Versapro Temperature Controller Installation and Operation Handbook Revision 1.
VersaPro Temperature Controller Page 2 Manual #: 022 Rev No: 1.11 Date: 30 October 2013 All trademarks used in this publication are duly marked and the sole property of their respective owners. No attempt at trademark or copyright infringement is intended or implied.
VersaPro Temperature Controller Page 3 TABLE OF CONTENTS TABLE OF CONTENTS ..................................................................................................................................................................... 3 1. Safety and Environment Information .................................................................................................................................... 7 1.1 2. Service and repair .................................................................
VersaPro Temperature Controller Page 4 7.1 Process Alarms ........................................................................................................................................................................... 17 OFF ................................................................................................................................................................................................. 17 Full Scale HI ..............................................................
VersaPro Temperature Controller 12.1 13 Controlling the Timer Remotely ............................................................................................................................................ 39 Tuning ................................................................................................................................................................................ 40 13.1 14 Page 5 What is tuning? ..........................................................................
VersaPro Temperature Controller 20 21 Page 6 19.7 ‘J’ Display EEPROM Values .................................................................................................................................................... 62 19.8 ‘S’ Status Display ................................................................................................................................................................... 62 19.9 ‘W’ Write RAM with EEPROM or Data Values ......................................
VersaPro Temperature Controller 1. Page 7 Safety and Environment Information Please read this section carefully before installing the controller This instrument is intended for industrial applications used in conjunction with Marathon Monitors zirconia oxygen sensors and standard thermocouple types. It is assumed that any installation meets either CE standards for industrial safety or NEC standard wiring practices.
VersaPro Temperature Controller 2.3 Page 8 Enclosure of live parts To prevent hands or metal tools touching parts that may be electrically live, the controller should be installed in an enclosure. The contacts on the rear of the instrument case or finger save but it is still possible for loose wiring, or metal objects to come in contact with live terminal connections. It is recommended that power be removed from the instrument connections before they are disconnected.
VersaPro Temperature Controller 2.9 Page 9 Voltage rating The maximum continuous voltage applied between any of the following terminals must not exceed 250VAC: line or neutral to any other connection; relay output to logic, dc or sensor connections; any connection to ground. The controller should not be wired to a three phase supply with an unearthed star connection. Under fault conditions in this supply could rise above 264VAC with respect to ground and the product would not be safe.
VersaPro Temperature Controller 2.12 Page 10 Grounding of the temperature sensor shield In some installations it is common practice to replace the temperature sensor while the controller is still powered up. Under these conditions, as additional protection against electric shock, we recommend that the shield of the temperature sensor be grounded at one end of the wire. Do not rely on grounding through the framework of the machine. 2.
VersaPro Temperature Controller 4 Page 11 Installation The VersaPro instrument is designed for up to 1/8" panel mounting in a DIN standard opening of 3.62" square (adapter panels available by special order). Required rear clearance is 7.5” to allow for wiring. As with all solid state equipment, the controller should be located away from excessive heat, humidity, and vibration.
VersaPro Temperature Controller Page 12 Figure 2 Wiring Schematic 4.1 Mounting To mount the instrument in a control panel, a hole must be cut 3.62" square in the necessary location on the panel. The following procedure should be followed to mount the VersaPro in the panel. 1) Insert the unit into previously cut out 3.62" square hole in panel. 2) While supporting unit, insert one clamping bracket into the groove on the bottom of unit, and then install the 6-32 set screw.
VersaPro Temperature Controller 5 Page 13 Process Control Options The Versapro is configured to perform as a single loop PID controller for a specific process. This instrument is setup as an oxygen controller. Table 1 Instrument Control Options Function Temperature Linear Input A Linear Input B 6 Description Uses the temperature signals from a thermocouple to control to temperature setpoint.
VersaPro Temperature Controller 6.2 Page 14 Time Proportioning Dual (TD) This mode is used when there are two processes to control that have complementary effects; like heat and cool. The time proportioning dual mode uses two control outputs; one for heat and one for cool. There is never a time when both outputs are on simultaneously. The control loop computes a percent output from -100 to +100%. When positive, the proportioning action applies to the forward output.
