should be deleted each time you exit your browser, select "Delete cookies on browser exit". 7. Confirm your entries with "OK". Result The general parameters for the Internet browser have been set. See also Reference for functions (Page 79) 4.
Commissioning the device 4.4 Configuring the device 5. If you want to define exceptions for specific addresses: – Open the "Advanced Proxy Settings" dialog with the "Advanced..." button. – Enter the desired addresses. Separate multiple addresses with a semicolon. 6. Confirm your entries with "OK". Result The proxy server is configured. See also Reference for functions (Page 79) 4.4.13.3 Changing privacy settings Cookies and encryption Cookies are pieces of information sent by a web server to a browser.
Commissioning the device 4.4 Configuring the device Procedure Proceed as follows: 1. Open the "Internet Options" dialog with the "Internet Options" icon. 2. Open the "Privacy" tab. 3. Select the behavior for handling cookies. – "Accept" Cookies are stored without request. – "Block" Cookies will not be stored. – "Prompt" Cookies will be stored on request. 4. If you want to allow cookies which are restricted to a single session, select "Always allow session cookies". 5. Open the "Advanced" tab. 6.
Commissioning the device 4.4 Configuring the device 4.4.13.4 Importing and deleting certificates You can import, view and delete certificates that have been imported for the HMI device. The certificates differ in the following ways: ● Certificates that you trust ● Own certificates ● Other certificates You can import additional certificates and delete certificates that are not required. The required settings can be obtained from your network administrator. Requirement The Control Panel is open.
Commissioning the device 4.4 Configuring the device 4. If you want to display information about a certificate: – Select the certificate. – Display the information with the "View" button. 5. If you want to delete a certificate: – Select the certificate. – Delete the certificate with the "Remove" button. The certificate is deleted from the certificate storage area of the HMI device. 6. Confirm your entries with "OK". The dialog closes. Result The changes to the certificates have been performed.
Commissioning the device 4.4 Configuring the device Procedure Proceed as follows: 1. Open the ""Backup/Restore"" dialog with the "Backup/Restore" icon. The available external storage media are shown in the list. 2. Select the desired external storage medium and press "Backup/Restore". 3. Open the "Backup/Restore" dialog in the "Backup" tab. The backup files on the external storage media are shown in the list. 4. Select a blank entry and start the backup process using "Backup".
Commissioning the device 4.4 Configuring the device 4.4.15 Restoring from external storage device Introduction A restore operation deletes the internal memory of the HMI device upon confirmation. The content of the backup file is then copied from the external storage medium into the internal memory of the HMI device. The HMI device is then restarted.
Commissioning the device 4.4 Configuring the device 3. Open the "Restore" tab in the "Backup/Restore" dialog. The backup files on the selected storage medium are shown in the list. 4. Select a backup file and start the restore process using the "Restore" button. The content of the backup file is checked. After a successful test, the alarm is displayed stating that the data from the internal memory have been deleted. 5. Acknowledge this alarm. The internal memory is deleted.
Commissioning the device 4.4 Configuring the device 4.4.16 Activate memory management NOTICE Memory management If you do not activate memory management, undefined states can occur during the runtime of the project. Requirement The Control Panel is open. Procedure Proceed as follows: 1. Open the "OP Properties" dialog with the OP icon. 2. Open the "Memory Monitoring" tab. 3. If you want to enable memory management, select "Shut down HMI Runtime...". 4. Confirm the entry with "OK".
Commissioning the device 4.
Commissioning a project Commissioning a project 5.1 5 Overview Configuration phase A project – the process image of the working process – is produced during configuration to visualize automated working processes. The process displays for the project contain displays for values and alarms which provide information about process statuses. The process control phase follows the configuration phase.
Commissioning a project 5.2 Operating modes 5.2 Operating modes Operating modes The HMI device may be in the following operating modes: ● Offline ● Online ● Transfer Changing the operating mode The configuration engineer must have configured an appropriate operating element to allow a change of the operating mode on the HMI device during ongoing operation.
Commissioning a project 5.4 Data transmission options 5.4 Data transmission options Overview The following table shows the options for data transfer between an HMI device and the configuring PC.
Commissioning a project 5.5 Transfer 5.5 Transfer 5.5.1 Setting transfer mode Introduction You can start the "Transfer" mode manually or automatically on the HMI device. If the automatic transfer is enabled, the HMI device automatically switches to "Transfer" mode when the following event occurs during runtime: You start project transfer on the connected configuring PC. Note With automatic transfer, the HMI device only switches to "Transfer" mode when the project is running on the HMI device.
