Specifications

Fuel
Fuel type Diesel
Standard fuel tank 340 L
High autonomy fuel tank 868 L
Lubrication
Oil capacity with filter 34 L
Min. Oil pressure 2 bar
Nominal oil pressure 4 bar
Oil consumption (100 % load) 0,09 L/h
Oil sump capacity 31 L
Type of lubricant Genlub
Cooling
Engine capacity with radiator 35,8 L
Max coolant temperature 105°C
Fan power 3,4 kW
Refrigerant type Gencool
Thermostat 87-102°C
Alternator data
Compliant with NEMA MG21 standards, UTE NF C51.111,
VDE 0530, BS 4999, IEC 34.1, CSA
The alternator is protected against short circuits
Vacuum impregnation, epoxy winding, IP23 protection
rating
Type LEROY SOMER LSA462M5
Number of phases 3
Power factor (cos Phi) 0.8
Number of poles 4
Excitation type AREP
Voltage regulator R450
Short-circuit current 3 IN
Number of bearings 1
Coupling Direct
Control unit(s)
NEXYS
Standard specifications
:
Frequency meter, Voltmeter, Ammeter
Alarms and faults
:
Oil pressure, Coolant temperature, Fail to start, Overspeed,
Alternator min/max, Fuel level low, Emergency shutdown
Engine parameters
:
Working hours counter, Engine speed, Battery voltage,
Fuel Level, Air Preheating
TELYS
Standard specifications:
Voltmeter, Ammeter, Frequency meter
Alarms and faults:
Oil pressure, Water temperature, Start failure, Overspeed,
Alternator min/max, Battery voltage min/max, Emergency
stop
Engine parameters:
Timer, Oil pressure, Water temperature, Fuel level, Engine
speed, Battery voltage
18/209