Specifications
VersaPro Temperature Controller Page 76
Copyright © 2013, United Process Controls Inc. All rights to copy, reproduce and transmit are reserved
BLOCK 1
HEX DEC PARAMETER DESCRIPTION READ/WRITE
available for TruCarb.
2A 42 PBOMV LAST MILLIVOLTS DURING PROBE BURN OFF
RANGE = -99 TO 2048
i.e. 1018 = 1018 mV
Available for Redox, Carbon, Dewpoint, and
TruCarb.
READ ONLY
2B 43 PBOTC LAST TEMPERATURE DURING PROBE
BURNOFF RANGE = 0 to 3000
i.e. 1715 = 1715° (F or C based on CONFIG0 BIT
6)
Available for Redox, Carbon, Dewpoint, and
TruCarb.
READ ONLY
2C 44 PBORT LAST PROBE BURNOFF RECOVERY TIME
RANGE = 0 – 255 SECONDS
Available for Redox, Carbon, and Dewpoint.
READ ONLY
2D 45 PREMT REMAINING TIME TO NEXT PROBE TEST
RANGE = 0 – 999
Where 999 = 99.9 hours
READ ONLY
2E 46 VGAS For Oxygen Controller: Measured Verification gas.
Value = Actual measured oxygen (0.1%)
READ ONLY
2F 47 PMC PROBE MAINTENANCE CONTROL WORD
BITS 0 – 1
00 = START FULL MAINTENANCE
01 = START BURNOFF (VERIFY) ONLY
10 = START PROBE IMP ONLY
11 = NONE
BITS 2 – 6 UNDEFINED
BIT 7 = NORMAL (0), CANCEL (1)
BITS 8 – 15 = PROBE MAINTENANCE
SEQUENCE NUMBER
READ ONLY
BLOCK 2
HEX DEC PARAMETER DESCRIPTION READ/WRITE
30 48 PTINT PROBE TEST INTERVAL SETTING (HRS)
Operator input for interval setting
RANGE = 0 – 999
Where 999 = 99.9 hours
DEFAULT = 0 (Disable Probe test)
READ ONLY
31 49 PTRECT PROBE TEST RECOVERY TIME SETTING
(SECONDS)
RANGE = 0 to 999
DEFAULT = 30
READ ONLY
32 50 BOTM BURN OFF TIME SETTING (SECONDS)
RANGE = 0 to 999
DEFAULT = 30
Burnoff function available for Redox, Carbon, and
Dewpoint.
READ ONLY
33 51 BOREC BURN OFF RECOVERY TIME SETTING
(SECONDS)
READ ONLY