Commissioning a project 5.5 Transfer Procedure Proceed as follows: 1. Open the "Transfer Settings" dialog with the Transfer Settings icon. 2. Open the "Channel" tab. 3. Select "Enable Transfer". 4. Select the data channel and set its parameters using "Properties...". Exception: The "USB device" data channel has no parameters. 5. To start "Transfer" mode automatically: – Select "Remote Control". – Close the dialog with "OK". 6. To start "Transfer" mode manually: – Disable "Remote Control".
Commissioning a project 5.5 Transfer 5.5.2 Start transfer Introduction To make a project executable on an HMI device, transfer the project from the configuring PC to the HMI device. With a transfer, you particularly specify whether to overwrite existing data on the HMI device such as the "User management" or "Recipe data". Requirement ● The project is opened in WinCC on the configuration PC. ● Project tree is displayed. ● Configuring PC is connected to the HMI device.
Commissioning a project 5.5 Transfer 5.5.3 Testing a project Introduction There are two options to test a project: ● Test the project on the configuring PC You can test a project at a configuring PC, using a simulator. You can find more detailed information on this in the online help of WinCC. ● Offline testing of the project on the HMI device Offline testing means that communication between the HMI device and PLC is down while the test is being carried out.
Commissioning a project 5.6 Backup and restore Requirement for online testing ● The project has been transferred to the HMI device. ● The HMI device is in "Online" mode. Procedure In "Online" mode, you can test individual project functions on the HMI device without them being affected by the PLC. PLC tags are updated in this case. You have the option to test all communication-dependent functions, for example alarms, etc. Test the operating elements and views of the project. 5.6 Backup and restore 5.6.
Commissioning a project 5.6 Backup and restore 5.6.2 Backing up and restoring data of the HMI device Note Only use the restore function for project data on HMI devices that were configured with the same configuration software. Requirement ● The HMI device is connected to the configuring PC. ● The HMI device is selected in the project tree. ● If a server is used for data backup: The configuring PC has access to the server.
Commissioning a project 5.7 Updating the operating system 5.7 Updating the operating system 5.7.1 Updating the operating system Introduction If the operating system version of an HMI device is not compatible with the configuration, you need to update the operating system of the HMI device. Depending on the protocol used, the operating system on the HMI device is updated automatically upon prompting when the project is loaded. Thereafter, the loading continues.
Commissioning a project 5.7 Updating the operating system 5.7.2 Updating the operating system of the HMI device If possible, use the interface with the highest bandwidth, for example, Ethernet, to make the connection. CAUTION Updating the operating system deletes all data on the HMI device If you update the operating system, data on the target system is deleted. Therefore, first back up the following data: User administration Recipes A reset to the factory settings also deletes the license keys.
Commissioning a project 5.7 Updating the operating system The HMI device is reset to the factory settings. To restore the factory settings on the HMI device, follow these steps: 1. Set the HMI device to "bootstrapping" mode. – Open the "OP Properties" dialog on the HMI device in the Control Panel. – Switch to the "Device" tab and select "Reboot". The "Attention" dialog box opens. – Select "Prepare for Reset". The HMI device restarts and switches to "bootstrapping" mode.
Commissioning a project 5.8 Managing add-ons and license keys 5.8 Managing add-ons and license keys 5.8.1 Managing add-ons Introduction You can install the following add-ons on an HMI device: ● Add-ons supplied with WinCC ● Add-ons purchased separately from WinCC The HMI device type determines which add-ons can be installed. For an overview of available add-ons, refer to "Introduction to WinCC". Requirement ● The HMI device is connected to the configuring PC.
Commissioning a project 5.8 Managing add-ons and license keys 5.8.2 Transferring license keys Introduction You need a license key for WinCC Runtime add-ons to use them on an HMI device. The required licenses are usually supplied as license keys on a data medium, for example, a USB stick. You can also obtain the license keys from a license server. Use the "Automation License Manager" to transfer the license keys to or from an HMI device.
Commissioning a project 5.8 Managing add-ons and license keys 5. Configure the corresponding "connection parameters", depending on the selected connection. 6. Click "OK". The connection to the HMI device is established. The connected HMI device is displayed in the left area of the "Automation License Manager". 7. Transfer the license keys to the HMI device: – In the left area, select the drive on which the license keys are located. The license keys are shown in the right area.
