Specifications

Generating set start-up
Screen no. Screen Data displayed
G 6
START-UP
IN PROGRESS
24/08/2005 13:12
Operating phase - generating set in starting phase
Date and time (depending on settings)
G 7
AIR PREHEATING
10 seconds
24/08/2005 13:12
Operating phase - air preheating prior to starting generating
set
Countdown for air preheating delay
Date and time (depending on settings)
Generating set started
Screen no. Screen Data displayed
G 8
Default
screen
AVAILABLE POWER
75%
24/08/2005 13:12
Operating phase – generating set in operation – stable
voltage and frequency
Available power
Date and time (depending on settings)
G 9
AUTOMATIC STOP
IN PROGRESS
LOAD SUPPRESSION
1 min 30 sec
24/08/2005 13:12
Operating mode - operation in Auto Mode
Opening of power supply device (motorised circuit breaker
or source changeover switch controlled by TELYS)
Countdown for the mains return delay OR the load test
delay
Date and time (depending on settings)
G 10
AUTOMATIC STOP
IN PROGRESS
COOLING DOWN
1 min 30 sec
24/08/2005 13:14
Operating mode - operation in Auto Mode
Generation set cooling in progress
Countdown for Engine Stop delay (cooling) OR Gradual
Stop delay (Coolant temperature) OR Overload Gradual
Stop delay OR OFF load test delay
Date and time (depending on settings)
53/209