VersaPro Temperature Controller Page 15 Deadband allows the process to deviate away from the setpoint by the width of the deadband before any control action occurs. The deadband is adjusted through the Proportional Band in units of the displayed setpoint value. The reset and rate values have no effect in ON/OFF control. Let’s assume the process setpoint is 1500° with a proportional band of 5. This represents a deadband of 5°, which is a band of ±5° around setpoint.
VersaPro Temperature Controller 6.9 Page 16 Direct or Reverse Control Action Control action determines how the output of the controller will react to effect a change on the process. The control action is considered ‘direct’ if an increase in the output produces an increase in the process value. A ‘reverse’ control action would be when an increase in the output produces a decrease in the process.
VersaPro Temperature Controller Page 17 ALARM DISPLAY CONDITION FLASH ERASE Fault alarm, contact assignable FLASH / EE SIZE Fault alarm, contact assignable TEMP OPEN Fault alarm, contact assignable ACTION not clear. Programming error, Reset instrument power, attempt reload. Programming error, Reset instrument power, attempt reload. Check thermocouple for open condition or loose connection. 7.
VersaPro Temperature Controller Page 18 Output Low An alarm is generated any time the control percent output drops below the alarm value. The alarm setting is minimum percent output allowed. Fault An alarm is generated any time an open input occurs on the T/C input. The input is pull up to a maximum value if no input is connected or if the input fails in an open circuit mode. The center display will indicate which of these conditions has caused the alarm.
VersaPro Temperature Controller 7.3 Page 19 Alarm Delay Times Each alarm can have delay ON, delay OFF, or both delays applied. Delays can be applied in increments of a second, up to a maximum of 250 seconds. ON delays are helpful if a known upset in the process can be ignored. This avoids nuisance alarms but still maintains an active alarm if the alarm condition persists following the delay.
VersaPro Temperature Controller 8 Page 20 Serial Interface The VersaPro has a single RS-485 half duplex (two wire) communications port. This port can be configured for either the Marathon protocol of Modbus RTU protocol. Baud rates and parities are selectable. The Modbus protocol only uses a parity of none. See the section on communications for details on both of these protocols. The Versapro can be connected to networks with up to 128 similar devices.
VersaPro Temperature Controller 9 Page 21 Front Panel Operation Figure 3 Versapro Front Panel The LEDS to either side of the LED segment arrays light when the corresponding function is active. COMM flashes when the instrument is properly interrogated over the RS485 port.
VersaPro Temperature Controller 9.1 Page 22 Enter Key If the normal process display is showing on the LED and LCD displays, then pressing the Enter key will cycle the LCD and lower LED through various controller parameters. For the controller, the display will cycle through the following list, the monitor will show only a partial list. TEMP / SETPT TEMP / %OUT REMAINING TIME The temperature process value will always be displayed in the top LED display.
VersaPro Temperature Controller Page 23 as long as the ENTER key is pressed. A new menu can be select only when the menu heading is displayed. You can exit from the Setup mode by pressing the SETUP key at any time. The following tables outline the Setup menus available in the VersaPro Controller and Monitor when the operator presses the SETUP key.
VersaPro Temperature Controller Page 24 The displayed menu is selected by pressing the ENTER key. The first parameter name in the selected menu list will appear in the center display. The upper LED group continues to display the menu name, the center display shows the parameter name, and the lower LED group shows the parameter value. A flashing cursor in the lower LED display indicates which digit can change if the parameter value is numeric. The UP or DOWN arrows increase or decrease the digit value.
Copyright © 2013, United Process Controls Inc. ENTER (HOLD FOR 5 SECONDS) SETUP TC OR MV BREAK TIMER ENABLE LOW PERCENT OUT HI PERCENT OUT CYCLE TIME RATE RESET PROPORTIONAL BAND DIGITAL EVENT MV FILTER ALARM 2 TIME OFF DELAY ALARM 2 TIME ON DELAY ALARM 2 ACTION FIRMWARE REVISION PERCENT OUTPUT COLD JUNCTION (DEG) MILLIVOLT PROB IN MILLIVOLT TEMP IN INFO PRESSING SETUP KEY ANYTIME ESCAPES FROM MENU.