Commissioning a project 5.
Operating a project 6.1 6 Overview Operator input options The hardware of the HMI device determines which of the following operator control options are available: ● Touch screen The operating elements shown in the dialogs are touch-sensitive. Touch objects are basically operated in the same way as mechanical keys. You activate operating elements by touching them with your finger. To double-click them, touch an operating element twice in succession.
Operating a project 6.1 Overview Unintentional actions CAUTION Do not carry out several operations simultaneously. You may otherwise trigger unintentional actions. With touch control: Always touch only one operating element on the screen With key control: Do not press more than two function keys simultaneously. Exception: The keyboard shortcut can also be used with the system keys.
Operating a project 6.1 Overview The type of optical feedback depends on the operating element: ● Buttons The HMI device generates different views for the "Pressed" and "Unpressed" states, provided the configuration engineer has configured a 3D effect: – "Pressed" state: – "Unpressed" state: The configuration engineer determines the appearance of a selected field, for example, line width and color for the focus.
Operating a project 6.2 Function keys 6.2 Function keys Function keys Function key assignment is defined during configuration. The configuration engineer can assign function keys globally and locally. Function keys are available only on key HMI devices. Function keys with global function assignment A globally assigned function key always triggers the same action on the HMI device or in the PLC irrespective of the screen displayed.
Operating a project 6.4 Setting the project language Direct keys The following objects can be configured as a direct key: ● Buttons ● Function keys You can also define image numbers in the case of HMI devices with touch operation. In this way, the configuration engineer can configure the direct keys on an image-specific basis. You can find detailed information on configuring direct keys in the online help for WinCC under "Visualizing processes > Communicating with controllers". 6.
Operating a project 6.5 Input of values 6.5 Input of values If you select an I/O field in the project using the tab sequence or by touch, the entire field content is selected. The screen keyboard appears on a touch HMI device. Procedure Proceed as follows: 1. To overwrite the value: – Enter the new value using the system keys or the screen keyboard. 2. To change the value: – Key HMI device: Deselect the content with . – Touch HMI device: Deselect the content with any cursor key.
Operating a project 6.6 Entering and editing numeric values 6.6 Entering and editing numeric values Introduction You enter numeric values depending on a type of HMI device, either with the system keys or the screen keyboard. Alternatively, you can also connect an external keyboard. Note When the screen keyboard is open, PLC job 51, "Select screen" has no function. ● With key HMI devices, only the numbers on the system keys are available. ● With touch HMI devices, a numerical screen keyboard opens.
Operating a project 6.7 Entering or changing alphanumeric values Requirement Cursor is in an I/O field. Procedure Proceed as follows: 1. Enter the desired value using the system keys or the screen keyboard. 2. Discard the entry with , if necessary. 3. Conclude your entry with . Result The numeric value has been changed. If you have discarded the entry, the I/O field remains empty or the original value is displayed.
Operating a project 6.7 Entering or changing alphanumeric values Requirement Cursor is in an I/O field. Procedure Proceed as follows: 1. Enter the desired value using the system keys or the screen keyboard. 2. Discard the entry with , if necessary. 3. Conclude your entry with . Result The alphanumeric value has been entered or changed. If you have discarded the entry, the I/O field remains empty or the original value is displayed.
Operating a project 6.8 Displaying infotext 6.8 Displaying infotext Purpose The configuration engineer uses infotext to provide additional information and operating instructions. The configuration engineer can configure infotext on screens and operating elements. The infotext of an I/O field may contain, for example, information on the value to be entered.
Operating a project 6.9 Closing the project Requirement Operating element with the configured infotext is selected. Procedure Proceed as follows: 1. Press the key. The infotext for the operating element is displayed. 2. Use the cursor keys to scroll as needed. Note Switching between displayed infotext The configuration engineer can configure infotext for an I/O field and the associated screen. You can switch between two infotexts by touching the infotext window. 3.
Operating a project 6.
Maintenance and care 7.1 7 Maintaining and caring for the touch screen and keyboard overlay Introduction The HMI device is designed for maintenance-free operation. The touch screen and keyboard overlay should nevertheless be cleaned regularly. Requirement ● Damp cleaning cloth ● Washing up liquid or foaming screen cleaning agent Procedure NOTICE Unintentional response If you clean the touch screen or an HMI device with a keyboard overlay when it is switched on, you may cause maloperations.
