Specifications
VersaPro Temperature Controller Page 74
Copyright © 2013, United Process Controls Inc. All rights to copy, reproduce and transmit are reserved
BLOCK 1
HEX DEC PARAMETER DESCRIPTION READ/WRITE
Analog Output of 20 mA. The source value is
based on the selection in ASRC upper byte where
1D 29 TEMPFIL Temperature Input Filter in seconds
Range = 0 to 3276. The higher the number the
faster the reading update.
DEFAULT = 1000
READ ONLY
1E 30 MVFIL Millivolt Input Filter in seconds
Range = 0 to 3276. The higher the number the
faster the reading update.
DEFAULT = 1000
READ ONLY
1F 31 CONFIG2 SETUP VALUES
BITS 0 - 4 OXYGEN EXPONENT
RANGE = 0 to 31, where 2 = % and 6 = ppm
DEFAULT = 2
BITS 5 - 6 DISPLAY DECIMAL PLACE where:
0 = no decimal point in display
1 = Display XXX.X
2 = Display XX.XX
3 = Display X.XXX
DEFAULT = 0
BITS 8 – 12 REDOX METAL NUMBER
RANGE = 0 – 14
DEFAULT = 0
BITS 13 – 15 SPARE
READ ONLY
20 32 COLDJCT COLD JUNCTION
Where 1 COUNT = 1°F (°C), RANGE = -99 TO
255°F (°C). Note this parameter is an unsigned
integer.
READ ONLY
21 33 TEMP MEASURED TEMPERATURE
Where temperature is presented in degrees C or
F, based on the C/F setting. Note this parameter
is an unsigned integer of temperature -2721 =
62815
Range = max / min range of selected
thermocouple.
READ ONLY
22 34 MV MEASURED MILLIVOLT
Where this value is scaled in 0.1 mV increments,
i.e. 10001 = 1000.1.
Range = 0 to 2000 mV.
READ ONLY
23 35 HADR AND
SIOSET
LOW BYTE – HOST ADDRESS
BITS 0-7
RANGE = 0 – 255
HIGH BYTE – SIO SETUP
BITS 8 – 9 PARITY SETTING
00 = Even Parity, 7 bits, 1 Stop bit
01 = No Parity, 8 bits, 1 Stop bit
10 = Odd Parity, 7 bits, 1 Stop bit
READ ONLY