Specifications
VersaPro Temperature Controller Page 77
Copyright © 2013, United Process Controls Inc. All rights to copy, reproduce and transmit are reserved
BLOCK 2
HEX DEC PARAMETER DESCRIPTION READ/WRITE
RANGE = 0 to 999
DEFAULT = 30
Burnoff function available for Redox, Carbon, and
Dewpoint.
34 52 VSTD VERIFY TEST GAS STANDARD
For oxygen process this is the test standard value
used to verify the probe.
RANGE = 0 to 999
Where the value 999 = 99.9% oxygen
DEFAULT = 30 (3.0%)
For TruCarb this is the FTCS calibration value.
This is the temperature correction factor in
milliohms to compensate the wire resistance
during decarb for the temperature measured
during the decarb process.
READ ONLY
35 53 VTOL VERIFY TEST TOLERANCE SETTING
This setting establishes the limit as VSTD VTOL
when comparing to the measured value VGAS
Range = 0 to 999
Where 0005 = 00.5%
DEFAULT = 0005
Verify function available for Oxygen.
READ ONLY
36 54 TAVE VERIFICATION SAMPLE AVERAGING SETTING
(SECONDS)
RANGE = 0 to 999
DEFAULT = 2
Verify function available for Oxygen.
READ ONLY
37 55 TDEL1 VERIFY DELAY 1 SETTING (SECONDS)
RANGE = 0 to 999
DEFAULT = 30
Verify function available for Oxygen.
READ ONLY
38 56 TDEL2 VERIFY DELAY 2 SETTING (SECONDS)
RANGE = 0 to 999
DEFAULT = 30
Verify function available for Oxygen.
READ ONLY
39 57 TMIN MINIMUM TEMPERATURE FOR PROBE CARE
TEST
This setting establishes the lowest process
temperature allowed for a probe test or TruCarb
decarburization process to proceed.
RANGE = 500°F to 2000°F (260°C to 1090°C)
DEFAULT = 1400°F (760°C)
NOTE: This value must be checked in the SETUP
menu when the temperature scales have been
changed.
READ ONLY
3A 58 TC_ZERO TC ZERO CALIBRATION NUMBER READ/WRITE
3B 59 TC_SPAN TC SPAN CALIBRATION NUMBER READ/WRITE
3C 60 MV_ZERO MV ZERO CALIBRATION NUMBER READ/WRITE
3D 61 MV_SPAN MV SPAN CALIBRATION NUMBER READ/WRITE
3E 62 DAC_OFFSET_1 DAC 1 OFFSET CALIBRATION READ ONLY