VersaPro Temperature Controller Page 26 Table 3 Control Menu (CtrL) Parameter Name PROCESS SOURCE Units or Options TEMP, INPUT A, INPUT B Range Display range: -500 to 9999 for temp 0 to 100 or EU for Input A 0 to 2000 or EU for Input B CONTROL MODE TP, TC, TD, PP, OF, OC, OD or NON CONTROL ACTION PROPORTIONAL BAND DIR/REV Process Value 0 – 9999 RESET Repeats / min 00.00 – 99.99 RATE Repeats / min 00.00 – 9.
VersaPro Temperature Controller Page 27 Parameter Name Units or Options Range IN A SLOPE Only in Linear mode -999 – 999 -99.9 – 99.9 -9.99 – 9.99 -.999 - .999 TEMP SCALE TC FILTER F OR C SECONDS IN B OFFSET Works only in mV Mode -999 – 9999 IN B SLOPE Works only in mV Mode -999 – 999 -99.9 – 99.9 -9.99 – 9.99 -.999 - .999 MV FILTER SECONDS 0 – 450 Description source. Linear slope to scale Input A to Engineering Units when INPUT A is selected as the process source.
VersaPro Temperature Controller Parameter Name ANALOG 1 RANGE Page 28 Units or Options Span scaling for selected process value or percent output. Range Description 0 or DAC_OFFSET for PROG 0 to 9999 for O2, LIN, and Temp HIPO for POUT 4096 or DAC_SPAN for PROG ANALOG 2 UNIT ANALOG 2 OFFSET ANALOG 2 RANGE LIN A, LINB B, TENP, POUT, PO1, PO2 , PROG Offset for selected process value or percent output. Span scaling for selected process value or percent output.
VersaPro Temperature Controller Parameter Name Page 29 Units or Options Range Description HIPO – Output High, this alarm sets the threshold for the maximum control output allowed which is set by ALARM 1 VALUE. ALARM 1 VALUE ALARM 1 ACTION ALRM 1 TM ON DLY ALRM 1 TMOFF DLY ALARM 2 TYPE ALARM 2 VALUE ALARM 2 ACTION ALRM 2 TM ON DLY ALRM 2 TMOFF DLY LOPO – Output Low, this alarm sets the threshold for the minimum control output allowed which is set by ALARM 1 VALUE.
VersaPro Temperature Controller Parameter Name BAUD RATE PARITY DELAY Page 30 Units or Options Range 1200,2400,4800,9600,19.2K None/Even/Odd NONE / 10 / 20 / 30 Description Default is 19.
VersaPro Temperature Controller Page 31 Pressing the Setup key once at any point in the Setup menu will return the instrument to the normal process display. 9.
VersaPro Temperature Controller 10 Page 32 Digital Input Event The VersaPro has a single digital input. This input is activated by making an isolated contact closure between terminals TB-B 11 and 12. This input is debounced for a momentary closure of at least 0.6 seconds. NOTE Do not connect either terminals TB-B 11 or 12 to any AC or DC potentials. These terminals are internally connected to an isolated 5VDC source. Use only an isolated contact closure across these terminals.
VersaPro Temperature Controller Page 33 Strt (controller only) This selection will start the timer function if the timer is enabled, the setpoint is greater than 0, and one alarm contact is assigned to a timer function. HOLd (controller only) This selection will place the timer in a hold state for as long as the event input is active. End (controller only) This selection will acknowledge the end condition of the timer, clear the end state, and reset the timer for another start.
VersaPro Temperature Controller 11 Page 34 Timer Function The Versapro timer function is available on all process controller options. The timer can operate independently or it can be dependent on the process based on how either alarm contact is configured. The instrument has three possible functions; timer, guaranteed start timer, and guaranteed soak timer. These functions are set through the mode selection of alarm 1 or alarm 2 in the Setup menu.
VersaPro Temperature Controller Page 35 The Rem LED on the front panel will flash while the timer is active in the RUN, HOLD, or END modes. The timer will go inactive when END is acknowledged or if the timer is disabled. The timer can be stopped by pressing the Enter and Right arrow keys during an active RUN state, sending a remote timer setpoint of 0 when the instrument is in remote mode, or by changing the remaining time to zero.
