Specifications

VersaPro Temperature Controller Page 29
Copyright © 2013, United Process Controls Inc. All rights to copy, reproduce and transmit are reserved
Parameter Name Units or Options Range Description
HIPO – Output High, this alarm
sets the threshold for the
maximum control output allowed
which is set by ALARM 1 VALUE.
LOPO – Output Low, this alarm
sets the threshold for the
minimum control output allowed
which is set by ALARM 1 VALUE.
FALt – Fault, open inputs for mV,
thermocouple or hardware fault.
Prob – Probe, fault active if
impedance or verification are out
of range.
tinE – Time, establishes alarm
contact as the contact used for
the End alarm.
Strt – Start, same as Time.
SOAk – Soak, same as Time.
ALARM 1 VALUE Trigger setpoint value
ALARM 1 ACTION REV, LREV, DIR, LDIR REV = Reverse (N.C.) can be
acknowledged even if the
condition still exists.
LREV = Latched Reverse (N.C.)
can not be acknowledged if the
condition still exists.
DIR = Direct (N.O.) can be
acknowledged even if the
condition still exists.
LDIR = Latched Direct (N.C.) can
not be acknowledged if the
condition still exists.
ALRM 1 TM ON DLY 0 – 250 SECONDS Delay ON time for ALARM1
ALRM 1 TMOFF DLY 0 – 250 SECONDS Delay OFF time for ALARM1
ALARM 2 TYPE Same as ALARM 1
TYPE
Same as ALARM 1 TYPE
ALARM 2 VALUE Trigger setpoint value
ALARM 2 ACTION Same as ALARM 1 ACTION
ALRM 2 TM ON DLY 0 – 250 SECONDS Delay ON time for ALARM2
ALRM 2 TMOFF DLY 0 – 250 SECONDS Delay OFF time for ALARM2
Table 8 Communication Menu (HOST)
Parameter Name Units or Options Range Description
PROTOCOL PROP OR BUSS PROP is Marathon Monitors,
Inc. protocol,
BUSS is Modbus
ADDRESS 1 TO 15 (MSI)
1 TO 255 (MOD)