Specifications

VersaPro Temperature Controller Page 27
Copyright © 2013, United Process Controls Inc. All rights to copy, reproduce and transmit are reserved
Parameter Name Units or Options Range Description
source.
IN A SLOPE Only in Linear mode -999 – 999
-99.9 – 99.9
-9.99 – 9.99
-.999 - .999
Linear slope to scale Input A to
Engineering Units when INPUT A
is selected as the process
source.
This is the slope number in the
linear calculation where: EU =
SLOPE(mV) + OFFSET
See key
TEMP SCALE F OR C Sets temperature scale.
TC FILTER SECONDS 0 – 450 Temperature filter setting in
seconds. Filters the temperature
value with a moving average time
window.
IN B OFFSET Works only in mV
Mode
-999 – 9999 Linear offset to scale Input B to
Engineering Units when INPUT B
is selected at the process source.
This is the offset in used in the
SLOPE(mV) + OFFSET equation.
IN B SLOPE Works only in mV
Mode
-999 – 999
-99.9 – 99.9
-9.99 – 9.99
-.999 - .999
Linear slope to scale Input B to
Engineering Units when INPUT B
is selected as the process
source.
This is the slope number in the
linear calculation where: EU =
SLOPE(mV) + OFFSET
MV FILTER SECONDS 0 – 450 Millivolt filter setting in seconds.
Filters the millivolt reading with a
moving average time window.
Table 5 Calculation Menu (CALC)
Parameter Name Units or Options Range Description
DISPLAY DECML PT Decimal point 0-4 Sets decimal pt., available for
Input A and Input B.
Table 6 Analog Output Menu (AOUt)
Parameter Name Units or Options Range Description
ANALOG 1 UNIT LIN A, LINB B,
TENP, POUT, PO1,
PO2 , PROG
4 to 20mA output.
ANALOG 1 OFFSET Offset for selected
process value or
percent output.
-30.0 to 300.0 for O2
and LIN
-300 to 3000 for
temperature
LOPO for POUT
This is the minimum value of the
process associated with the 4mA
output. The magnitude of this
number is based on the display
resolution.
In POUT mode the offset is fixed
to the LOPO value.
When PROG is selected the
offset is fixed at 0