Installation Manual

23
2 PER Periods DAY and SLEEP are available
4 Per Periods WAKE, DAY, EVE, and SLEEP are available.
Default is 4.
SW26 Minimum Cooling Setpoint
This selection allows the installer to configure the minimum cooling setpoint that the user is
allowed to set. The range is based on the value of the adjustable deadband SW11, such that the
minimum of the range is 50F/10C plus the adjustable deadband and the maximum is
90F/32C.
Default is 52F/11C (based on the adjustable deadband default = 2).
SW27 Maximum Heating Setpoint
This selection allows the installer to configure the maximum heating setpoint. The range is based
on the adjustable deadband value SW11, such that the minimum of the range is 50F/10C and
the maximum is 90F/32C minus the deadband.
Default is 88F/31C (based on the adjustable deadband default = 2).
SW28 UV Light Reminder
This selection allows the installer to select the number of months after which the UV Light
reminder will be displayed to indicate to the homeowner that it is time to call the dealer to have
the UV Lights replaced. Selections available are OFF, 6, 12, 18, 24, 30, 36, 42, 48.
OFF The UV Light reminder is turned off and will never be displayed.
6 - 48 The number of months after which the UV Light reminder will be displayed.
Default is OFF
SW29 Humidifier Pad Reminder
This selects the number of months after which the Humidifier Pad Reminder will be displayed.
This is not based on run time.
OFF The Humidifier Pad Reminder is disabled and will never be displayed.
1-24 The number of months after which the Humidifier Pad Reminder icon will be displayed.
Default is OFF
SW30 Programmable Fan
This selection allows the homeowner to program the fan selection to “Auto” or “On” fan
operation for each of the program schedule periods. This selection is only available on
programmable Thermostat