Unit installation
247585-UAI-A-0706
4 Unitary Products Group
ADJUSTMENT OF MANIFOLD GAS PRESSURE
ADJUSTMENT OF MANIFOLD GAS PRESSUREADJUSTMENT OF MANIFOLD GAS PRESSURE
ADJUSTMENT OF MANIFOLD GAS PRESSURE
FOR 80% FURNACES
FOR 80% FURNACESFOR 80% FURNACES
FOR 80% FURNACES
Inlet  and  manifold  gas  pressure  may  be  measured  by  con-
necting the “U” tube manometer to the gas valve with a piece
of  tubing.  Follow  the  appropriate  section  in  the  instructions
below. Refer to Figure 1 for a drawing of the locations of the
pressure ports on the gas valve.
Turn gas off at the ball valve or gas cock on gas supply
line before the gas valve. Find the pressure ports on the
gas valve marked Out P and In P.
1. The manifold pressure must be taken at the port marked
OUT P.
2. The gas line pressure must be taken at the port marked
IN P.
3. Using  a  3/32” (2.4  mm)  Allen  wrench,  loosen  the  set
screw  by  turning  it  1  turn  counter  clockwise.  DO  NOT
REMOVE  THE  SET  SCREW  FROM  THE  PRESSURE
PORT.
Read the inlet gas pressure
Connect the positive side of the manometer to the IN P Tap
on the gas valve. Do not connect any tubing to the negative
side of the manometer, as it will reference atmospheric pres-
sure. Refer to Figure 1 for connection details.
1. Turn gas and electrical supplies on and follow the oper-
ating instructions to place the unit back in operation.
IMPORTANT - The inlet gas pressure operating range table
specifies what the minimum and maximum gas line pressures
must be for the furnace to operate safely. The gas line pres-
sure MUST BE a minimum of
• 7” W.C. (1.74 kPA) for Natural Gas
• 11” W.C. (2.74 kPA) for Propane (LP) Gas
in order to obtain the BTU input specified on the rating plate
and/or  the  nominal  manifold  pressure  specified  in  these
instructions and on the rating plate.
2. Once the correct  gas inlet pressure  has been  estab-
lished, see Table 13, turn the gas valve to OFF and turn
the electrical supply switch to OFF; then remove the flex-
ible tubing from  the  gas  valve pressure tap and tighten
the  pressure tap plug  using  the  3/32”  (2.4  mm) allen
wrench.
3. Turn  the  electrical  and  gas  supplies  back  on,  and  with
the burners in operation, check for gas leakage around
the  gas  valve  pressure  port  for  leakage  using  an
approved non-corrosive gas leak detection fluid, or other
non-flammable leak detection methods.
Read the manifold gas pressure
Connect  the  positive  side  of  the  manometer  to  the  adapter
previously installed in  the  OUT P  Tap  on  the  gas  valve. Do
not connect any tubing to the negative side of the manome-
ter, as it will reference atmospheric pressure. Refer to Figures
3 and 4 for connection details.
IMPORTANT  -  The  cap  for  the  pressure  regulator  must  be
removed  entirely  to  gain access  to the adjustment  screw.
Loosening or  tightening  the  cap  does  not  adjust  the  flow of
gas.
NOTE:  The  regulated  outlet  pressures,  both  low  and  high,
have  been  calibrated  at  the  factory.  Additional  pressure
adjustment should not be necessary. If adjustment is neces-
sary, set to the following specifications. After adjustment,
check for gas leakage.
1. Refer  to  Figure  1  for  location  of  pressure  regulator
adjustment cap and adjustment screws on main  gas
valve.
2. Turn gas and electrical supplies on and follow the oper-
ating instructions to place the unit back in operation.
3. Adjust manifold pressure by adjusting gas valve regula-
tor screw for the appropriate gas per the following:
SINGLE STAGE GAS VALVE MODELS
SINGLE STAGE GAS VALVE MODELSSINGLE STAGE GAS VALVE MODELS
SINGLE STAGE GAS VALVE MODELS
1. Refer to Figure 1 or 2 for location of pressure regulator
adjustment  cap  and  adjustment  screw  on  main  gas
valve.
2. Turn gas and electrical supplies on and follow the oper-
ating instructions to place the unit back in operation.
3. Adjust manifold pressure by adjusting gas valve regula-
tor screw for the appropriate gas per the following table.
TABLE 1: 
Inlet Gas Pressure Range
INLET GAS PRESSURE RANGE
Natural Gas Propane (LP)
Minimum 4.5” W.C. (1.12 kPa) 8.0” W.C. (1.99 kPa)
Maximum 10.5” W.C. (2.61 kPa) 13.0” (3.24 kPa) W.C.
TABLE 2: 
Nominal Manifold Pressure -Two Stage Valve (High Fire) 
or Single Stage Valve
SINGLE/SECOND STAGE MANIFOLD PRESSURES (IN WC)
Altitude (feet)
0-7999 8000-8999 9000-9999
Gas Heating Value
(BTU/cu ft.)
2500 (LP) 9.8 8.2 7.5
SINGLE/SECOND STAGE MANIFOLD PRESSURES (KPA)
Altitude (m)
0-2437 2438-2742 2743-3048
Gas Heating Value
(MJ/cu m)
93.2 (LP) 2.44 2.03 1.86
TABLE 3: 
Nominal Manifold Pressure - Two Stage Valve (Low Fire)
FIRST STAGE MANIFOLD PRESSURES (IN WC)
Altitude (feet)
0-7999 8000-8999 9000-9999
Gas Heating Value
(BTU/cu ft.)
2500 (LP) 4.1 3.8 3.5
FIRST STAGE MANIFOLD PRESSURES (KPA)
Altitude (m)
0-2437 2438-2742 2743-3048
Gas Heating Value
(MJ/cu m)
93.2 (LP) 1.03 0.95 0.87