VersaPro Temperature Controller Page 36 11.4 Guaranteed Soak Timer The guaranteed soak timer works in conjunction with the alarm process value. The alarm value is the valid band around the process setpoint. The process must be within the band around the process setpoint to start the timer once it has been activated. If the process passes above or below the alarm band setting, the timer will go to a HOLD state. The timer will be allowed to continue only when the process is within the band setting.
VersaPro Temperature Controller Page 37 IDLE Timer Enable = YES Timer Start = NO Remaining Time = 0 Timer Enable = NO OR Timer Start = NO OR Enter key OR Remote Time Setpt = -1 OR Event(END) = ON END Time Enable = YES Timer Start = YES Display = END Alarm End Alarm = ON Alarm contact = ON Rem Light = Flash Event(STRT) = ON OR Remote Timer SP = -2 OR Enter / Left arrow OR Timer Start = YES AND Timer SP > 0 Timer Enable = NO OR Timer Start = NO OR Remote Time Setpt = -1 OR Enter/Left arrow RUN Timer St
VersaPro Temperature Controller Page 38 Timer will hold if: 1. 2. Digital HOLD event = ON or Alarm Soak or Run deviation is active Timer will run if: 1. Timer Enable = YES and 2. Timer Start = YES and 3. Timer Setpoint > 0 and 4. Digital HOLD event = OFF and 5. Remaining Time > 0 Timer will reset to IDLE without activating END if: 1. Enable = NO or 2. Timer Start = NO or 3. Remote Timer setpoint = -001 or 4. Enter/Left keys pressed Timer goes to END state if: 1.
VersaPro Temperature Controller Page 39 Timer Control Byte Bit 0 1 2 3 4&6 7 Description Timer Enabled Timer Running End Hold N/A Control Purpose Indicates that the timer is enabled in the setup menu. Indicates that the timer has started. Indicates that the timer has timed out and not acknowledged. Indicates that the timer is in hold mode. Not used. Set when the timer is started. Reset when timer has stopped. Is toggled by the Enter + Left Arrow or set by the SIO sending a time setpoint. 12.
VersaPro Temperature Controller 13 Page 40 Tuning Before attempting to tune the instrument make sure you understand the Operation and Setup part of the instrument. This section applies to the controller only. 13.1 What is tuning? Tuning the controller means that the control characteristics of the controller are matched to those of the process in order to obtain hold the process to setpoint.
VersaPro Temperature Controller Page 41 A much higher proportional band may be necessary for extreme lag in the process response. In most cases, the derivative part of the control equation is not necessary. Generally, furnace control can be maintained using only the proportional band and the reset parameters. Make sure you record all operating parameters and keep them in a secure place for later reference. Copyright © 2013, United Process Controls Inc.
Copyright © 2013, United Process Controls Inc. START RESET PROCEDURE HERE. INCREASE PB BY 30% OSCILLATING START PROPORTIONAL BAND PROCEDURE HERE. THESE SETTINGS ASSUME THE SYSTEM IS STABLE WITH A PB OF 30. KEEP INCREASING PB BY 50% IF OSCILLATING. A CHANGE SETPOINT BY 5% RESET X 2 CHANGE SETPOINT BY 5% DECREASE PB BY 10% STABLE IS CONTROL STABLE? ALLOW PROCESS TO STABILIZE SET PB = 30 RESET = .01 RATE = .
VersaPro Temperature Controller 14 Page 43 Scaling Analog Inputs If either input is set to Linear mode the displayed value for that input can be scaled any desired engineering unit. This is helpful if the measured linear value has to be scaled and re-transmitted on one of two analog output channels. Using the equation y = mx + b, where Y is the desired engineering unit to be displayed X is the linear millivolt value M is the Slope of the y/x relationship B is the y intercept 14.
VersaPro Temperature Controller 15 Page 44 Scaling Analog Outputs The analog outputs are scaled to simple offset and span values. For example if analog output 1 were to be scaled for a 0 to 2000° value, the offset value would be 0 and the span value would be 2000. It is possible to narrow the response to the process even if the instrument can measure a larger process range.
