Installation Manual

20
Default is 2.
SW12 Smart Recovery
Smart Recovery OFF means setpoints change precisely at setback recovery time. 30, 60, or 90
selects the number of minutes recovery starts before programmed recovery time. Recovery takes
place smoothly during the selected recovery time, ending at the recovery time and temperature
which is programmed. Not available when thermostat is configured as non--programmable.
Default is 90
SW13 Room Air Temperature Offset Adjust
The number of degrees to be added to the displayed temperature to calibrate or deliberately
miscalibrate the measured room temperature (-5 to +5F).
Default is 0
SW14 Humidity Display Offset Adjust
The percentage to be added to the displayed humidity to calibrate or deliberately miscalibrate the
measured room humidity (-9% to +9% RH).
Default is 0
SW15 Enable Auto Mode
This selection is not available if the Thermostat is configured as Heat Only or Cool Only in
SW1. This allows the homeowner to select auto changeover mode in addition to heat and cool.
This allows the Thermostat to automatically change between heating mode and cooling mode
when sufficient demand for heating or cooling exists.
ON Auto mode is available.
OFF Auto mode is not available.
Default is ON
SW16 Maximum Cycles Per Hour
This selection limits the number of cycles per hour that the Thermostat allows the system to
operate. Selections are 2, 4, 6.
2 The heating and cooling outputs will be energized no more than 2 times per hour. When an
output is energized, it will not be energized again for 30 minutes.
4 The heating and cooling outputs will be energized no more than 4 times per hour. When an
output is energized, it will not be energized again for 15 minutes.
6 The heating and cooling outputs will be energized no more than 6 times per hour. When an
output is energized, it will not be energized again for 10 minutes.