Specifications

List of faults which will cause the generating set to stop and generate a fault code
Low coolant level fault: indicates that the level of coolant is low
in the radiator (linked to a two second time delay).
Or
Overload or short-circuit fault (optional): with the circuit breaker
SD contact closing (overload or short-circuit), the generating
set switches off immediately also causing the main circuit
breaker to be triggered.
Associated message
Additional fault linked to message opposite: is displayed in the
following two cases:
Differential fault (1)
insulation fault (2)
(1) Differential fault (optional): with a differential fault causing
the activation of the differential relay, the generating set
stops immediately also causing the main circuit breaker to
be tripped.
(2) Insulation fault (optional): with an insulation fault causing
the activation of the control unit performing insulation, the
generating set stops immediately.
Associated message
Underspeed fault: indicates an incorrect rotation speed (below
1000 rpm).
Associated message
Emergency stop or external emergency stop fault
Associated message
"STOP" fault activated if the "STOP" button is pressed whilst
the "AUT" LED is flashing to indicate that the generating set is
operating in automatic mode.
Associated message