VersaPro Temperature Controller 16.1 Page 45 Calibration Displays and Keyboard Operation When entering the Calibration Menu, the operator has to answer one of two questions depending on which I/O functions have to be calibrated. If the CALIBRATION IN prompt is answered with a YES, then the parameters related to the thermocouple input, millivolt input, and cold junction can be changed. If this prompt is skipped by pressing the Enter key, then a second prompt, CALIBRATION OUT is displayed.
VersaPro Temperature Controller Page 46 Calibration of the Thermocouple Input Calibration procedure: 1. Connect terminals TB-B 1, 2 to an isolated, stable millivolt source calibrator using standard copper wire, 20 AWG is sufficient. 2. Set the calibrator output to 0.00 mV. 3. Activate the calibration mode by entering the SETUP menus, selecting the Calibration menu and changing Calibration IN - NO to YES. 4. Use the Enter key to select the TC ZERO mode. 5.
VersaPro Temperature Controller Page 47 Table 13 Usable Thermocouple Range (°F) T/C type B E J K N R S T Minimum Value (°F) 800 -440 -335 -340 -325 300 * 300 * -380 Maximum Value (°F) 3270 1830 1400 2505 2395 3210 3210 755 * Due to the extreme non-linearity of low level signals, using type R and S below 300° F is not recommended. Calibration of the Analog Output Channels The same calibration procedure can be used for either output channel. Calibration procedure: 1.
VersaPro Temperature Controller 17 Communications 17.1 Modbus Page 48 The MODBUS protocol describes an industrial communications and distributed control system (DCS) that integrates PLCs computers, terminals, and other monitoring, sensing, and control devices. MODBUS is a Master/Slave communications protocol, whereby one device, (the Master), controls all serial activity by selectively polling one or more slave devices.
VersaPro Temperature Controller Page 49 The Function Code field tells the addressed slave what function to perform. MODBUS function codes are specifically designed for interacting with a PLC on the MODBUS industrial communications system. Command codes were established to manipulate PLC registers and coils. As far as the VersaPro is concerned, they are all just memory locations, but the response to each command is consistent with Modbus specifications.
VersaPro Temperature Controller Page 50 The Versapro will respond to several error conditions. The three exception codes that will generate a response from the instrument are: 01 – Illegal Function 02 - Illegal Data Address 03 – Illegal Data Value 04 – Slave Device Failure The response from the Versapro with an exception code will have the most significant bit of the requested function set followed by the exception code and the high and low CRC bytes. 17.
VersaPro Temperature Controller Page 51 Table 14 10Pro / 10Pro-T Command Set COMMAND LETTER p (low case) o (low case) i (low case) h (low case) I (upper case as in Instrument) J (upper case) l (lower case as in limits) m (low case) P (upper case) Process ( temperature) Read Auto / Manual mode Read Remote / Local Read Remote Process Setpoint Read Auto Process Setpoint Update Process Setpoint Temporarily Update Process Setpoint Permanently Read Actual Process Timer Same Same Read Remote Time Setpoint Read
VersaPro Temperature Controller Page 52 Transmit from Host or Master Add F 0x46 Prefix A 0x41 Cmd I 0x49 D1 1 0x31 D2 4 0x34 D3 5 0x35 D4 0 0x30 Delim 0x00 LRC N 0x4E 0x04 Response from 10Pro 0x06 17.3 Add F 0x46 Prefix A 0x41 Cmd I 0x49 D1 1 0x31 D2 4 0x34 D3 5 0x35 D4 0 0x30 Delim 0x00 LRC H 0x48 0x04 Instrument Type ‘U’ Command Set The MSI (Marathon Monitors Inc.
VersaPro Temperature Controller Page 53 Instrument Response 0x06 Add Prefix Cmd 2 0x32 U 0x55 x 0x78 Table # 00 0x30 0x30 Par # 0A 0x30 0x41 Data Delim $ 0x24 D1 D2 D3 D4 Delim LRC 0 0x30 0 0x30 1 0x31 4 0x34 0x00 J 0x4A 0x04 The response from the instrument includes the ‘$’ character. This characters acts as the data delimiter, which separates the parameter data from the parameter address.