Maintenance and care 7.2 Clean screen for Touch HMI devices 7.2 Clean screen for Touch HMI devices The touch screen of the HMI device can be cleaned when it is switched on and a project is running. An operating element must be available in the project that can be used to call the "clean" screen. Once the clean screen is activated, touch screen operation is locked for a configured period of time. The time the touch screen is locked can be set between 5 and 30 seconds.
Maintenance and care 7.3 Spare parts and repairs 7.3 Spare parts and repairs Repairs In case of repair, the HMI device must be shipped to the Return Center in Fürth. Repairs may only be carried out at the Return Center in Fürth. Depending on the work necessary to repair the device, the Center may decide to give you a credit note. A credit note is only granted when the sender orders a new HMI device. The address is: Siemens AG Industry Sector Returns Center Siemensstr.
Maintenance and care 7.
Technical specifications 8.1 8 Certificates and approvals Approvals CAUTION The following overview shows possible approvals. The HMI device itself is certified as shown on the rear panel labels.
Technical Support UL approval Underwriters Laboratories Inc., to ● UL 508 (Industrial Control Equipment) ● CSA C22.2 No. 142 (Process Control Equipment) or Underwriters Laboratories Inc., to ● UL 508 (Industrial Control Equipment) ● CSA C22.2 No.
Technical Support Ex approval The following approvals apply to the HMI device in accordance with ● EN 60079-0:2009 ● EN 60079-15:2005 ● EN 60079-31:2009 valid: II 3 G Ex nA IIC Tx Gc II 3 D Ex tc IIIC T 70 °C Dc IP65 x: Temperature values, see EC design examination certificate The EC type examination certificates are available on the Internet at: Technical Support (http://www.siemens.
Technical Support 8.2 Directives and declarations 8.2.1 Electromagnetic compatibility Introduction The HMI device fulfills, among other things, the requirements of the EMC law pertaining to the domestic European market. EMC-compatible installation of the HMI device The EMC-compliant installation of the HMI device and the application of interference-proof cable is the basis for interference-free operation.
Technical Support Sinusoidal interference The following table shows the EMC behavior of the modules with respect to sinusoidal interference. This requires the HMI device to meet the specifications and directives for electrical installation.
Technical Support 8.2.2 ESD guideline What does ESD mean? An electronic module is equipped with highly integrated components. Due to their design, electronic components are highly sensitive to overvoltage and thus to the discharge of static electricity. Such electronic components or modules are labeled as electrostatic sensitive devices.
Technical Support Charge Every person without a conductive connection to the electrical potential of his/her surroundings can be electrostatically charged. 9ROWDJH The material with which this person comes into contact is of particular significance. The figure shows the maximum electrostatic voltages with which a person is charged, depending on humidity and material. These values conform to the specifications of IEC 61000-4-2.
Technical Support Protective measures against discharge of static electricity ● Disconnect the power supply before you install or remove modules which are sensitive to ESD. ● Pay attention to good grounding: – When handling electrostatical sensitive devices, make sure that persons, the workstation and devices, tools and packaging used are properly grounded. In this manner, you avoid static discharge.
Technical Support Dimension drawings 8.3.1 Dimension drawings of the FKP400 Comfort 8.
Technical Support Dimension drawings of the KP700 Comfort 8.3.
Technical Support Dimension drawings of the KP900 Comfort 8.3.
Technical Support Dimension drawings of the KP1200 Comfort 8.3.
Technical Support 8.3.
Technical Support Dimension drawings of the KTP400 Comfort 8.3.
Technical Support Dimension drawings of the TP700 Comfort 8.3.
Technical Support Dimension drawings of the TP900 Comfort 8.3.
Technical Support Dimension drawings of the TP1200 Comfort 8.3.
Technical Support 8.3.
Technical Support 8.3.
Technical Support 8.3.
Technical Support 8.3.13 Dimensions for labeling strips This section contains the labeling strip dimensions for the Comfort Panels key models. You will find labeling strip templates with a scale of 1:1 as a Word file: ● On the Internet at: Downloads for Comfort Panels (http://support.automation.siemens.
