Unit installation
247585-UAI-A-0706
Unitary Products Group 5
TWO STAGE GAS VALVE MODELS
TWO STAGE GAS VALVE MODELSTWO STAGE GAS VALVE MODELS
TWO STAGE GAS VALVE MODELS
NOTE: 
The  regulated  outlet  pressures,  both  low  and  high,
have  been  calibrated  at  the  factory.  Additional  pressure
adjustment should not be necessary. If adjustment is neces-
sary,  set to the following specifications. After adjustment,
check for gas leakage.
1. Refer  to  Figure  2  for  location  of  pressure  regulator
adjustment cap  and adjustment screws  on main gas
valve.
2. Turn gas and electrical supplies on and follow the oper-
ating instructions to place the unit back in operation.
3. Adjust manifold pressure by adjusting gas valve regula-
tor screw for the appropriate gas per the following:
:
IMPORTANT - 
If gas valve regulator is turned in (clockwise),
manifold pressure is increased. If screw is turned out (coun-
terclockwise), manifold pressure will decrease.
4. After the manifold pressure has been adjusted, re-calcu-
late  the  furnace  input  to  make  sure  you  have  not
exceeded the specified input on the rating plate. Refer to
“CALCULATING  THE  FURNACE  INPUT  (NATURAL
GAS)”. Refer to calculations on Page 6.
5. Once the correct BTU (kW) input has been established,
turn the gas valve to OFF and turn the electrical supply
switch  to  OFF;  then  remove  the  flexible  tubing  and  fit-
tings from the gas valve pressure tap and the pressure
reference hose from the right side of the burner box and
tighten  the  pressure  tap  plug  using  the  3/32”  (2.4  mm)
Allen  wrench.  Replace  the  burner  box  front  cover  (if  it
was  removed)  and  place  the  pressure  reference  hose
back on the gas valve.
6. Turn  the  electrical  and  gas  supplies  back  on,  and  with
the burners in operation, check for gas leakage around
the  gas  valve  pressure  port  for  leakage  using  an
approved  gas  detector,  a  non-corrosive  leak  detection
fluid, or other leak detection methods.
CALCULATING THE FURNACE INPUT
CALCULATING THE FURNACE INPUTCALCULATING THE FURNACE INPUT
CALCULATING THE FURNACE INPUT
(NATURAL GAS)
(NATURAL GAS)(NATURAL GAS)
(NATURAL GAS)
NOTE: 
Burner orifices are sized to provide proper input rate
using natural gas with a heating value of 1030 BTU/Ft
3
. If the
heating value of your gas is significantly different, it may be
necessary to replace the orifices.
1. Turn  off  all  other  gas  appliances  connected  to  the  gas
meter.
2. At the gas meter, measure the time (with a stop watch) it
takes to use 2 cubic ft. (0.0566 m
3
) of gas.
3. Calculate the furnace input by using one of the following
equations.
CALCULATING THE FURNACE INPUT
CALCULATING THE FURNACE INPUTCALCULATING THE FURNACE INPUT
CALCULATING THE FURNACE INPUT
(PROPANE GAS)
(PROPANE GAS)(PROPANE GAS)
(PROPANE GAS)
NOTE: 
Burner  orifices are  sized  to  provide  the  proper input
rate using propane gas with a heating value of 2500 BTU/Ft
3
.
If the heating value of your gas is significantly different, it may
be  necessary  to  replace  the  orifices  with  different  size  ori-
fices.  Follow  the  procedure  below  to  calculate  the  furnace
input.
1. Turn off all gas appliances connected to the gas meter.
2. Start the furnace.
3. Use a stop watch to measure the time it takes for the fur-
nace to burn 1 cubic ft. of gas.
4. Calculate the furnace input by using one of the following
equations.
An overpressure protection device, such as a pres-
sure  regulator,  must  be  installed  in  the  gas  piping
system upstream of the furnace and must act to limit
the downstream pressure to the gas valve so it does
not exceed 0.5 PSI (14” w.c.) (3.48 kPa). Pressures
exceeding  0.5  PSI  (14”  w.c.)  (3.48  kPa)  at  the  gas
valve will cause damage to the gas valve, resulting
in a fire or explosion or cause damage to the furnace
or some of its components that will result in property
damage and loss of life.
FIGURE 1 - 
Single Stage Gas Valve
INLET
WRENCH
BOSS
INLET
PRESSURE
PORT
ON
OFF
ON/OFF SWITCH
(Shown in ON position)
MAIN REGULATOR
ADJUSTMENT
OUTLET
OUTLET
PRESSURE
PORT
VENT PORT
The  manifold  pressure  must  be  checked  with  the
screw-off cap for the gas valve pressure regulator in
place.  If not,  the manifold  pressure setting  could
result  in  an  over-fire condition.  A  high  manifold
pressure will cause an over-fire condition, which
could  cause  premature  heat  exchanger  failure.  If
the manifold pressure is too low, sooting and even-
tual clogging of the heat exchanger could occur. Be
sure  that  gas  valve  regulator  cap  is  in  place  and
burner box to gas valve pressure reference hose is
connected.
FIGURE 2 - 
Two Stage Gas Valve
INLET
WRENCH
BOSS
INLET
PRESSURE
PORT
ON OFF
SWITCH
LOW STAGE REGULATOR
ADJUSTMENT
OUTLET
OUTLET
PRESSURE
PORT
VENT
PORT
HIGH STAGE REGULATOR
ADJUSTMENT








