Operating instructions
035-17452-000 Rev. B (0106)
2 Unitary Products Group
TABLE 1: List of Approved Model Series
Approved Furnace
Model Series
Tile Lined Chimney Kit
Model Number
Furnace
Flue Outlet Size
BGU050* - 125*, FG8050* - 125*,
G8C050* - 125*, GF8050* - 125*
1CK0603 3”
BGU150*, FG8D150*, GF8150D*
FC8*, FL8*, GM8*, GR8*, GY8*,
G8*, L8*, P*D*, P4HU,
LC8*, LL8*,LM8*, P*8*, XYF8*, XYG8*
1CK0604 4”
FIGURE 1: Chimney Inspection Chart
Is the crown missing mortar or brick?
Is the crown missing mortar or brick?
Is liner and top seal in good
condition?
Is there mortar, tile, fuel oil residue
or other debris in the cleanout?
Is the clay tile misaligned, have
missing sections, or gapped?
Is the chimney exposed to the
outdoors below the roofline?
The chimney is acceptable
to use with this kit.
Line chimney with the properly sized,
listed flexible metal liner or Type-B vent
per NFGC or National Canadian Code
vent sizing tables, and liner or vent
manufacturer’s installation instructions
.
Rebuild crown
Repair liner or top seal or
reline chimney as necessary
Is the chimney serving one or
more draft hooded appliance(s)?
Is the chimney properly sized
for these instructions?
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
No
No
No
No
No
No
Yes
Repair
Reline