Technical Support Labeling strips for KP1200 Comfort 5 5 5 5 Labeling strips for KP1500 Comfort 5 /DEHOLQJ VWULSV DQG IRU NH\V ) ) ) DQG ) ) ) 5 5 /DEHOLQJ VWULS IRU NH\V ) ) 5 5 /DEHOLQJ VWULS IRU NH\V ) ) 5 5 /DEHOLQJ VWULS IRU NH\V ) ) 5 5 /DEHOLQJ VWULS IRU NH\V ) ) 5 Comfort Panels 190 Operating Instructions, 03
Technical Support 8.4 Technical specifications 8.4.1 KP400 Comfort to KP1200 Comfort, KTP400 Comfort to TP1200 Comfort Weight HMI devices KP400 C omfort Weight without packaging KTP400 Comfort KP700 Comfort TP700 Comfort KP900 Comfort TP900 Comfort KP1200 Comfort TP1200 Comfort 0.6 kg 2.2 kg 1.4 kg 2.7 kg 1.9 kg 4.4 kg 2.8 kg TP900 Comfort KP1200 Comfort TP1200 Comfort 0.
Technical Support Memory HMI devices KP400 C omfort Usable memory for application data Usable memory for recipe data 1 Additional memory for options KTP400 Comfort KP700 Comfort KP900 Comfort TP900 Comfort 4 MB 12 MB 512 KB 2 MB 4 MB 12 MB Memory card 1 TP700 Comfort KP1200 Comfort TP1200 Comfort KP1200 Comfort TP1200 Comfort KP1200 Comfort TP1200 Comfort 2 x MMC/SD combination slot Can be extended via memory card Interfaces HMI devices KP400 C omfort KTP400 Comfort 1 x RS 422/485 (P
Technical Support Miscellaneous HMI devices KP400 C omfort KTP400 Comfort KP700 Comfort TP700 Comfort Buffered real-time clock 1 Audio reproduction TP900 Comfort KP1200 Comfort TP1200 Comfort Yes Onboard beeper Integrated or external via Line OUT Magnetic field intensity 1 KP900 Comfort 50/60 Hz; 100 A/m RMS Battery backup typically 6 weeks 8.4.2 KP1500 Comfort, TP1500 Comfort to TP2200 Comfort Weight HMI devices KP1500 Comfort Weight without packaging TP1500 Comfort 5.
Technical Support Input device HMI devices KP1500 Comfort TP1500 Comfort TP1900 Comfort Keyboard (numeric/alpha entry) Yes No Touch screen (analog resistive) No Yes Function keys 36 No Labeling strips Yes No TP2200 Comfort Memory HMI devices KP1500 Comfort TP1500 Comfort 24 MB Usable memory for recipe data 1 4 MB Additional memory for options TP2200 Comfort 24 MB Memory card 1 TP1900 Comfort Usable memory for application data 2 x MMC/SD combination slot Can be extended via memor
Technical Support Power supply HMI devices KP1500 Comfort TP1500 Comfort Rated voltage TP1900 Comfort TP2200 Comfort 24 V DC Permissible voltage range +19.2 V to +28.8 V Rated current 1.5 A Inrush current I2t 1.3 A 2.2 A 32 W 53 W 0.
Technical Support 8.4.3 Ambient conditions 8.4.3.1 Transport and storage conditions Mechanical and climatic conditions for transportation and storage This HMI device meets the requirements for IEC 61131-2 relating to transport and storage conditions. The following specifications apply to the transport and storage of an HMI device in its original packaging.
Technical Support 8.4.3.2 Operating conditions Mechanical and climatic conditions of use The HMI device is designed for use in a location protected from the effects of the weather.
Technical Support Testing mechanical ambient conditions The following table provides information on the type and scope of tests for mechanical ambient conditions. Tested for Test standard Comments Vibrations Vibration test in accordance with IEC 60068, part 2–6 (sinusoidal) Type of vibration: Frequency cycles at a rate of change of 1 octave/minute. 5 Hz ≤ f ≤ 8.4 Hz, constant amplitude 0.075 mm 1 8.
Technical Support 8.4.3.3 Information on insulation tests, protection class and degree of protection Test voltages Insulation strength is demonstrated in the type test with the following test voltages in accordance with IEC 61131-2: Circuits with a nominal voltage of Ue to other circuits or ground 24 V Test voltage 520 V DC or 370 V AC For Ethernet connector: 1500 V AC Protection class Protection Class I in accordance with IEC 61140, i.e.
Technical Support 8.5 Bit assignment of the direct keys The following figures show the assignment of the keys and LEDs to the bytes in the PLC process image. Further information may be available in your plant documentation. 8.5.