VersaPro Temperature Controller Page 54 Response from Instrument ACK 0x06 Add Prefix Cmd 1 0x31 U 0x55 X 0x58 Table # 00 0x30 0x30 Par # 06 0x30 0x36 Data Delim $ 0x24 D1 D2 D3 D4 Delim LRC 0 0x30 0 0x30 0 0x30 0 0x30 NULL 0x00 18 0x18 EOT 0x04 The parameters for the Versapro are listed in the manual appendix. This listing includes the parameter name, number, and a short description that includes bit and byte mapping information.
VersaPro Temperature Controller Page 55 A U * tt bb $ ddd-------ddd CC D L E (E)End of Transmission (EOT) HEX(04) (L) LRC is the result of an XOR function performed on all previous character in the messeage. (D) Delimter marks the end of DATA and signals the up coming EOT character. NUL HEX(00) or Backspace HEX(08)* *If LRC was going to be an EOT HEX(04) then D = HEX(08). (CC) MOD 256 checksum of data characters ASCII values in two (2) HEX digits.
VersaPro Temperature Controller Page 56 Parameter 7 Parameter 8 Parameter 9 Parameter 10 Parameter 11 Parameter 12 Parameter 13 Parameter 14 Parameter 15 Parameter 16 Parameter 17 Parameter 18 Parameter 19 Parameter 20 Parameter 21 Parameter 22 Parameter 23 Parameter 24 MOD 256 Delimiter LRC EOT 03B6 07D0 0000 0C00 03E8 03E8 0000 0000 0000 0000 0060 1C25 00F3 3C69 0001 03E8 0000 3D62 BF 00 1B 04 30 33 42 36 30 37 44 30 30 30 30 30 30 43 30 30 30 33 45 38 30 33 45 38 30 30 30 30 30 30 30 30 30 30 30 30 30
VersaPro Temperature Controller 18 Page 57 Troubleshooting Questions This section is organized alphabetically by the functional name of various instrument operations and features. Some explanations may be listed in more than one category since the problem can be approached from several different points of view. Each problem is presented as a question for typical problems that may be encountered. In most cases the problem can be resolved by changing a setup parameter in the instrument. 18.
VersaPro Temperature Controller 18.3 Page 58 Digital Communications How come I have communications problems with an instrument address following a Versapro address setting. If the timer function has been enabled and the Versapro host protocol is set to ‘Prop’ for the Marathon protocol, the instrument will take the next host address setting to respond with the timer parameters.
VersaPro Temperature Controller 19 Page 59 Versapro Monitor Mode The Versapro’s internal EEPROM can be reprogrammed when placed in Monitor Mode. This mode allows the user to perform checks and set default conditions in the instrument by using a RS232 to RS485 converter and the popular Windows program HyperTerminal. It is necessary to enter this mode when a CPU has been reprogrammed or if a checksum fault has occurred in EEPROM.
VersaPro Temperature Controller Page 60 Bits per second: 19200 Data bits: 7 Parity: EVEN Stop bits: 1 Flow control: None Select the File \ Properties \ Settings tabs and make the following selections; Select the ‘Terminal Keys’ button Select the ‘Ctrl+H’ button Set ‘Emulation’ to ANSI Set ‘Telnet terminal ID’ to ANSI Set ‘Backscroll buffer lines’ to 500 Click on the ASCII Setup… button; Set ‘Line delay’ to 25 msec Set ‘Character delay’ to 0 msec Click on the ‘OK’ button to escape the Connections window.
VersaPro Temperature Controller Command D J K L S W X Z Page 61 Command Description Displays 16 rows by 16 bytes of memory Displays all values in EEPROM Programs EEPROM for RAM values Loads RAM EEPROM area with FLASH defaults Displays status of processor Writes a byte from EEPROM to RAM EEPROM mirror or writes data to RAM.
