Specifications

Fuel
Fuel type Diesel
Standard fuel tank 340 L
High autonomy fuel tank 868 L
Lubrication
Oil capacity with filter 34 L
Min. Oil pressure 2 bar
Nominal oil pressure 4 bar
Oil consumption (100 % load) 0,09 L/h
Oil sump capacity 31 L
Type of lubricant Genlub
Cooling
Engine capacity with radiator 35,8 L
Max coolant temperature 105°C
Fan power 3,4 kW
Refrigerant type Gencool
Thermostat 87-102°C
Alternator data
● Compliant with NEMA MG21 standards, UTE NF C51.111,
VDE 0530, BS 4999, IEC 34.1, CSA
● The alternator is protected against short circuits
● Vacuum impregnation, epoxy winding, IP23 protection
rating
Type LEROY SOMER LSA462M5
Number of phases 3
Power factor (cos Phi) 0.8
Number of poles 4
Excitation type AREP
Voltage regulator R450
Short-circuit current 3 IN
Number of bearings 1
Coupling Direct
Control unit(s)
NEXYS
Standard specifications
:
Frequency meter, Voltmeter, Ammeter
Alarms and faults
:
Oil pressure, Coolant temperature, Fail to start, Overspeed,
Alternator min/max, Fuel level low, Emergency shutdown
Engine parameters
:
Working hours counter, Engine speed, Battery voltage,
Fuel Level, Air Preheating
TELYS
Standard specifications:
Voltmeter, Ammeter, Frequency meter
Alarms and faults:
Oil pressure, Water temperature, Start failure, Overspeed,
Alternator min/max, Battery voltage min/max, Emergency
stop
Engine parameters:
Timer, Oil pressure, Water temperature, Fuel level, Engine
speed, Battery voltage
18/209