Technical Support 8.5.2 KP400 Comfort Inputs Outputs 1 byte 1 byte /(' .H\V 'LUHFW NH\ DVVLJQPHQW 8.5.3 ) ) ) %\WH ) ) ) ) ) Q ) ) ) ) ) ) ) ) KP700 Comfort Inputs Outputs 3 bytes 3 bytes /(' .H\V 'LUHFW NH\ DVVLJQPHQW 8.5.
Technical Support 8.5.5 KP900 Comfort Inputs Outputs 4 bytes 4 bytes /(' .H\V 'LUHFW NH\ DVVLJQPHQW 8.5.
Technical Support 8.5.7 KP1200 Comfort Inputs Outputs 5 bytes 5 bytes /(' .H\V 'LUHFW NH\ DVVLJQPHQW 8.5.
Technical Support 8.5.9 KP1500 Comfort Inputs Outputs 5 bytes 5 bytes /(' .H\V 'LUHFW NH\ DVVLJQPHQW 8.5.
Technical Support 8.6 Description of the ports 8.6.1 Power supply Plug connector, 2-pin Pin number 8.6.2 Assignment 1 +24 VDC (L+) 2 GND 24 V (M) PROFIBUS (Sub-D RS422/485) Name of interface on HMI device: X2 Sub-D socket, 9-pin, with screw lock Pin Assignment for the RS 422 Assignment for the RS 485 1 n. c. n. c.
Technical Support 8.6.3 PROFINET (LAN) 10/100 Mb Name of interface on HMI device: X1 RJ45 plug connector 8.6.4 Pin Assignment 1 Tx+ 2 Tx– 3 Rx+ 4 n. c. 5 n. c. 6 Rx– 7 n. c. 8 n. c. PROFINET (LAN) 10/100/1000 Mb Models of 15" and more have this interface.
Technical Support 8.6.5 USB USB socket type A Name of interface on HMI device: X61/X62 Pin Assignment 1 +5 VDC, out (max. 500 mA) 2 USB-DN 3 USB-DP 4 GND USB socket type mini B Name of interface on HMI device: X60 8.6.
Technical Support 8.7 Communication with PLCs Number of connections Connection KP400 Comfort KP700 Comfort to KP1500 Comfort KTP400 Comfort TP700 Comfort to TP2200 Comfort Number using a bus connection 4 8 Number of connections based on "SIMATIC HMI HTTP Protocol" 4 8 NOTICE Communication faults with PROFINET IO If you enable PROFINET services in the Control Panel of the HMI device, communication problems can occur if you use PLCs from other manufacturers.
Technical Support 8.8 Scope of functions with WinCC The following tables show the objects which can be integrated in a project for an HMI device. Note The specified values are maximum values of the individual objects. Simultaneous use of multiple objects with their maximum value can lead to problems in the active project.
Technical Support Tags, values and lists Object Specification HMI devices KTP400 Comfort KP700 Comfort to KP1200 Comfort TP700 Comfort to TP1200 Comfort KP1500 Comfort, TP1500 Comfort to TP2200 Comfort 1024 2048 4096 KP400 Comfort 1 Tags Number Limit value monitoring Input/output Yes Linear scaling Input/output Yes Text lists Number 300 500 1 Graphics lists Number 100 500 1 The maximum total of text and graphics lists is 500.
Technical Support Logs Note The HMI devices are suitable for the logging of relatively small volumes of data. Manage the data in several adjacent archives in a segmented circular log. The use of a large circular log has a negative effect on performance.
Technical Support Safety Object Specification HMI devices KP400 Comfort KTP400 Comfort User view KP1500 Comfort, TP1500 Comfort to TP2200 Comfort KP700 Comfort to KP1200 Comfort TP700 Comfort to TP1200 Comfort Number of user groups 50 Number of users 50 Number of authorizations/ user permissions 32 Infotexts Object Specification HMI devices KP400 Comfort Infotexts Length (no.
Technical Support Technical Support A.1 A Service and support You can find additional information and support for the products described on the Internet at the following addresses: ● Technical support (http://www.siemens.de/automation/csi_en_WW) ● Support request form (http://www.siemens.com/automation/support-request) ● After-sales information system for SIMATIC PC / PG (http://www.siemens.com/asis) ● SIMATIC Documentation Collection (http://www.siemens.
Technical Support A.2 Troubleshooting A.2 Troubleshooting This section contains information on localizing and rectifying possible faults. Error message Possible cause Remedy "System card is missing or defective" No system memory card inserted. Insert a system memory card. Use only the SIMATIC HMI Memory Card ≥ 2 GB. System memory card is defective. Replace the defective system memory card with a new SIMATIC HMI Memory Card.