VersaPro Temperature Controller Page 62 The ‘K’ command is a single character command that copies the values in the RAM mirror into the EEPROM. The EEPROM is completely erased before any values are written. There is no display that is generated while this function is executed. It is necessary to wait about 5 seconds for the display prompt (>) to return before another command is issued. 19.
VersaPro Temperature Controller Page 63 Figure 13 ‘S’ and ‘D’ Commands 19.12 Loading Default Values The most common use of the Monitor Mode is to re-set or load the processor’s internal EEPROM with default values and re-calculate the EEPROM checksum. This is done with a series of commands starting with the ‘L’ command. The instrument holds default operational parameters in FLASH. This area of memory is mapped the same way the EEPROM memory is.
VersaPro Temperature Controller Page 64 Figure 14 ‘L’ and ‘K’ Commands At the prompt, type in the character ‘X’ and press Enter. The ‘X’ command causes the instrument to exit the Monitor Mode, reset, and return to operation mode. Check the instrument parameter settings and verify the input and output calibration settings. 19.13 What if an error occurs If you receive check sum errors following the ‘L’ or ‘K’ commands, retry these commands.
VersaPro Temperature Controller 20 Page 65 Technical Specification 20.1 Environmental ratings Panel sealing: Instruments are intended to be panel mounted. The rating of panel sealing is IP64. Operating temperature: 0 to 55oC. Ensure the enclosure provides adequate ventilation. Relative humidity: 5 to 95%, non-condensing. Atmosphere: The instrument is not suitable for use above 2000m or in explosive or corrosive atmospheres. 20.
VersaPro Temperature Controller Parity: Page 66 Even, odd, or None Control Mode Time Proportioning Single Contact Direct Time Proportioning Single Contact Reverse Time Proportioning Dual Contact Direct Time Proportioning Dual Contact Reverse Time Proportioning Complement Contact Direct Time Proportioning Complement Contact Reverse Position Proportioning Direct Position Proportioning Reverse On / Off Direct On / Off Reverse On / Off Dual Direct On / Off Dual Reverse On / Off Complement Direct On / Off Com
VersaPro Temperature Controller Storage Temperature Operating and Storage Humidity Page 67 -40 °C to 85 °C (-40 to 185 F) 85% max relative humidity, noncondensing, from –20 to 65°C Note: Specifications may change without notification. Copyright © 2013, United Process Controls Inc.
VersaPro Temperature Controller 21 Page 68 Versapro Memory Map NOTE: Modbus refers to the hexadecimal address location. These parameters are formatted as unsigned 16 bit integers. Any real number such as temperature can be evaluated as a signed number, other parameters are bit mapped words that must be evaluated as single bits are bit groups.
VersaPro Temperature Controller HEX DEC 08 8 PARAMETER ALRMMD1 Page 69 BLOCK 0 DESCRIPTION determine the real alarm value. Range = -999 to 9999.
VersaPro Temperature Controller HEX DEC PARAMETER Page 70 BLOCK 0 DESCRIPTION BIT 4 ACTION CONTROL 0 = DIRECT 1 = REVERSE READ/WRITE BIT 5 NO LATCH = 0 LATCHED = 1 0A 10 PB 0B 11 RESET 0C 12 RATE 0D 13 CYCTIM 0E 14 RSTC 0F 15 HIPO 10 16 LOPO 11 17 CONMD BIT 6 – 15 SPARE Proportional Band – Based on display units Range = 1 to 9999 Default = 20 Reset – Based on seconds Range = OFF to 9999 Where 0020 is assumed to be 00.
VersaPro Temperature Controller HEX DEC PARAMETER Page 71 BLOCK 0 DESCRIPTION 001 = TIME PROP W/ COMPLEMENT 010 = TIME PROP, DUAL 011 = SPARE 100 = ON/OFF 101 = ON/OFF W/ COMPLEMENT 110 = ON/OFF, DUAL 111 = VALVE POSITIONING W/ FEEDBACK READ/WRITE BIT 8 = DIRECT (0) OR REVERSE (1) ACTING BIT 9 = MANUAL (0) OR AUTO (1) BIT 10 = SETPT LOCAL (0) OR SETPT REMOTE (1) BIT 11 = MONITOR (0), CONTROLLER (1) BITS 12 = SENSOR BREAK OUTPUT 0 (0), OUTPUT HOLD (1) 12 18 CONFIG0 13 19 CTRLOUT Copyright © 2013,
VersaPro Temperature Controller HEX DEC 14 20 ALRMT1 15 21 ALRMT2 16 22 FAULT 17 23 CJTRM HEX 18 DEC 24 PARAMETER PARAMETER ASRC Copyright © 2013, United Process Controls Inc. Page 72 BLOCK 0 DESCRIPTION 1000 = 100.0% and 64536 = -100.