B Abbreviations ANSI American National Standards Institution CPU Central Processing Unit CSV Comma Separated Values CTS Clear To Send DC Direct Current DCD Data Carrier Detect DHCP Dynamic Host Configuration Protocol DIL Dual-in-Line (electronic chip housing design) DNS Domain Name System DP Distributed I/O DSN Data Source Name DSR Data Set Ready DTR Data Terminal Ready IO Input and Output ESD Components and modules endangered by electrostatic discharge EMC Electromagnetic Co
Abbreviations RAM Random Access Memory PELV Protective Extra Low Voltage RJ45 Registered Jack Type 45 RTS Request to send RxD Receive Data SD Memory Card Abbreviation of Secure Digital Memory Card SELV Safety Extra Low Voltage SP Service Pack PLC Programmable Logic Controller Sub-D Subminiature D (plug) TAB Tabulator TCP/IP Transmission Control Protocol/Internet Protocol TFT Thin Film Transistor TxD Transmit Data UL Underwriter’s Laboratory USB Universal Serial Bus UPS Uninte
Glossary "Transfer" mode The "Transfer" operating mode is an operating mode of the HMI device in which an executable project is transferred from the configuring PC to an HMI device. Acknowledge Acknowledgment of an alarm confirms that it has been noted. Alarm logging Output of user-specific alarms to a printer, in parallel to their output to the HMI device screen. Alarm, acknowledgment Acknowledgment of an alarm confirms that it has been noted.
Glossary Configuration software Configuration software is used to create projects used for the purpose of process visualization. WinCC represents such configuration software, for example. Configuring PC A configuring PC is a programming device or PC on which plant projects are created using an engineering software.
Glossary Function key Function keys on the HMI device can be assigned user-specific functions. The functions assigned to these keys are defined during configuration. The assignment of the function keys may be specific to an active screen or independent of it. Half Brightness Life Time Time period after which brightness is reduced to 50% of the original value. The specified value depends on the operating temperature. Hardcopy Output of the screen content to a printer.
Glossary Plant General term referring to machines, processing centers, systems, plants and processes which are operated and monitored on an HMI device. PLC PLC is a general term for devices and systems with which the HMI device communicates, for example SIMATIC S7. PLC job A PLC job triggers a function for the PLC on the HMI device. Process visualization Process visualization is the representation of technical processes by means of text and graphic elements.
Glossary Project file, executable An executable project file is the file generated from the project file for a specific HMI device. The executable project file is transferred to the associated HMI device where it is used to operate and monitor plants. An executable project file has the extension "*.fwc". Protection class The protection class is used in electrical engineering to classify and identify electrical equipment in relation to existing safety measures designed to prevent electric shock.
Glossary Tag A tag is a defined memory location to which values can be written and from which values can be read. This can be done from the PLC or the HMI device. We distinguish between external tags (process tags) and internal tags, depending on whether or not the tag is interconnected with the PLC. Transfer Transfer of a runtime project from the configuring PC to the HMI device.
Index A ACK key, 73 Acknowledge key, 73 Acoustic feedback, 155 Acoustic signal For inadvertent operation, 155 with inadvertent operation, 80 Acoustics Feedback, 97, 98 Add-on Installing, 139, 149 Removing, 139, 149 Add-ons, 23 Address assignment TCP/IP network, 119 Addressing, 117 Alarm Functional scope, 209 Alarm buffer Functional scope, 209 ALARM_S, 209 Alphanumeric values Entering, 161 ALT key, 70 Ambient conditions Climatic, 198 Mechanical, 197 Test, 198 Approval for Australia, 171 Approvals, 169 Assig
Index Character repeat, 79 Screen keyboard, 82 Clean screen, 166 Cleaning product, 165 Clearance HMI device, 32 Climatic Storage conditions, 196 Transport conditions, 196 Closing Project, 163 Color depth Changing, 92 Setting, 79 Compatibility conflict, 144 Components sensitive to electrostatic charge, 174 Computer name For network operation, 118 Setting, 80 Conductor cross-section, 44 Equipotential bonding, 42 Configuration phase, 137 Configuring Network, 118 Operating system, 65 Remote operation via Sm@rt