VersaPro Temperature Controller HEX DEC PARAMETER Page 73 BLOCK 1 DESCRIPTION READ/WRITE *For Programmable, write required output value into DACV1, where DACV1 = 0 is minimum output and DACV1 = 4096 is maximum output.
VersaPro Temperature Controller HEX DEC PARAMETER 1D 29 TEMPFIL 1E 30 MVFIL 1F 31 CONFIG2 20 32 COLDJCT 21 33 TEMP 22 34 MV 23 35 HADR AND SIOSET Page 74 BLOCK 1 DESCRIPTION READ/WRITE Analog Output of 20 mA. The source value is based on the selection in ASRC upper byte where Temperature Input Filter in seconds Range = 0 to 3276. The higher the number the faster the reading update. DEFAULT = 1000 Millivolt Input Filter in seconds Range = 0 to 3276.
VersaPro Temperature Controller HEX DEC PARAMETER Page 75 BLOCK 1 DESCRIPTION BITS 10 – 11 RESPONSE DELAY 0 = No delay applied to response 1 = 10ms delay applied to response 2 = 20ms delay applied to response 3 = 30ms delay applied to response READ/WRITE BITS 12 – 14 BAUD SELECT 000 = 76.8K 001 = 38.4K 010 = 19.
VersaPro Temperature Controller HEX DEC PARAMETER 2A 42 PBOMV 2B 43 PBOTC 2C 44 PBORT 2D 45 PREMT 2E 46 VGAS 2F 47 PMC HEX 30 DEC 48 PARAMETER PTINT 31 49 PTRECT 32 50 BOTM 33 51 BOREC Copyright © 2013, United Process Controls Inc. Page 76 BLOCK 1 DESCRIPTION available for TruCarb. LAST MILLIVOLTS DURING PROBE BURN OFF RANGE = -99 TO 2048 i.e. 1018 = 1018 mV Available for Redox, Carbon, Dewpoint, and TruCarb. LAST TEMPERATURE DURING PROBE BURNOFF RANGE = 0 to 3000 i.e.
VersaPro Temperature Controller HEX DEC PARAMETER 34 52 VSTD 35 53 VTOL 36 54 TAVE 37 55 TDEL1 38 56 TDEL2 39 57 TMIN 3A 3B 3C 3D 3E 58 59 60 61 62 TC_ZERO TC_SPAN MV_ZERO MV_SPAN DAC_OFFSET_1 Copyright © 2013, United Process Controls Inc. Page 77 BLOCK 2 DESCRIPTION RANGE = 0 to 999 DEFAULT = 30 Burnoff function available for Redox, Carbon, and Dewpoint. VERIFY TEST GAS STANDARD For oxygen process this is the test standard value used to verify the probe.
VersaPro Temperature Controller HEX 3F 40 41 42 DEC 63 64 65 66 43 44 67 68 ANUM BZERO 45 46 69 70 BNUM TIME CONTROL AND EVNT 47 71 PARAMETER DAC_SPAN_1 DAC_OFFSET_2 DAC_SPAN_2 AZERO COMP Copyright © 2013, United Process Controls Inc.
VersaPro Temperature Controller Page 79 Reach us at www.group-upc.com United Process Controls brings together leading brands to the heat treating industry including Waukee Engineering, Furnace Control, Marathon Monitors and Process-Electronic. We provide prime control solutions through our worldwide sales and services network with easy-toaccess local support. UNITED PROCESS CONTROLS INC. MMI PRODUCTS PLANT 3100 East Kemper Road, Cincinnati, Ohio 45241, U.S.A.