Index DNS, 121 Server, Documentation Enclosed, 29 Double-click, 79 Setting, 83 Drop-down list box Opening, 72 E EC Declaration of Conformity, 169 Elbow adapter, 21 Electrical isolation Safe, 44 Electrical potential difference, 42 Electromagnetic compatibility, 172 E-Mail Setting, 80, 124 EMC, 172 Emission, 27, 173 Enable SecureMode, 86 Service concept, 62 Encryption, 128 END key, 70 Enter key, 70 ENTER key, 70 Entering Alphanumeric values, 161 Hexadecimal values in the project, 159 Numeric values in the p
Index H Hexadecimal values Entering in the project, 159 HMI device Backing up data, 145 Clearance, 32 EMC-compatible installation, 172 Mounting, 39 Operating with system keys, 69 Operator control, 60 Resetting to factory settings, 148 Restart, 99 Restarting, 79 Restoring data, 145 Shutting down, 53 Switching on, 52 Technical specifications, 191, 193 Testing, 52 Transfer license key, 150 Updating the operating system (Windows CE), 147 HMI devices Display, 191, 193 Input device, 191, 194 Interfaces, 192, 194
Index L Labeling Approvals, 170 EC Declaration of Conformity, 169 Function key, 34 Guidelines for Explosion Protection, 171 Labeling strips Attaching, 35 Dimensions, 189 Printing, 34 LAN connection, 79 Language change Functional scope, 212 License Managing, 150 License key Transfer to an HMI device, 150 Transferring, 139 Transferring back, 139 License keys, 150 Limit test, 159 Limit value monitoring Functional scope, 210 List of abbreviations, 215 Loader, 65 Opening, 65 Log Format, 211 Functional scope, 21
Index OP properties, 79 Device, 101 Memory monitoring, 135 Persistent storage, 90 Touch, 84 Opening Control Panel, 67 Drop-down list box, 72 Loader, 65 Operating Control Panel with system keys, 72 Dialog with system keys, 72 Explorer with system keys, 71 Feedback, 154 HMI device with system keys, 69 Project with system keys, 73 Windows CE with system keys, 71 With external keyboard, 153 With external mouse, 153 Operating instructions Purpose, 3 Scope, 3 Operating mode, 138 Changing, 138 Offline, 138 Online
Index Protocol PLC, 208 Proxy Server, 79, 124, 127 Setting, 79 Restoring data HMI device, 145 Returns Center, 167 Reverse polarity protection, 45 RS 422 to RS 232 converter, 21 R S Radiation, 26 High frequency radiation, 26 Radio interference, 27 Emission, 173 Rated load Interface, 49 Real-time clock Internal, 87 Rear view 4" model, Devices with 7" and larger displays, Recipe Functional scope, 210 Recommissioning, 137 Recycling, 167 Reducing Backlighting, 94 Regional and language settings, 80, 89 Regio
Index Screen orientation Changing, 92 Setting, 79 Screen saver, 80, 94 Setting, 94 Scroll back key, 70 Scroll forward key, 70 Search engine Internet, 126 SecureMode Enable, 86 Removing, 87 Switching on again, 87 Security information, 26 Security settings, 79 Service concept Disabling, 64 Enable, 62 Replacing HMI device, 63 Service pack, 167 Service packages, 21 Set up Network, 117 Password protection, 86 Time server, 111 Setting Backlighting, 80 Brightness, 79 Browser, 79 Color depth, 79 Computer name, 80
Index Settings Internet, 80 Language, 80 Regional, 80 S7-Transfer, 80 Shift key, 70 SHIFT key, 70 Shutting down HMI device, 53 Side view 4" model, Devices with 7" and larger displays, Siemens HMI input panel options, 79 Sm@rtServer, 23 Configuring, 80, 125 SMTP server, 124 Software add-ons, 23 Sound Assigning to an event, 80 Setting, 80, 98 Setting event, 98 Spare part Plastic clamp, 21 Power supply terminal, 21 Standards, 169 Start HMI device, 79, 99 Transfer, 142 Static electricity Protective measures, 1
Index Transfer, 137, 138, 140 Cancel, 52 Start, 142 Starting automatically, 140 Starting manually, 140 Transfer mode Setting, 141 Unintentional, 113 Via MPI, 115 Via PROFIBUS DP, 115 Transfer settings, 80, 113 Channel, 113 Directories, 104, 105 Transferring License key, 139 License key on HMI device, 150 Project, 137, 139 Transferring back License key, 139 Transport conditions, 196 Transport damage, 29 Trends Functional scope, 212 U UL approval, 170 Unintentional action, 60, 61, 154 Unintentional transfer